Honeywell R8184G Thermostat User Manual

Home

href="
R8184G PROTECTORELAY  
OIL PRIMARY  
RED RESET  
BUTTON  
HOLE OR KNOCKOUT FOR  
CAD CELL LEADS  
APPLICATION  
The TRADELINE intermittent ignition oil primary control  
operates the oil burner, oil valve (if desired) and the ignition  
transformer in response to a call for heat from the thermo-  
stat. Through a C554 Cad Cell Flame Sensor, the R8184  
monitors the burner flame and shuts down the system on  
ignitionfailureoronflamefailureduringtheruncycle.Alight  
emitting diode (LED) on the terminal strip lights when the  
safety switch opens to provide safety shutdown indication.  
A manual reset button is provided to reset the safety switch  
after lockout.  
LOW VOLTAGE  
TERMINAL STRIP  
2
4
x 4 JUNCTION  
BOX  
For convenience in system maintenance, the safety  
switch can be manually opened using a lever on the front of  
the control. Clock thermostats that power the clock through  
the primary control transformer will lose time during lockout  
unless backup batteries are installed.  
R8184GiscomponentrecognizedbyUnderwritersLabo-  
ratories Inc. and meets their flammability test requirements  
for a final enclosure.  
CAD  
CELL LEADS  
LINE  
VOLTAGE LEADS  
MOUNTING  
SCREW HOLE  
1
1
2
STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.  
T-T TERMINALS ON R8184G; T1-T2 TERMINALS ON R8184N.  
M1643B  
Fig. 1—Mounting the R8184G controls with 130° F  
54° C] maximum ambient temprature.  
INSTALLATION  
[
WHEN INSTALLING THIS PRODUCT…  
1. Read these instructions carefully. Failure to follow  
LOCATION  
them could damage the product or cause a hazardous  
condition.  
1. Mount on a 4 x 4 inch junction box, directly on the main  
burner, or inside the appliance cabinet. In replacement  
applications, mount in the same location as the old control.  
2. Ensure the operating temperatures are within the am-  
bient temperature range. Ambient temperature ranges are  
either -40° to 130° F [-40° C to 54° C] or -40° F to 150° F  
[-40° C to 66° C] (Refer to box label).  
2. Check the ratings given in the instructions and on the  
product to make sure the product is suitable for your  
application.  
3. Installer must be a trained, experienced service tech-  
nician.  
4. After installation is complete, check out product op-  
MAKEWIRINGCONNECTIONSANDMOUNTCONTROL  
Wiring must comply with all local codes and ordinances.  
Before mounting the control, make line voltage connec-  
tions as shown in Fig. 1 or 2. Splice leads with solderless  
connectors. Do not exceed load ratings shown on the device  
label.  
If cad cell leads are run with line voltage wires, breakout  
knockout at the bottom of the low voltage terminal strip and  
thread can cell leads through the hole.  
eration as provided in these instructions.  
CAUTION  
1
. Disconnect power before beginning installation to  
prevent electrical shock or equipment damage.  
. Make sure combustion chamber is free of oil or  
vapor before starting system.  
2
If necessary use control as a template to mark and drill new  
mounting holes. Mount using No. 6 screws (obtain locally).  
R8184G PROTECTORELAY CONTROL  
THERMOSTAT  
JUNCTION BOX  
LINE VOLTAGE  
THERMOSTAT  
BLACK  
T
2
SAFETY  
2
SWITCH  
1K  
L1  
T
LIMIT  
(HOT)  
SAFETY  
SWITCH  
HEATER  
LOCKOUT  
INDICATOR  
LED  
1
1K2  
ORANGE  
BURNER  
MOTOR  
L2  
R1  
SAFETY  
SWITCH  
BILATERAL  
SWITCH  
OIL VALVE  
TRIAC 1K1  
CAD CELL  
(OPTIONAL)  
R2  
F
F
IGNITION  
CAPACITOR  
WHITE  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN  
SERIES WITH LIMIT CONTROLLER.  
M1635  
Fig. 2—Typical hookup for TRADELINE R8184G with indicator light.  
D.T.  
Rev. 4-91  
Form Number 69-0617—1  
© Honeywell Inc. 1991  
href="
L1 (HOT)  
L2  
FAN  
RELAY  
1
T87F/Q539A  
COOLING  
TRANSFORMER  
R
C
COOLING  
CONTROL  
G
Y
RH  
R8184G PROTECTORELAY CONTROL  
JUNCTION BOX  
LINE VOLTAGE  
THERMOSTAT  
W
X
BLACK  
T(R)  
2
SAFETY  
SWITCH  
2
1K  
L1  
(HOT)  
T(W)  
LIMIT  
3
LOCKOUT  
INDICATOR  
LED  
SAFETY  
SWITCH  
HEATER  
1
1K2  
VIOLET  
ORANGE  
BURNER  
MOTOR  
L2  
R1  
SAFETY BILATERAL  
SWITCH SWITCH  
OIL VALVE  
(OPTIONAL)  
TRIAC  
1K1  
CAD CELL  
R2  
F
IGNITION  
CAPACITOR  
WHITE  
F
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE  
VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.  
3
REMOVE PLUG AND ROUTE VIOLET LEADWIRE THROUGH HOLE IN BASE OF R8184.  
