Honeywell AQ1000TN2 Thermostat User Manual

Home

href="
Hydronic Zoning ThermAQo10s00tTaNt2  
OWNER’S GUIDE  
href="
Need Help?  
For assistance with this product please visit http://yourhome.honeywell.com  
or call Honeywell Customer Care toll-free at 1-800-468-1502.  
Read and save these instructions.  
®
U.S. Registered Trademark. Patents pending.  
©
9-06 Honeywell International Inc. All rights reserved.  
69-2005EF  
href="
Table of contents  
User’s section  
About your new thermostat....................................................................................1  
Screen display .......................................................................................................2  
Power-up / modes of operation..............................................................................3  
User’s configuration menu.....................................................................................4  
Temperature display and setting............................................................................6  
Installer’s section  
Installation..............................................................................................................7  
Configuration switches...........................................................................................8  
Installer’s configuration menu................................................................................9  
Appendix  
Technical specifications .......................................................................................12  
2
-year limited warranty ........................................................................................13  
69-2005EF  
href="
About your new thermostat  
Honeywell’s AQ1000TN2 hydronic zoning ther-  
mostat can be used to control the ambient air  
temperature or floor temperature. You can  
choose among the following temperature con-  
trol modes (see page 8):  
Screen  
A mode:  
F mode:  
controls and displays the  
ambient air temperature  
Temperature  
adjustment  
buttons  
controls and displays the floor  
temperature using an external  
temperature sensor  
Backlight  
button  
AF mode:  controls and displays the  
ambient air temperature  
maintains the floor temperature  
within desired limits using an  
external temperature sensor  
1
69-2005EF  
href="
Screen display  
The arrow appears when  
the setpoint is displayed  
Indoor temperature  
Temperature  
control mode  
Outdoor temperature 1  
Keypad lock 2  
Heating is On  
Freeze Protection mode  
Comfort / Unoccupied mode  
(see next page)  
(
see next page)  
1
2
The outdoor temperature will be displayed only if the data is available.  
This icon appears to indicate that the thermostat settings cannot be modified as the hydronic  
zoning controller has locked the keypad. The backlight button and the  
used to activate the backlight and to display the setpoint.  
buttons can still be  
2
69-2005EF  
href="
Power-up / modes of operation  
The thermostat is powered through the wires connecting it to the AQ2000 Series  
hydronic zoning controller. Therefore, the thermostat turns on when the controller is  
powered. The thermostat can be placed in one of the 3 following modes of operation:  
Comfort Mode  
The thermostat is normally in the Comfort mode. In this mode, the  
temperature is set using the  
buttons.  
Unoccupied Mode  
When the Unoccupied mode is activated by the hydronic zoning controller,  
the temperature setpoint is lowered by the temperature setback value.  
This value is set in the User’s configuration menu (see page 5).  
Freeze Protection Mode  
When the Freeze Protection mode is activated by the hydronic zoning  
controller, the thermostat is placed at the Freeze Protection temperature.  
This value is set in the Installer’s configuration menu (see page 10).  
3
69-2005EF  
href="
User’s Configuration Menu  
1.  
Press the backlight button for 3 seconds to access the configuration menu.  
The first parameter is displayed.  
2.  
3.  
4.  
To modify a parameter, press either of the  
To display the next parameter, briefly press the backlight button.  
To exit the menu, press the backlight button for 3 seconds.  
buttons.  
The parameters appear in the order shown in the following table.  
Parameter  
Default setting Options  
Display mode  
Temperature setback  
Backlight  
Automatic  
7 °F (4 °C)  
Temporary  
Automatic, °F, °C  
0 to 16 °F (0 to 9 °C)  
Temporary / Permanent  
4
69-2005EF  
href="
Display Format  
Use this parameter to choose the temperature display mode. When  
the automatic mode is selected, the thermostat displays the  
temperature format set on the hydronic zoning controller. If °F or °C is  
selected, the thermostat displays the temperature in the selected  
format respectively.  
