Honeywell TR71 Thermostat User Manual

Home

href="
®
Zio /Zio Plus LCD Wall Modules  
®
TR70, TR71, TR75 WITH Sylk Bus  
SPECIFICATION DATA  
Programmable for: Home screen options, tenant  
access, contractor access, optional password  
protection to contractor mode, access to controller  
parameters, setpoint, override, fan, and other  
parameters.  
Ability to access and adjust most parameters in the  
programmable controller.  
TR75 can access and adjust the controller schedule.  
Ability to balance the VAV system from the wall  
module.  
Home screen can display one to three of any of the  
following parameters: Temperature Setpoint, Room  
Temperature, Room Humidity, Outdoor Humidity,  
Outdoor Temperature, and Time, or one of virtually any  
parameter in the controller.  
Network bus jack.  
Simple 2-wire terminal connection to the  
programmable controller (includes power) and an  
optional 2-wire terminal connection for the network. All  
connections are polarity insensitive.  
GENERAL  
The TR70 Series Zio (TR70/TR70-H, TR71/TR71-H) and Zio  
Plus (TR75/TR75-H) are 2-wire, non-polarity sensitive, Sylk  
bus communicating wall modules for use with Spyder® and  
ComfortPoint™ programmable controllers.  
Permanent retention of user configuration, including  
setpoints after a power outage.  
Table 1. TR70 Series Features.  
All models have a space-temperature sensor, network bus  
jack, and an LCD panel with three softkeys and two Up/Down  
adjustment keys. The TR7-H, TR71-H and TR75-H models  
include an onboard humidity sensor.  
Zio  
Zio  
Zio Plus  
TR75  
Features  
TR70 TR71  
Scheduling  
x
4.9K  
x
Parameter Memory (bytes)  
Up to four Zios on Sylk  
Enumerated Values  
1K  
x*  
2K  
x
NOTE: Refer to the Zio/Zio Plus LCD Wall Modules Oper-  
ating Guide (form 63-2719) for information about  
customizing the wall module configuration in the  
WEBs-AX Workbench, such as modifying the  
default Home screens or creating your own appli-  
cation.  
x
x
Setpoint Limits as NVs – linking  
now possible  
x
x
System and Fan command as NVs  
Password protection  
x
x
x
x
x
x
FEATURES  
The TR70 Series wall modules include:  
Firmware version/model visible on  
display  
Ability to control tenant access to controller  
parameters via password protection.  
0.5 and 5 value increments  
x
x
x
x
Ability to assign labels for enumerated values.  
"-" and "/" characters in parameter  
names  
Customized parameter access, by using the Honeywell  
WEBs-AX Workbench tool.  
* Support for up to four TR71 and/or TR75s per Spyder, and if  
a TR70 is present, a maximum of three Zios (any combina-  
tion of models) are allowed.  
Ability to link setpoint limits to a network variable.  
6
3-1322-02  
href="
®
ZIO /ZIO PLUS LCD WALL MODULES  
SPECIFICATIONS  
1
2
3
4
NET-1  
NET-2  
S-BUS  
S-BUS  
(
optional)  
(optional)  
Compatibility: Full feature set, including scheduling and  
password protection requires the latest Spyder firmware  
SLOTS FOR SUBBASE  
LOCKING TABS (X4)  
HONEYWELL  
TR70-H  
YY WK  
PATENT PENDING  
(field upgradeable with Spyder Flash Tool), Spyder Tool  
GOLDEN VALLEY,MN  
ASSEMBLED IN MEXICO  
50028668-XXX  
version greater than 5.18, and WEBs-AX Workbench ver-  
sion 3.4.57 or greater.  
WALL MODULE BUS  
ADDRESS DIAL  
(DEFAULT SETTING = 1)  
1
0
2
3
Construction: Two-piece construction, cover and internally  
wired subbase. Field wiring, 18 to 24 AWG (0.82 to 0.20  
sq. mm), connects to a terminal block in the subbase.  
4
5
9
8
7 6  
S-BUS PROGRAMMABLE  
Mounting Options: The LCD wall modules can be mounted  
on a standard two by four inch junction box or on a 60 mm  
diameter junction box. The modules may be mounted up to  
CONTROLLER CONNECTION  
1
1
2
3
4
NETWORK BUS  
CONNECTION  
200 ft. (61 m) from the programmable controller. Twisted  
pair wiring is recommended for distances longer than 100  
ft. (30.5 m).  
Dimensions (H/W/D): See Fig. 2 on page 2.  
1
