T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASES  
					4600  
					SETTING  
					4400  
					4200  
					4000  
					3800  
					3600  
					C815A THERMISTOR RESISTANCE  
					R = 400 ohms ± 10% AT 77°F (25°C)  
					Setting the Heat Anticipator (T874Q Only)  
					Set each heat anticipator to match its primary control  
					current draw. If the primary control nameplate has no  
					rating or if further adjustment is necessary, use the  
					following procedure to determine the current draw of each  
					stage. (Measure the current draw of each heating stage  
					with the thermostat removed and the power on.)  
					3400  
					3
					3
					200  
					000  
					2800  
					2
					2
					600  
					400  
					2200  
					2
					1
					000  
					800  
					ꢀ
					Connect an ac ammeter of appropriate range  
					between the heating terminals of the subbase as  
					follows:  
					1600  
					1400  
					1200  
					1000  
					800  
					Stage 1: between W1 and RH or R.  
					Stage 2: between W2 and R.  
					Move the system switch to AUTO (if applicable).  
					After one minute, read the ammeter and record the  
					reading.  
					6
					4
					00  
					00  
					ꢁ
					ꢂ
					200  
					0
					-20  
					0
					20  
					40  
					60  
					80  
					100  
					120 140  
					M1590A  
					TEMPERATURE OF THERMISTOR (°F)  
					ꢃ
					After mounting the thermostat, set the adjustable  
					heat anticipator(s) to match the respective  
					reading(s) measured in step ꢂ.  
					Fig. 10 Thermistor resistance chart.  
					The proper thermistor operation must be verified to assure  
					the correct operation of the thermostat. Check the  
					thermistor operation as follows:  
					Temperature Setting  
					Move the heating and cooling levers to the desired  
					positions. The minimum differential between the heating  
					and cooling setpoints is 3°F (1.7°C), which means the  
					setting levers cannot be set closer together than 3°F  
					ꢀ
					ꢁ
					Disconnect the T wire on the subbase.  
					Use an ohmmeter to measure resistance between  
					the T wire and the transformer common.  
					Take the outdoor temperature at thermistor location  
					and find the correct thermistor resistance on the  
					chart in Fig. 10.  
					ꢂ
					ꢃ
					(1.7°C) (5° F [2.8°C] for T874W).  
					Subbase Setting  
					If the resistance measured in step ꢁ and the  
					calculated resistance in step ꢂ vary by more than  
					15 percent, the thermistor requires replacement.  
					Contact the installing dealer for the packaged  
					replacement outdoor thermistor.  
					System switching positions control thermostat operation as  
					follows:  
					OFF: Both the heating and cooling systems are off. If  
					the fan switch is in the AUTO position, the cooling  
					fan is also off.  
					AUTO: Thermostat automatically changes between the  
					heat and cool modes, depending on the indoor  
					temperature.  
					HEAT: Heating system is controlled by the thermostat.  
					Cooling system is off.  
					EM. HT.: Emergency heat relay is energized. The  
					cooling system is off. When the compressor has  
					failed and the heat pump is not operating, switch to  
					the EM. HT. position.  
					CHECKOUT  
					Heating  
					Move the system switch on the Q674 Subbase to HEAT or  
					AUTO. Move the heating lever on the T874 about 10°F  
					(6°C) above room temperature. Both stages of heating  
					start and the fan runs after a short delay. Move the heating  
					lever about 10°F (6°C) below room temperature. The  
					heating equipment shuts off, and the fan runs for a short  
					time, and then shuts off.  
					Fan switching positions control fan operation as follows  
					Q674B,C, or L):  
					ON: Fan operates continuously.  
					(
					AUTO: Fan operates with cooling equipment as  
					controlled by the thermostat or with the heating  
					equipment as controlled by the plenum switch.  
					Cooling  
					Move the system switch on the Q674 Subbase to COOL  
					or AUTO. Move the cooling lever on the T874 Thermostat  
					about 10°F (6°C) below room temperature. The cooling  
					equipment and fan start. Move the cooling lever about  
					To switch positions, use thumb and index finger to slide  
					the lever to the desired position. The switch lever must  
					stop in detent over the desired function indicator mark for  
					proper circuit operation.  
					10°F (6°C) above room temperature. The cooling equip-  
					ment and fan stop.  
					Emergency Heat  
					C815 Outdoor Reset Thermistor (T874W only)  
					The T874W is used with a C815 Thermistor mounted in  
					the outdoor section. The thermistor must be used; if not,  
					thermostat performance will deviate radically from proper  
					operation.  
					Move the system switch to EM. HT. The EM. HT. LED  
					comes on. Move the heating lever about 10°F (6°C) above  
					room temperature. The electric strip heater(s) comes on.  
					Move the heating lever about 10°F (6°C) below room  
					temperature. The electric strip heater de-energizes. The  
					EM. HT. LED remains on until the system switch is moved  
					to another postion.  