Honeywell T7300F Series Thermostat User Manual

Home

href="
T7300F Series 2000  
Commercial Thermostat and  
Q7300H Communicating Subbase  
SPECIFICATION DATA  
FEATURES  
T7300F  
For use with multistage conventional or heat pump  
applications.  
Proportional plus Integral (P+I) control eliminates  
temperature fluctuations.  
®
Intelligent Recovery control automatically optimizes  
equipment start times based on building load.  
®
Intelligent Fan feature energizes fan continuously in  
the Occupied periods. Fan can also be configured for  
conventional heat or electric heat fan operation.  
7-day programmable with four periods per day.  
Configurable reversing valve operation.  
Selectable automatic or manual changeover.  
Remote sensor capability.  
APPLICATION  
The T7300F Series 2000 Commercial Thermostat and  
Q7300H Communicating Subbase control 24 Vac commercial  
single-zone multistage heating, ventilating and air conditioning  
Keypad lockout available.  
Auxiliary contacts can interface with C7400/W7459  
Economizer System for total rooftop control  
integration.  
(
HVAC) equipment. Additionally, the Q7300H Subbase allows  
remote access and the sharing of clock, schedule, setpoints,  
bypass and other system parameters with other devices in a  
LONWORKS® network.  
Q7300H  
Provides networking capability on a LONWORKS Bus  
using a Free Topology Transceiver (FTT).  
Conforms to LONMARK® thermostat functional profile.  
Dial-in capability allows remote monitoring and control  
of key variables such as time, schedule, setpoints,  
mode, fan status.  
Communicates schedule information to other network  
devices.  
Selects fan operation and system mode using a remote  
T7300F Thermostat.  
Shares information such as time-of-day, temporary  
setpoint and occupancy status with multiple T7300 or  
Excel 10 controllers.  
Installer setup may be done locally from the T7300  
keypad or from a local or remote personal computer.  
Fully integrated with Honeywell's light commercial  
building solutions to provide enhanced alarming,  
trending, scheduling and dial-out capabilities.  
®
®
U.S. Registered Trademark  
®
Copyright © 2001 Honeywell • All Rights Reserved  
63- 1281- 1  
href="
T7300F SERIES 2000 COMMERCIAL THERMOSTAT AND Q7300H COMMUNICATING SUBBASE  
SPECIFICATIONS  
Remote Sensor Wiring Temperature Offset:  
Occurs with every 500 ft (157m) to 1000 ft (305m) of 2-wire  
cable. See Table 3.  
Models Available:  
Q7300H Subbase:  
The Q7300H Series 2000 Communicating Subbase includes  
terminals for connection to the LONWORKS Bus and a network  
jack for quick access by personal computer based tools.  
Additionally, a communications service-pin pushbutton is  
provided to simplify startup.  
Table 3. Temperature Offset.  
Temperature Range  
18 AWG  
-0.4°F  
20 AWG  
-0.7°F  
22 AWG  
-1.0°F  
50 to 90°F  
Q7300H2003 Communicating Subbase, with O and B  
terminals, provides 3-stage heating and 2-stage cooling  
control for heat pump systems.  
Q7300H2011 Communicating Subbase, without O and B  
terminals, provide 3-stage heating and 2-stage cooling  
control for heat pump systems.  