EACH OF THE TWO WIRE CONNECTIONS FOR THE S-BUS AND NETWORK  
BUS TERMINALS ARE POLARITY INSENSITIVE.  
M27349  
Environmental Ratings:  
Operating Temperature: 30°F to 110°F (-1°C to 43°C)  
Shipping Temperature: -40°F to 150°F (-40°C to 65.5°C)  
Relative Humidity: 5% to 95% non-condensing  
Fig. 1. LCD wall module components (rear view).  
NOTE: 18 Vdc power for the LCD wall modules is sup-  
plied from the programmable controller.  
Temperature Setpoint Range: Default range is 55°F to 85°F  
(10°C to 35°C); configurable for other ranges.  
Module Dimensions  
Temperature Sensor Accuracy: ±0.36°F at 77°F (±0.2°C at  
5°C)  
2
3 5/16 (84)  
Humidity Sensor Accuracy (TR71-H/TR75-H only): ±5%  
RH from 20% to 80% RH  
Power: 18 Vdc power is supplied to the wall module from the  
2-wire S-BUS connection to the programmable  
controller.  
Accessories: 50007298-001 (pack of 12) medium, cover  
plate; 6-7/8 x 5 in. (175 x 127 mm).  
4 5/8  
(
117)  
Approvals: CE; UL94-HB plastic enclosure; FCC Part 15,  
Class B  
Terminal Wiring Location  
Fig. 1 illustrates the location of the terminal block and other  
features on the TR70 Series wall modules.  
1
5/16  
24)  
(
M27347  
Fig. 2. Wall module dimensions in inches (mm).  
Communications  
The wall modules use a sensor bus (S-BUS) for  
communications with the programmable controller.  
For network communication, the building’s LON or BACnet®  
network wires connect to the two terminals (NET-1 and NET-  
2
). See Fig. 1. A network bus port is accessible at the bottom  
of the wall module by removing the jack plug.  
The network bus and S-BUS terminals (see Fig. 1) are  
insensitive to polarity, minimizing installation errors due to  
mis-wiring. The recommended wire size for the network bus  
63-1322—02  
2
href="
®
ZIO /ZIO PLUS LCD WALL MODULES  
and S-BUS is 18-24 AWG (0.82 to 0.20 sq mm) depending on  
application, plenum or non-plenum rated, unshielded, twisted  
pair, solid conductor wire.  
LCD Display  
The LCD display may be customized for tenant and contractor  
users. The following are a few samples of the various Home  
screens that are configurable for the LCD Wall Modules. Not  
all possible Home screens are illustrated here. There are  
many other configurable Home screens.  
NOTES:  
1.  
Home screens can display one to three of any of  
the following parameters: Temperature Setpoint,  
Room Temperature, Room Humidity, Outdoor  
Humidity, Outdoor Temperature, and Time, or one  
of virtually any parameter in the controller.  
M27377  
Fig. 5. Sample Tenant Home screen with  
Setpoint display only.  
2.  
Refer to the Zio/Zio Plus LCD Wall Modules Oper-  
ating Guide (form 63-2719) for information about  
customizing the wall module configuration in the  
WEBs-AX Workbench, such as modifying the  
default Home screens or creating your own appli-  
cation.  
Sample Tenant LCD Displays  
The Fan and Occupied settings are optional for Home screen  
setup. If there are no parameters configured for Tenant  
access, the “View More” softkey does not display on the  
Tenant Home screen.  
M27356  
Fig. 6. Sample Tenant “View More” display showing  
CO sensor value from controller.  
2
NOTE: Any configured parameter may be displayed.  
Sample Contractor LCD Displays  
The Contactor mode allows advanced options using the  
softkeys. Contractor mode also allows for customizing the  
Tenant view, including setting the tenant’s Home screen and  
“View More” access.  
M27354  
Fig. 3. Sample Tenant Home screen with System Status,  
Setpoint, Outside Temperature, and  
Room Temperature (predominant).  
M27357  
Fig. 7. Sample Contractor Home screen display with  
System Status, Setpoint, Outside Temperature,  
and Room Temperature (predominant).  
CONTACTOR HOME SCREEN SOFTKEYS  
The three softkeys on the Contractor Home screen (Fig. 7)  
provide the following:  
SET HOME SCREEN - allows the contractor to choose  
among multiple Home screen options for the tenant.  
M27379  