Temperature Setback  
When the Unoccupied mode is activated by the hydronic zoning  
controller (certain controller models only), the temperature setpoint is  
lowered (set back). Use this parameter to specify the amount of  
temperature setback.  
Backlight  
Use this parameter to choose between temporary and permanent  
backlight. When temporary backlight is selected, the screen is lit for  
12 seconds every time any button is pressed.  
5
69-2005EF  
href="
Temperature Display and Setting  
The thermostat generally displays the actual (measured) temperature. To display the  
setpoint temperature, press one of the  
buttons once. The setpoint will be  
displayed for the next 5 seconds. An arrow appears at the left of the setpoint  
temperature display.  
To change the setpoint, press one of the  
buttons until the desired temperature is  
displayed. To scroll faster, press and hold the button.  
Error Messages  
The measured temperature is below the thermostat’s display range.  
The measured temperature is above the thermostat’s display range.  
Verify the thermostat and external (floor) sensor connections.  
6
69-2005EF  
href="
Installation  
1
.
Remove the faceplate from the base by unscrewing the screw underneath the ther-  
mostat and tilting the bottom of the faceplate up. Note that the screw remains cap-  
tive on the base.  
2
.
.
Insert the wires through the center hole of the base and secure the base to the wall  
or onto an electrical box.  
3
Connect the wires to the terminals (no polarity to observe).  
Terminal  
TH  
Description  
1
2
3
AQ2000 Series hydronic zoning controller connections  
TH  
SENSOR  
External sensor connections for floor temperature  
measurement (required only if the thermostat is set to F  
or AF mode; see pages 1 and 8)  
4
SENSOR  
4
.
.
Set the configuration switches (see next page).  
Re-attach the faceplate to the base and secure with the captive screw.  
5
NOTE: Keep the thermostat's air vents clean and unobstructed at all times.  
7
69-2005EF  
href="
Configuration switches  
The configuration (DIP) switches are located behind the  
thermostat faceplate.  
NOTE : DIP switch 1 is not used.  
Installer Configuration Menu (switch 2)  
Use DIP switch 2 to set the thermostat in either Installer or  
User mode.  
Temperature Control Mode (switches 3 & 4)  
Use DIP switches 3 and 4 to select the temperature control  
mode (A, F or AF).  
NOTE : F or AF mode should be used only when an external  
(floor) sensor is connected to the thermostat (see page 7).  
8
69-2005EF  
href="
Installer’s Configuration Menu  
The parameters in the installer’s configuration menu must be modified by qualified  
personnel only. Incorrect settings can result in property damages.  
1.  
2.  
3.  
4.  
5.  
6.  
Remove the thermostat from its base.  
Place switch 2 on the back of the thermostat in the up position (Installer mode).  
Return the thermostat to its base. The first parameter is displayed.  
To modify a parameter, press either of the  
To view the next parameter, briefly press the backlight button.  
To exit the menu, place switch 2 back to its initial position.  
buttons.  
The parameters appear in the order shown in the following table.  
Parameter  
Minimum setpoint temperature  
Maximum setpoint temperature  
Freeze Protection temperature  
Minimum floor limit  
Default setting  
41 °F (5 °C)  
Range  
41 °F (5 °C) to 100 °F (38 °C)  
41 °F (5 °C) to 100 °F (38 °C)  
41 °F (5 °C) to 100 °F (38 °C)*  
41 °F (5 °C) to 100 °F (38 °C)  
41 °F (5 °C) to 100 °F (38 °C)  
100 °F (38 °C)  
41 °F (5 °C)  
41 °F (5 °C)  
Maximum floor limit  
100 °F (38 °C)  
*
The Freeze Protection temperature range is set by the minimum and maximum setpoint temperatures.  
For example, if you change the minimum setpoint temperature to 50 °F (10 °C), you cannot then set the  
Freeze Protection temperature lower than 50 °F (10 °C).  
9
69-2005EF  
href="
Minimum Setpoint Temperature  
This parameter is the minimum temperature at which the thermostat  
can be set.  
Maximum Setpoint Temperature  
This parameter is the maximum temperature at which the thermostat  
can be set.  
