Honeywell 7300 Thermostat User Manual

Home

href="
Wireless Communication Card for  
TB7200/7300/7600 Series  
Communicating Thermostats  
INSTALLATION INSTRUCTIONS  
APPLICATION  
The Honeywell wireless communication card (TB-VWG-APP-1014)  
and related WirelessStatNetwork.jar driver file are designed for use  
with WEBs-AX controllers to integrate Honeywell TB7200, TB7300,  
and TB7600 Series wireless thermostats into a WEBs-AX building  
control system. This card allows the integrator to work in the familiar  
Workbench tool set using any of the TB7200, TB7300, and TB7600  
Series wireless thermostats.  
The wireless communication card and TB7200, TB7300, and  
TB7600 Series thermostats use ZigBee® wireless mesh. The  
wireless thermostats are ideal for retrofit applications where the  
addition of communicating field bus wiring in the building space is  
difficult or cost prohibitive.  
This document covers the mounting of the wireless communication  
card in a WEBs-AX controller.  
BEFORE YOU BEGIN  
Included in the wireless card package you should find the following items:  
The wireless communication card  
A local antenna  
A #2 phillips screwdriver is required for installation.  
To add the Honeywell wireless thermostat network to a WEBs system, you need two .jar files for the WEBStation-AX.  
You can download these files from the Honeywell Buildings Forum at buildingsforum.honeywell.com.  
.
Jar Files Needed:  
Wireless Thermostat Network Driver: WirelessTstat.jar, version 4.0.4.8 or greater.  
Wireless Thermostat Device and Point Configuration: Wireless TstatDevices.jar, version 4.0.4.8 or greater.  
More Information  
We recommend downloading the Honeywell Wireless Installation and Integration Reference Guide for the TB7200,  
TB7300, and TB7600 Series Thermostats (Form No. 63-4522) from http://customer.honeywell.com before you begin  
installation.  
6
2-2020-03  
href="
WIRELESS COMMUNICATION CARD FOR TB7200/7300/7600 SERIES COMMUNICATING THERMOSTATS  
INSTALLATION  
CAUTION  
Erratic System Operation Hazard.  
Failure to follow proper wiring practices can introduce disruptive electrical interference (noise). Keep wiring at  
least one foot away from large inductive loads such as motors line starters, lighting ballasts, and large power  
distribution panels.  
Shielded cable is required in installations where these guidelines cannot be met.  
Ground shield only to grounded controller case.  
IMPORTANT  
All wiring must comply with local electrical codes and ordinances or as specified on installation wiring dia-  
grams.  
Power to the WEBs-AX controller must be OFF when installing or removing the wireless communication card or  
damage will occur! Also, be careful to plug the wireless communication card into its connector properly (pins  
aligned).  
Only one the wireless communication card can be installed in a WEBs-AX controller. Always install the card in option  
slot 1 in WEB-2xx and WEB-6xx models. Option slot 1 or 2 can be used on WEB-7xx models.  
Mounting the wireless communication card on a WEBs-AX controller  
1
.
Remove power from the controller.  
Remove the controller cover. To do this, press in the four tabs on both ends of the unit, and lift the cover off.  
2
.
NOTE: If other expansion accessory modules are  
plugged into the controller, you may need to  
slide them away from the unit to get to the cover  
tabs.  
BATTERY  
SCREWS (4)  
ASSEMBLY  
(
INCLUDES  
UNPLUG  
CABLE AND  
BRACKET)  
BATTERY HERE  
OPTION  
SLOT 2  
AREA  
3.  
Remove the battery and bracket assembly by taking out  
the four screws. (Fig. 1)  
4
5
6
.
.
.
Unplug the battery from the connector on the controller.  
Remove screws and battery assembly.  
Remove the front blanking end plate for option slot 1  
WEB/  
CP-201/  
00/  
700  
(
Com1) on WEB-2xx and WEB-6xx controllers and  
6
option slot 1 or 2 (Com3 or Com4 in the WEBStation-AX)  
on WEB-7xx controllers.  
BLANKING  
END PLATE  
7.  
Carefully insert the pins of the wireless communication  
card into the appropriate socket. The mounting holes on  
the option board should line up with the standoffs on the  
base board. If they do not, the connector is not properly  
aligned. Press until the option card is completely seated.  
Plug the battery cable back into the battery connector on  
the controller  
Set the battery and bracket assembly back over the  
option card slots, with the mounting holes aligned with  
the standoffs.  
OPTION  
SLOT 1  
AREA  
M32538  
Fig. 1. Removing battery and bracket assembly  
8
.
.
9
1
0. Re-fasten screws through battery bracket the four hold-  
ing screws through. DO NOT over tighten.  