Fig. 4. Sample Tenant Home screen with Room  
Temperature and Time (predominant).  
3
63-1322—02  
href="
®
ZIO /ZIO PLUS LCD WALL MODULES  
SET VIEW MORE - allows the contractor to give additional  
parameter access (view only or adjustable) to the tenant.  
TYPICAL SPECIFICATION  
1
.
.
The wall module shall have an LCD display.  
The wall module shall have a customizable home  
screen:  
PARAMETERS - allows the contractor to monitor and/or  
adjust parameters in the programmable controller.  
2
a. Shall have the option to show up to 3 parameter  
values on a single display.  
b. Shall have the option to show occupied status.  
c. Shall have the option to show system status.  
d. Shall have the option to show fan status.  
e. Shall have the option to show up to three of the fol-  
lowing parameters:  
room temperature, setpoint, outside  
temperature, room humidity, outside humidity,  
time of day.  
f. Shall have the option to show on the home screen  
any single parameter in the controller, with a user  
defined 8 letter name.  
The wall module shall offer access to all parameters  
necessary to balance a VAV system.  
The wall module shall offer the ability to restrict access  
to parameter information with keypad enabled lock out  
and with optional 4 digit password protection (password  
on TR71 and TR75 only).  
M27358  
3
.
.
Fig. 8. Sample Contractor parameter display showing  
user-created discharge air parameter value.  
4
5.  
6.  
7.  
8.  
The wall module shall retain user configuration including  
setpoints after power outage.  
The wall module shall use a two wire polarity insensitive  
connection for all communication and power needs.  
The wall module shall offer the ability to access and  
adjust virtually all controller parameters.  
The wall module shall offer the ability for the tenant to  
adjust override time period within the limits set by the  
contractor.  
9.  
The wall module shall offer a communication jack for  
remote access to the network.  
M27359  
10. The wall module shall offer a ± 5% on board humidity  
sensor (TR70-H, TR71-H, and TR75-H only).  
Fig. 9. Sample Contractor parameter display showing  
sensor setpoint value (CO sensor from controller).  
1
1
1
1
1
1
1. The wall module shall be configured through the Honey-  
2
well WEBs-AX Workbench tool.  
2. The wall module shall communicate with other devices  
using the Sylk bus protocol.  
3. The wall module shall be compatible with LON and  
BACnet controllers.  
4. The wall module shall offer the ability to view/edit the  
controller's schedule (TR75 only).  
5. The wall module shall have the ability to display enu-  
merated values as text.  
NOTE: Any configured parameter may be displayed.  
6. The wall module shall have the ability to use the value of  
a parameter as the upper or lower limit of another  
parameter (TR75 only).  
ComfortPoint™ is a trademark of Honeywell International Inc.  
LONMARK® is a trademark of the LonMark Association.  
BACnet® is a registered trademark of BACnet International.  
Spyder® is a registered trademark of Honeywell International Inc.  
Sylk® is a registered trademark of Honeywell International Inc.  
Zio® is a registered trademark of Honeywell International Inc.  
Automation and Control Solutions  
Honeywell International Inc.  
1
985 Douglas Drive North  
®
U.S. Registered Trademark  
© 2011 Honeywell International Inc.  
3-1322—02 M.S. Rev. 12-11  
Printed in United States  
Golden Valley, MN 55422  
customer.honeywell.com  
6

Honeywell TH8321U1097 Thermostat User Manual

Aprilaire 8531 111 137B 97185 Thermostat User Manual

Honeywell T4039C Thermostat User Manual

Honeywell PRO TH3210D Thermostat User Manual

Honeywell 69 0786 2 Thermostat User Manual

White Rodgers 1F95EZ 0671 Thermostat User Manual

Honeywell AT72D1683 Thermostat User Manual

Honeywell T7984 B Thermostat User Manual

Lux Products PSDH021Ba Thermostat User Manual

Honeywell Q674C Thermostat User Manual