Q7300H2029 Communicating Subbase with 3-stage  
heating and 3-stage cooling control for conventional  
systems.  
Q7300H2037 Communicating Subbase with 2-stage  
heating and 1-stage cooling control for conventional  
systems.  
1
0 to 32°C  
-0.3°C  
-0.4°C  
-0.6°C  
Humidity Ratings: 5% to 90% RH, noncondensing.  
Auxiliary Heat and Emergency Heat Indication:  
Thermostat display indicates when Auxiliary Heat or  
Emergency Heat is activated.  
Clock Accuracy: ±1 minute per month.  
Loss of Power: Thermostat maintains programmed times  
and temperatures for product life. Clock and day  
information is retained for two hours.  
T7300F Thermostat:  
T7300F Series 2000 Commercial Thermostat has a keypad  
for setting system parameters, a corresponding LCD display  
and a flip-down keypad cover. The T7300F Thermostat  
mounts on the Q7300H Subbase.  
Minimum Stage Operation Time:  
Minimum On (Heat and Cool): Factory setting 2 minutes;  
adjustable 0 to 2 minutes.  
Minimum Off (Compressor): Factory setting 4 minutes;  
adjustable 0 to 5 minutes.  
Minimum Off (Heat): Factory setting 4 minutes;  
T7300F2002 Series 2000 Commercial Electronic  
Thermostat without system and fan switching.  
T7300F2028 Series 2000 Commercial Electronic  
Thermostat with system and fan switching.  
adjustable 0 to 4 minutes.  
Mounting:  
Electrical Ratings:  
Power: 20 to 30 Vac, 50/60 Hz.  
System Current Draw: 6 VA maximum at 30 Vac, 50/60 Hz.  
T7300F Thermostat mounts on a Q7300H Subbase.  
Q7300H Subbase mounts horizontally on a wall or outlet box  
with two no. 6 x 32 screws and anchors (included).  
Output Relay Draw: See Table 1.  
Finish (color): Taupe.  
Table 1. Maximum Amperes at 30 Vac.  
Accessories:  
C7400 Enthalpy Sensor.  
R8222 Switching Relay.  
Relay  
Running  
0.5A  
Inrush  
2.5A  
Fan  
T675A Temperature Control.  
Heat (all stages)  
1.5A  
1.5A  
1.5A  
3.5A  
7.5A  
3.5A  
T7022A1010 Remote Temperature Sensor.  
T7047C Remote Temperature Sensor.  
T7047G Remote Temperature Sensor.  
T7147A Remote Temperature Sensor and Override Module.  
W859F Packaged Economizer.  
W950A System Supervisor.  
W7459 Economizer Logic Module.  
C7046C Discharge Air Sensor.  
C7150B Discharge Air Sensor.  
Cool (all stages)  
Auxiliary (Economizer)  
Temperature Ratings:  
Operating: 40°F to 110°F (4°C to 43°C).  
Shipping: -20°F to +130°F (-29°C to +54°C).  
Display Accuracy: ±1°F (±0.5°C).  
Setpoint:  
Heating: 40°F to 90°F (4°C to 32°C).  
Cooling: 45°F to 90°F (7°C to 32°C).  
Dimensions: See Fig. 1.  
Deadband: 2°F (1°C); adjustable 2°F to 10°F (1°C to 6°C).  
Default Settings: See Table 2.  
LONMARK Functional Profile:  
Q7300H supports the LONMARK Functional Profile No. 8060,  
Thermostat Object (Type 09). See Fig. 2.  
Table 2. Default Setpoints.  
Control  
Heating  
Cooling  
Occupied  
70°F (21°C)  
78°F (26°C)  
Unoccupied  
55°F (13°C)  
90°F (32°C)  
6
3-12811  
2
href="
T7300F SERIES 2000 COMMERCIAL THERMOSTAT AND Q7300H COMMUNICATING SUBBASE  
6-11/16 (170)  
1/16 (2)  
3-3/16 (77)  
1-3/8 (35)  
1
(
-7/8  
47)  
4-1/8  
(105)  
1-11/16  
(
43)  
7-5/16 (186)  
7/8  
(22)  
4
-5/8  
Set Program  
Unoccupied  
Start Time  
Set Temperature  