M718  
Fig. 3—Typical hookup for Tradeline R8184G with indicator light and isolated alarm relay.  
Mount control as shown in Fig. 1 or 2. After mounting,  
make low voltage connections to the screw terminals. Strip  
leads 3/8 in. [10 mm] and insert under terminal screw. See  
Fig. 1 or 2. Connect cad cell leads to F-F terminals and  
thermostat leads to T-T terminals. See Fig. 3 or 4.  
2. Safety switch should lock out in safety switch timing  
(see label). Indicator light should come on. Ignition and  
motor should stop and oil valve should close.  
Simulate power failure:  
1. Follow starting procedure to turn on burner.  
2. With burner running, trip circuit breaker or remove  
fuse to turn off power to the system.  
3
. Burner should stop.  
CHECKOUT  
START SYSTEM  
4. Restore power. Burner should restart.  
If system does not operate as described, proceed to  
Troubleshooting.  
WARNING  
Can cause severe burns.  
Make sure combustion chamber is free of oil or oil  
vapor before starting system.  
. Push in and release red reset button.  
. Open hand valve in oil supply line.  
. Make sure system is powered. Check circuit  
breaker or fuse and close system switch, if  
provided.  
. Set thermostat to call for heat.  
. Burner should light and operate until call for  
heat ends.  
TROUBLESHOOTING AND  
Fire hazard.  
MAINTENANCE  
IMPORTANT  
This control contains no field-serviceable parts. Do  
not attempt to take it apart. Replace entire control if  
operation is not as described.  
1
2
3
PRELIMINARY STEPS  
1. Check wiring connections and power supply. Make  
sure power is on to the controls, burner motor, and ignition  
transformer.  
4
5
2. Make sure limit control is closed.  
CHECK OIL PRIMARY RELAY  
NOTE: You’ll need an insulated jumper wire with both ends  
stripped.  
CHECK SAFETY FEATURES  
Simulate flame failure:  
1
2
3
. Follow starting procedure to turn on burner.  
. Close hand valve in oil supply line.  
. Safety switch should lock out approximately in safety  
1
. Disconnect cad cell leads from F-F terminals.  
2. Resetsafetyswitchandsetthermostattocallforheat.  
Burner should start.  
. Within safety switch timing, jumper F-F terminals with  
insulated jumper wire. Burner should continue to run.  
. After safety switch timing, remove jumper. Burner  
should shut down in safety switch timing.  
. If operation is not as described, replace oil primary  
control.  
switchtimingindicatedonlabel. Indicatorlightshouldcome  
on. Ignition and motor should stop and oil valve should  
close.  
3
4
Simulate ignition failure:  
1. Follow starting procedure to turn on burner, except do  
5
not open oil supply hand valve.  
2
href="
CHECK CAD CELL  
. Disconnect power at system switch, circuit breaker or  
fuse.  
1
PUSH LEVER DOWN  
TO TRIP SAFETY SWITCH  
2
3
. Clean cell face with soft cloth.  
. Makesurecellisseatedsecurelyinsocket. Becareful  
not to disturb socket position.  
4
. Reconnect cad cell leads to F-F terminals.  
5. Reset safety switch, turn on power and set thermostat  
WHEN SAFETY SWITCH TRIPS  
TRIP SAFETY SWITCH BEFORE PERFORMING  
BURNER MAINTENANCE  
RESET BUTTON POPS OUT  
INDICATOR LIGHT COMES ON  
(TRADELINE ONLY)  
CAUTION  
Tripping the safety switch shuts down the burner but  
doesnotdisconnectthepowersupply.Turnoffpower  
at system switch or circuit breaker before servicing  
the control system, burner motor, oil valve or ignition  
to avoid electric shock.  
M17882  
To trip the safety switch, move the safety switch lever  
down until the red reset button pops out and the indicator  
light comes on. See Fig. 5. Burner will not operate until  
safety switch is reset by pushing in the red reset button.  
Fig. 4—Move lever down to trip safety switch.  
3
69-0617—1  
href="
Automation and Control Solutions  
Honeywell International Inc. Honeywell Limited—Honeywell Limitée  
1
985 Douglas Drive North  
35 Dynamic Drive  
Golden Valley, MN 55422  
Scarborough, Ontario M1V 4Z9  
www.honeywell.com  

Honeywell T8001C Thermostat User Manual

Honeywell HCE100B Thermostat User Manual

Lux Products LHP 750 Thermostat User Manual

White Rodgers 1F98EZ 1441 Thermostat User Manual

White Rodgers 196 Thermostat User Manual

Honeywell T7984 B Thermostat User Manual

Honeywell HE300 Thermostat User Manual

Honeywell T8196A Thermostat User Manual

Honeywell MS3000 Thermostat User Manual

Honeywell T4039H Thermostat User Manual