Freeze Protection Temperature  
This parameter is used to prevent frozen pipes inside the room where  
the thermostat is located. When the Freeze Protection mode is acti-  
vated by the hydronic zoning controller, the thermostat is placed at  
the Freeze Protection temperature.  
1
0
69-2005EF  
href="
Minimum Floor Limit Temperature  
This parameter is used only if the thermostat has been configured for  
AF temperature control. If the floor temperature is below that limit, the  
pump or valve will be activated regardless of the ambient tempera-  
ture.  
Maximum Floor Limit Temperature  
This parameter is used only if the thermostat has been configured for  
AF temperature control. If the floor temperature is above that limit,  
the pump or valve will be deactivated regardless of the ambient tem-  
perature.  
11  
69-2005EF  
href="
Technical Specifications  
Power supply: powered by the boiler controller  
Default setpoint range: 40 °F to 100 °F (5 °C to 38 °C)  
Default floor limit (AF model): 40 °F to 100 °F (5 °C to 38 °C)  
Setpoint interval: ± 1.0 °F (0.5 °C)  
Indoor temperature display range: 32 °F to 158 °F (0 °C to 70 °C)  
Outdoor temperature display range: -58 °F to 212 °F (-50 °C to 100 °C)  
Display resolution: ± 1.0 °F (0.5 °C)  
Storage: -20 °F to 130 °F (-30 °C to 55 °C)  
Controller type: Proportional Integral (PI)  
Memory type: All settings are stored in non-volatile memory and are therefore safe  
during a power outage  
1
2
69-2005EF  
href="
2
-year limited warranty  
Honeywell warrants this product, excluding battery, to be free from defects in the workmanship  
or materials, under normal use and service, for a period of two (2) years from the date of  
purchase by the consumer. If at any time during the warranty period the product is determined  
to be defective or malfunctions, Honeywell shall repair or replace it (at Honeywell’s option).  
If the product is defective,  
(
i) return it, with a bill of sale or other dated proof of purchase, to the place from which you  
purchased it; or  
(
ii) call Honeywell Customer Care at 1-800-468-1502. Customer Care will make the  
determination whether the product should be returned to the following address: Honeywell  
Return Goods, Dock 4 MN10-3860, 1885 Douglas Dr. N., Golden Valley, MN 55422, or  
whether a replacement product can be sent to you.  
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is  
shown by Honeywell that the defect or malfunction was caused by damage which occurred  
while the product was in the possession of a consumer.  
Honeywell’s sole responsibility shall be to repair or replace the product within the terms stated  
above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND,  
13  
69-2005EF  
href="
INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY  
OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR  
ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or  
limitation of incidental or consequential damages, so this limitation may not apply to you.  
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS  
PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE  
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS  
HEREBY LIMITED TO THE TWO-YEAR DURATION OF THIS WARRANTY.  
Some states do not allow limitations on how long an implied warranty lasts, so the above  
limitation may not apply to you. This warranty gives you specific legal rights, and you may have  
other rights which vary from state to state.  
If you have any questions concerning this warranty, please write Honeywell Customer  
Relations, 1985 Douglas Dr, Golden Valley, MN 55422 or call 1-800-468-1502. In Canada, write  
Retail Products  
ON15-02H, Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario  
M1V4Z9.  
1
4
69-2005EF  
href="
Automation and Control Solutions  
Honeywell International Inc.  
985 Douglas Drive North  
Honeywell Limited-Honeywell Limitée  
1
35 Dynamic Drive  
Golden Valley, MN 55422  
yourhome.honeywell.com  
Toronto, Ontario M1V 4Z9  
®
©
U.S. Registered Trademark  
2006 Honeywell International Inc.  
69-2005EF  
Rev. 9-06  
href="
Thermostat de zonage hydAroQ1n0i0q0TuNe2  
GUIDE DU PROPRIÉTAIRE  
href="
Besoin d’aide?  