Run  
Program  
Occupied  
Start Time  
Change  
Time/Temp  
(117)  
Occupied  
Temp  
Unoccupied  
Temp  
Day  
Temporary  
Occupied  
Set Current  
Day/Time  
Clear  
Start Time  
Heat/Cool  
Settings  
Copy  
Continous  
Unoccupied  
System  
Fan  
M16086A  
Fig. 1. Dimensions of T7300F, Q7300H in in. (mm).  
3
63-12811  
href="
T7300F SERIES 2000 COMMERCIAL THERMOSTAT AND Q7300H COMMUNICATING SUBBASE  
Hardware  
Output  
Thermostat Object  
Type Number 09.  
nviSetpoint  
SNVT_temp_p  
nvoHeatOutput  
SNVT_ lev_percent  
nv1  
nv2  
nvoCoolOutput  
SNVT_ lev_percent  
Mandatory nv3  
Network  
Variables  
nvoSpaceTemp  
SNVT_ temp_p  
nv4  
nv5  
nvoUnitStatus  
SNVT_hvac_status  
nviSpaceTemp  
SNVT_ temp_p  
nvoTerminalLoad  
nv6  
nv7  
nv8  
nv9  
nv11  
nv12  
nv13  
nv14  
SNVT_ lev_percent  
nviOccCmd  
SNVT_occupancy  
nvoEffectSetpt  
SNVT_ temp_p  
Optional  
Network  
Variables  
nviApplicMode  
SNVT_hvac_mode  
nvoTerminalfan  
SNVT_switch  
nviSetptOffset  
SNVT_ temp_p  
nvoEnergyHoldOff  
SNVT_switch  
nviEnergyHoldOff  
SNVT_switch  
nv10  
Configuration Properties  
nc49 - nciSndHrtBt  
SNVT_time_sec  
SNVT_time_sec  
SNVT_temp_p  
SNVT_str_asc  
SNVT_temp_setpt  
SNVT_temp_p  
SNVT_temp_p  
SNVT_temp_p  
SNVT_temp_p  
(mandatory)  
nc48 - nciRcvHrtBt  
nc64 - nciMin Delta  
nc17 - neiLocation  
nc60 - nciSetPnts  
nc79 - nciUpSPHeat  
nc80 - nciLrSPHeat  
nc76 - nciUpSPCool  
nc77 - nciLrSPCool  
(optional)  
(optional)  
(optional)  
(mandatory)  
(optional)  
(optional)  
(optional)  
(optional)  
Manufacturer  
Defined  
Section  
Hardware  
Input  
M16087A  
Fig. 2. Functional Profile Number 8060—LONMARK Thermostat Object (Type 09).  
Thermostat profile variables not used are grayed).  
(
NOTE: For additional information on the LONMARK Functional Profile, see the LONMARK Application Layer Interoperability  
Guidelines and the LONMARK Functional Profile: Thermostat. Both documents are available from LONMARK at internet  
address: www.lonmark.org.  
LONWORKS® and LONMARK® are registered trademarks of Echelon Corporation.  
®
Home and Building Control Home and Building Control  
Honeywell International  
Home and Building Control  
Honeywell Building  
17 Changi Business Park Central 1  
Singapore 486073  
Honeywell Europe  
S.A.  
3 Avenue du Bourget  
1140 Brussels  
Belgium  
Honeywell Latin American  
Region  
480 Sawgrass Corporate Parkway  
Suite 200  
Sunrise FL 33325  
Honeywell  
985 Douglas Drive North  
Golden Valley, MN 55422  
Honeywell Limited-Honeywell Limitée  
1
35 Dynamic Drive  
Scarborough, Ontario  
M1V 4Z9  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
6
3-12811 B.B. Rev. 9-01  
www.honeywell.com  

Honeywell T8602D Thermostat User Manual

Bryant TSTATBBPQ501 Thermostat User Manual

Aube TH113 F Thermostat User Manual

White Rodgers F145 1378 Thermostat User Manual

Lennox ComfortSenset 3000 Series Non Programmable Thermostat Thermostat User Manual

White Rodgers 1F95W 80 Thermostat User Manual

Aprilaire 8365 Thermostat User Manual

Aube Wine Thermometer Thermostat User Manual

Honeywell RTH2310 Thermostat User Manual

White Rodgers 1F83 0471 Thermostat User Manual