1. Replace the controller cover.  
1
1
2. Install the antenna. (Fig. 2)  
Fig. 2. Antenna location  
62-2020—03  
2
href="
WIRELESS COMMUNICATION CARD FOR TB7200/7300/7600 SERIES COMMUNICATING THERMOSTATS  
STATUS LED INDICATORS  
See the table below for status indicators on the wireless communication card.  
Table 1. Status LED Indicators  
Indicator  
Description  
1
2
3
x 200ms short blink  
x 200ms short blinks  
x 200ms short blinks  
Power on  
Power on and card memory initialized properly  
Power on, card memory initialized properly and serial communication with WEBs-AX  
controller main board active  
4
x 200ms short blinks  
Power on, card memory initialized properly, serial communication with WEBs-AX  
controller main board active and wireless networks started successfully  
4
1
x 200ms short blinks and Power on, card memory initialized properly, serial communication with WEBs-AX  
x 1500ms long blink controller main board active, wireless networks started successfully and wireless  
communication with wireless thermostats active  
SPECIFICATIONS  
Thermostat Compatibility: TB7200, TB7300, and TB7600 Series wireless thermostats  
Network Protocol: ZigBee wireless mesh  
WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and WEB-7xx  
Platform:  
WEB-2xx and WEB-6xx - WEBStation-AX 3.0 or later  
WEB-7xx - WEBStation-AX 3.5 or later  
Number of Thermostats Supported:  
WEB-2xx - up to 30 wireless thermostats  
WEB-6xx & WEB-7xx - up to 50 wireless thermostats  
NOTE: The maximum number of thermostats supported by a WEBs-AX controller is dependent on resources  
available at the controller.  
Connections: 2 x 15 gold plated header for serial connection to compatible WEBs-AX controller and SMA connector  
for antenna.  
Input: Reset button  
Status LED: 1 green LED  
Board Dimensions: 2.2 in. x 1.75 in. (excluding antenna)  
Approximate Shipping Weight: .02 lb  
Agency Approvals: Compliant with FFC Part 15, Subpart C; C-Tick: EN55022:2006, IEC 61326-1:2005  
3
62-2020—03  
href="
WIRELESS COMMUNICATION CARD FOR TB7200/7300/7600 SERIES COMMUNICATING THERMOSTATS  
DISCLAIMER  
NO WARRANTY. Honeywell, Inc. (herein after referred to as “Honeywell”) makes no warranty as to the accuracy of or  
use of this technical documentation. Any use of the technical documentation or the information contained therein is  
solely at the risk of the user.  
Documentation may include technical or other inaccuracies or typographical errors. Honeywell reserves the right to  
make changes to this document without prior notice, and the reader should in all cases consult Honeywell to determine  
whether any such changes have been made. The information in this publication does not represent a commitment on  
the part of Honeywell.  
Honeywell shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use  
of this material.  
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the  
Honeywell wireless gateway.  
Honeywell, Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices.  
Although Honeywell has taken many precautions in assuring the robustness of the TB7200/7300/7600 Series wireless  
thermostat product line and associated network access point. Please note; future application of additional wireless  
devices utilizing the same or similar channels and / or frequencies may degrade performance of overall system and / or  
reliability.  
Non-approved modifications or changes made to the wireless communication card or wireless thermostats may void the  
FCC compliance of the and wireless thermostats.  
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device  
may not cause harmful interference, and (2) This device must accept any interference received, including interference  
that may cause undesired operation.  
NOTE: The manufacturer is not responsible for any radio or tv interference caused by unauthorized modifica-  
tions to this equipment. Such modifications could void the user’s authority to operate the equipment.  
Automation and Control Solutions  
Honeywell International Inc.  
1
985 Douglas Drive North  
®
U.S. Registered Trademark  
© 2011 Honeywell International Inc.  
2-2020—03 M.S. Rev. 09-11  
Printed in United States  
Golden Valley, MN 55422  
customer.honeywell.com  
6

Honeywell 8162 Thermostat User Manual

White Rodgers T7350 Thermostat User Manual

Honeywell T8624C Thermostat User Manual

White Rodgers 37 5148B Thermostat User Manual

Bryant T1 PAC Thermostat User Manual

White Rodgers 1F96 Thermostat User Manual

Honeywell T827 Thermostat User Manual

Aprilaire 8800 Thermostat User Manual

Honeywell T8132C Thermostat User Manual

Honeywell T8024D Thermostat User Manual