Pour obtenir de l’aide sur ce produit, veuillez consulter le http://yourhome.honeywell.com  
ou joindre le service à la clientèle en composant sans frais le 1 800 468-1502  
Veuillez lire le mode d’emploi et le conserver en lieu sûr.  
®
Marque de commerce enregistrée aux États-Unis. Brevets en instance.  
©
10-06 Honeywell International inc. Tous droits réservés.  
69-2005EF  
href="
Table des matières  
Section de l’utilisateur  
À propos du thermostat .........................................................................................1  
Affichage................................................................................................................2  
Mise sous tension / modes de fonctionnement......................................................3  
Menu de configuration de l’utilisateur ....................................................................4  
Affichage et réglage de la température..................................................................6  
Section de l’installateur  
Installation..............................................................................................................7  
Commutateurs de configuration.............................................................................8  
Menu de configuration de l’installateur ..................................................................9  
Annexe  
Fiche technique ...................................................................................................12  
Garantie limitée de 2 ans.....................................................................................13  
69-2005EF  
href="
À propos du thermostat  
Le thermostat de zonage hydronique  
AQ1000TN2 de Honeywell permettent de  
réguler la température ambiante ou la tempé-  
rature du plancher. Vous pouvez choisir l’un  
des modes de régulation de la température  
suivants (voir la page 8) :  
Écran  
Mode A :  régulation de la température  
ambiante  
Boutons  
d’ajustement  
de la  
température  
Mode F :  
régulation de la température du  
plancher au moyen d’une sonde de  
température externe  
Bouton de  
rétroéclairage  
Mode AF : régulation de la température  
ambiante  
maintien la température du plancher  
dans les limites désirées au moyen  
d’une sonde de température externe  
1
69-2005EF  
href="
Affichage  
La flèche apparaît lorsque  
la température de consigne  
est affichée  
Température intérieure  
Mode de régulation  
de la température  
Température extérieure 1  
Chauffage en cours  
Mode Hors-gel  
Clavier verrouillé 2  
Mode Confort / Inoccupé  
(voir la page suivante)  
(
voir la page suivante)  
1
2
La température extérieure sera affichée uniquement si les données sont disponibles.  
Cette icône apparaît pour indiquer que les réglages du thermostat ne peuvent être modifiés,  
puisque le régulateur hydronique de zonage a verrouillé le clavier. Le bouton de rétroéclairage  
et les boutons  
permettent cependant d’activer le rétroéclairage et d’afficher la  
température de consigne.  
2
69-2005EF  
href="
Mise sous tension / modes de fonctionnement  
Le thermostat est alimenté au moyen des fils qui le relient au régulateur hydronique de  
zonage Série AQ2000. Le thermostat est donc mis sous tension en même temps que le  
régulateur. On peut placer le thermostat dans l’un des modes de fonctionnement suivants :  
Mode Confort  
Le thermostat est normalement en mode Confort. Dans ce mode, la tem-  
pérature de consigne est réglée au moyen des boutons  
.
Mode Inoccupé  
Lorsque le mode Inoccupé est activé à partir du régulateur, la température  
de consigne est abaissée. La marge d’abaissement est modifiable à partir  
du menu de configuration de l’utilisateur (voir la page 5).  
Mode Hors-gel  
Lorsque le mode Hors-gel est activé à partir du régulateur, le thermostat  
est placé à la température Hors-gel. Cette valeur est modifiable à partir  
du menu de configuration de l’installateur (voir la page 10).  
3
69-2005EF  
href="
Menu de configuration de l’utilisateur  
1.  
Appuyer sur le bouton de rétroéclairage pendant 3 secondes pour accéder  
au menu de configuration. Le premier paramètre apparaît.  
2
3
.
.
Pour modifier un paramètre, appuyer sur l’un des boutons  
Pour afficher un autre paramètre, appuyer brièvement sur le bouton de  
rétroéclairage  
.
.
4.  
Pour sortir du menu de configuration, appuyer sur le bouton de rétroéclairage  
pendant 3 secondes.  
Les paramètres apparaissent dans l’ordre indiqué dans le tableau suivant.  
