T775A,B,C,D REMOTE TEMPERATURE CONTROLLER  
					Programming Keys  
					The four programming keys are Select, Up and Down (arrows),  
					and Enter:  
					For example: Load 1: Compressor 1 (cool)  
					Setpt 1  
					Diff 1  
					On at  
					Off at  
					•
					Select: Sequentially prompts the user about what parameter  
					is being displayed. After the last parameter value is viewed,  
					pressing the Select key again displays the control values  
					from the beginning of the display loop. The parameters are:  
					2
					.
					For two sensor models (T775B), determine which loads  
					will be controlled from sensor A or sensor B and enter on  
					the worksheet.  
					—
					—
					—
					—
					—
					setpoint,  
					differential,  
					stage energized,  
					heat or cool (operation mode),  
					1,2,3,4 (indicating assigned stage).  
					For example: Load 1: Compressor 1 (cool)—Sensor A  
					•
					•
					Up and Down: Allow the displayed parameter to be  
					increased or decreased. After pressing Select, a control  
					value can be changed using these keys. Control values  
					increase or decrease by 1°F or 1°C each time an arrow key  
					is pressed.  
					Setpt 1  
					Diff 1  
					On at  
					Off at  
					Enter: Places the new value in the microprocessor memory.  
					3.  
					Determine setpoint (Setpt) and switching differential  
					Diff) for each load and enter on the worksheet.  
					(
					IMPORTANT  
					Control values/operations are not placed in the micro-  
					For example: Load 1: Compressor 1 (cool)—Sensor A  
					processor memory until the Enter key is pressed.  
					Setpt 1  
					Diff 1  
					78°F  
					4°F  
					On at  
					Off at  
					Press the Select and Enter keys at the same time to change  
					the control algorithm from heating to cooling or from cooling to  
					heating:  
					—
					Heating and cooling parameters are not displayed during  
					normal Select key sequences.  
					The only parameters displayed after pressing the Select  
					and Enter keys at the same time are the stage indication,  
					and the word heat or cool.  
					To change the operation from heating to cooling (or vice  
					versa) for a desired output stage, use the arrow keys.  
					The next stage of heat or cool assignment appears after  
					pressing the Select key. When all stages are programmed,  
					the display reverts to sensed temperature and load  
					energized status.  
					4.  
					Refer to the Control Algorithm subsection of Operation  
					section to calculate the load on and off temperatures.  
					Enter them on the worksheet.  
					—
					NOTE: Remember that the on/off outputs are off at  
					setpoint in both heating and cooling operating  
					modes. When in cooling mode, the load turns  
					off at setpoint plus the differential. When in  
					heating mode, the load turns on at setpoint  
					minus the differential.  
					—
					—
					For example: Load 1: Compressor 1 (cool)—Sensor A  
					NOTE: Control values and operation selection remain in the  
					device memory even after the power is removed.  
					Setpt 1  
					Diff 1  
					78°F  
					4°F  
					On at  
					Off at  
					82°F  
					78°F  
					Display  
					Once power is applied or restored to the device, the display  
					counts down from 210 until the display reads zero. During this  
					time all previously energized outputs de-energize. This is  
					intended to protect compressors in the event of a power failure.  
					CAUTION  
					The T775 will not allow the user to program for both  
					heating and cooling loads to be energized at the  
					same time.  
					NOTE: To avoid viewing the entire countdown, press the  
					Select key.  
					If this situation results, cooling loads will be energized  
					and heating loads will be prevented from energizing.  
					The number (1,2,3,4) of these nonenergized loads will  
					flash along with the word HEAT to indicate a call for  
					both heating and cooling loads controlled by one  
					sensor has occurred and to alert the user to reprogram  
					the affected control values.  
					The LCD display now shows what it normally reads:  
					—
					—
					—
					load (sensed) temperature,  
					stages energized,  
					and, for two sensor devices, the sensor (Sensor A or  
					Sensor B) being read.  
					5.  
					Remove the T775 cover and enter the values listed on  
					the worksheet and the date in the first column on the  
					label inside the T775 cover.  
					NOTE: At any time during programming, a 60 second pause  
					between key presses reverts the display to indicate  
					the sensed temperature and stage status.  
					For two sensor applications, the user has three options for  
					display of sensed temperature. The display can be configured  
					Keypad Programming and Display  
					The T775 utilizes a Liquid Crystal Display (LCD) for interactive  
					prompting during programming and display of sensed and  
					assigned setpoint and differential values. User programming of  
					the T775 is accomplished through the four programming keys.  
					to:  
					—
					—
					—
					lock onto continuous Sensor A,  
					lock onto continuous Sensor B sensed temperature,  
					alternate between Sensor A and Sensor B (at approximate  
					five-second intervals).  
					6
					3-2489—2  
					8