Paramètre  
Valeur par défaut Options  
Automatique Automatique, °F, °C  
Mode d’affichage  
Marge d’abaissement de la température 4 °C (7 °F)  
0 °C à 9 °C (0 °F à 16 °F)  
Temporaire / Permanent  
Rétroéclairage  
Temporaire  
4
69-2005EF  
href="
Format d’affichage  
Ce paramètre permet de choisir le format d’affichage de la température.  
Si vous choisissez le mode automatique (Au), le thermostat affichera la  
température dans le format utilisé par le régulateur hydronique de  
zonage. Si vous choisissez le mode °F ou °C, le thermostat affichera  
respectivement la température en °F ou °C.  
Abaissement de la température  
Lorsque le mode Inoccupé est activé à partir du régulateur hydronique de  
zonage (certains modèles de régulateurs seulement), la température de  
consigne est abaissée. Ce paramètre permet de déterminer la marge  
d’abaissement de la température.  
Rétroéclairage  
Ce paramètre permet de choisir entre le rétroéclairage temporaire et le  
rétroéclairage permanent. Avec le rétroéclairage temporaire, l’écran  
s’illumine pendant 12 secondes chaque fois que vous appuyez sur un  
bouton.  
5
69-2005EF  
href="
Affichage et réglage de la température  
Le thermostat affiche généralement la température réelle (mesurée). Pour afficher la  
température de consigne, appuyer une fois sur l’un des boutons  
. La température  
de consigne sera affichée pendant les 5 secondes suivantes. Une flèche apparaît à  
gauche de la température de consigne affichée.  
Pour changer la température de consigne, appuyer sur un des boutons  
jusqu’à  
ce que la température désirée soit affichée. Pour faire défiler la température de con-  
signe plus rapidement, maintenir le bouton enfoncé.  
Messages d’erreur  
La température mesurée est inférieure à la plage d’affichage.  
La température mesurée est supérieure à la plage d’affichage.  
Vérifier les connexions du thermostat et de la sonde externe (du plancher).  
6
69-2005EF  
href="
Installation  
1.  
2.  
3.  
Retirer la façade du socle en desserrant la vis située sous le thermostat et en tirant  
sur la partie inférieure. Noter que la vis reste captive sur le socle.  
Insérer les fils à travers l’ouverture du centre du socle et fixer le socle sur le mur ou  
sur une boîte électrique.  
Raccorder les fils aux bornes (aucune polarité).  
Borne  
Description  
1
2
3
TH  
Connexion du régulateur hydronique de zonage Série  
AQ2000  
TH  
SENSOR  
Connexion de la sonde externe pour mesurer la tempéra-  
ture du plancher (requise uniquement si le thermostat est  
placé en mode F ou AF; voir les pages 1 et 8)  
4
SENSOR  
4
.
.
Placer les commutateurs de configuration, s’il y a lieu (voir la page suivante).  
Remettre la façade sur le socle et serrer la vis.  
5
NOTA : Garder les ouvertures d’aération du thermostat propres et dégagées en tout temps.  
7
69-2005EF  
href="
Commutateurs de configuration  
Les commutateurs de configuration (DIP switch) sont situés  
au dos de la façade du thermostat.  
NOTA : Le commutateur 1 n’est pas utilisé.  
Menu de configuration de l’installateur (commutateur 2)  
Utiliser le commutateur 2 pour mettre le thermostat en mode  
Installateur ou Utilisateur.  
Mode de régulation de la température (commutateurs 3 & 4)  
Utiliser les commutateurs 3 et 4 pour sélectionner le mode  
de régulation de la température (A, F ou AF).  
NOTA : Utiliser le mode F ou AF uniquement si une sonde  
externe (pour le plancher) est reliée au thermostat (voir la  
page 7).  
8
69-2005EF  
href="
Menu de configuration de l’installateur  
Seuls des installateurs compétents sont autorisés de modifier les paramètres du menu de  
configuration. Des réglages inappropriés peuvent causer des dommages à la propriété.  
1.  
2.  
3.  
4.  
5.  
6.  
Retirer le thermostat du socle.  
Positionner le commutateur 2, au dos du thermostat, vers le haut (mode Installateur).  
Remettre le thermostat sur son socle. Le premier paramètre est affiché.  
Pour modifier un paramètre, appuyer sur l’un des boutons  
Pour afficher le paramètre suivant, appuyer brièvement sur le bouton de rétroéclairage  
Pour sortir du menu, remettre le commutateur 2 à sa position initiale.  
.
.
Les paramètres apparaissent dans l’ordre indiqué dans le tableau suivant.  
Paramètre  
Température de consigne minimale  
Température de consigne maximale  
Protection Hors-gel  
Réglage par défaut  
5 °C (41 °F)  
Plage  
5 °C (41 °F) à 38 °C (100 °F)  
5 °C (41 °F) à 38 °C (100 °F)  
5 °C (41 °F) à 38 °C (100 °F)*  
5 °C (41 °F) à 38 °C (100 °F)  
5 °C (41 °F) à 38 °C (100 °F)  
38 °C (100 °F)  
5 °C (41 °F)  
Limite minimale du plancher  
Limite maximale du plancher  
5 °C (41 °F)  
38 °C (100 °F)  
*
La plage de la température Hors-gel est définie par les températures de consigne minimale et maximale.  
Par exemple, si vous modifiez la température de consigne minimale à 10 °C (50 °F), vous ne pourrez pas  
régler la température Hors-gel à une valeur inférieure à 10 °C (50 °F).  
9
69-2005EF  
href="
Température de consigne minimale  
Ce paramètre est la température minimale à laquelle le thermostat  
peut être réglé.  
Température de consigne maximale  
Ce paramètre est la température maximale à laquelle le thermostat  
peut être réglé.  
Température Hors-gel  
Ce paramètre sert à empêcher le gel dans les tuyaux dans la pièce  
où se situe le thermostat. Lorsque le mode Hors-gel est activé à partir  
du régulateur hydronique de zonage, le thermostat est placé à la  
température Hors-gel.  
1
0
69-2005EF  
href="
Limite de température minimale du plancher  
Ce paramètre servira uniquement si le thermostat est configuré en  
mode AF. Si la température du plancher est inférieure à cette limite,  
la pompe ou valve sera activée peu importe la température ambiante.  
Limite de température maximale du plancher  
Ce paramètre servira uniquement si le thermostat est configuré en  
mode AF. Si la température du plancher est supérieure à cette limite,  
la pompe ou valve sera désactivée peu importe la température  
ambiante.  
11  
69-2005EF  
href="
Fiche technique  
Alimentation : Alimenté par le régulateur hydronique de zonage  
Plage de réglage par défaut : 5 °C à 38 °C (40 °F à 100 °F)  
Limite du plancher par défaut (modèle AF) : 5 °C à 38 °C (40 °F à 100 °F)  
Intervalle de consigne : ± 0,5 °C (1,0 °F)  
Plage d’affichage de la température intérieure : 0 °C à 70 °C (32 °F à 158 °F)  
Plage d’affichage de la température extérieure : -50 °C à 100 °C (-58 °F à 212 °F)  
Résolution d’affichage : ± 0,5 °C (1,0 °F)  
Entreposage : -30 °C à 55 °C (-20 °F à 130 °F)  
Type de régulateur : Proportionnel intégral (PI)  
Mémoire : Les réglages sont stockés dans la mémoire non volatile et sont donc  
conservés lors d’une panne de courant.  
1
2
69-2005EF  
href="
Garantie limitée de 2 ans  
Honeywell garantit ce produit, à l'exception des piles, contre tout vice de fabrication ou de  
matière dans la mesure où il en est fait une utilisation et un entretien convenables, et ce, pour  
deux (2) ans à partir de la date d'achat par le consommateur. En cas de défectuosité ou de  
mauvais fonctionnement pendant la période de garantie, Honeywell remplacera ou réparera le  
produit (au gré de Honeywell).  
Si le produit est défectueux,  
(
(
i) le retourner, accompagné d'une preuve d'achat indiquant la date d'achat, à l’endroit où il a  
été acheté, ou  
ii) s'adresser aux Services à la clientèle de Honeywell en composant le 1 800 468-1502. Les  
Services à la clientèle détermineront alors si le produit doit être retourné à l'adresse  
suivante : Honeywell Return Goods, Dock 4 MN10-3860, 1885 Douglas Dr N, Golden  
Valley, MN 55422, ou si un produit de remplacement peut vous être expédié.  
La présente garantie ne couvre pas les frais de retrait ou de réinstallation. La présente garantie  
ne s'appliquera pas s'il est démontré que la défectuosité ou le mauvais fonctionnement est dû à  
un endommagement du produit alors que le consommateur l'avait en sa possession.  
La responsabilité de Honeywell se limite à réparer ou à remplacer le produit conformément aux  
modalités susmentionnées. HONEYWELL N'EST EN AUCUN CAS RESPONSABLE DES  
PERTES OU DOMMAGES, Y COMPRIS LES DOMMAGES INDIRECTS OU ACCESSOIRES  
13  
69-2005EF  
href="
DÉCOULANT DIRECTEMENT OU INDIRECTEMENT D'UNE VIOLATION QUELCONQUE  
D'UNE GARANTIE, EXPRESSE OU TACITE, APPLICABLE AU PRÉSENT PRODUIT NI DE  
TOUTE AUTRE DÉFECTUOSITÉ DU PRÉSENT PRODUIT. Certaines provinces ne permettent  
pas l'exclusion ou la restriction des dommages indirects et, par conséquent, la présente  
restriction peut ne pas s'appliquer.  
LA PRÉSENTE GARANTIE TIENT LIEU DE TOUTES LES AUTRES GARANTIES,  
EXPRESSES OU TACITES, ET LES GARANTIES DE VALEUR MARCHANDE ET DE  
CONFORMITÉ À UNE FIN PARTICULIÈRE SONT PAR LES PRÉSENTES EXCLUES APRÈS  
LA PÉRIODE DE DEUX ANS DE LA PRÉSENTE GARANTIE. Certaines provinces ne  
permettent pas de limiter la durée des garanties tacites et, par conséquent, la présente  
limitation peut ne pas s'appliquer.  
La présente garantie donne au consommateur des droits légaux spécifiques et peut-être  
certains autres droits qui peuvent varier d'une province à l'autre.  
Pour toute question concernant la présente garantie, prière d'écrire aux Services à la clientèle  
de Honeywell à l'adresse suivante : Honeywell Customer Relations, 1985 Douglas Drive,  
Golden Valley, MN 55422, ou encore composer le 1 800 468-1502. Au Canada, prière de  
s'adresser au service des Produits de détail, Honeywell Limited/Honeywell Limitée, 35,  
Dynamic Drive, Scarborough (Ontario) M1V 4Z9.  
1
4
69-2005EF  
href="
Solutions de régulation et d'automatisation  
Honeywell International Inc.  
985 Douglas Drive North  
Honeywell Limited-Honeywell Limitée  
1
35, Dynamic Drive  
Golden Valley, MN 55422  
yourhome.honeywell.com  
Toronto, (Ontario) M1V 4Z9  
®
©
Marque de commerce déposée aux É.-U.  
2006 Honeywell International Inc. Tous droits réservés  
Rev. 10-06  
69-2005EF  

Honeywell 1000 Series Thermostat User Manual

Honeywell T4039B Thermostat User Manual

White Rodgers 1F92W 51 Thermostat User Manual

Honeywell 69 1776EFS 01 Thermostat User Manual

Honeywell T8095A191108AJ Thermostat User Manual

Aprilaire 8533 Thermostat User Manual

Honeywell AQ1000TP2 Thermostat User Manual

Honeywell RTH2308 Thermostat User Manual

Hunter Fan 40120 Thermostat User Manual

Lux Products PSP722E Thermostat User Manual