Smart Setback Recovery (via DIP switch #6)
Smart Setback Recovery (SSR) affects the way the ther-
mostat responds to program events. If SSR is disabled, the
thermostat will react to a program event at the time the
event occurs. However, if SSR is enabled, the thermostat
will react to a program event before the event occurs such
that the desired temperature is reached at the time of the
event, not after.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1, Y1, Y2, and E at
93°F+/−6°F.
Fan Control
AUTO or ON modes.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are
available. When programmed time has elapsed, a FILTER
indicator is displayed.
I/O Relays
All thermostat relays are latching type to minimize power
consumption.
Maintenance Reminder
Table 4
51M37 Terminal Designations
Term. Description
Settings of Off, 6 or 12 (months of chronological time) are
available. When programmed time has elapsed, a mainte-
nance indicator ꢀMAINT" is displayed.
B
Reversing valve, heat active
Reversing valve, cool active
24VAC
Service Reminder
O
R
The SERVICE indicator is displayed only under the follow-
ing conditions:
Y1
First-stage cooling/heating, compressor
energized
S
if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the R terminal;
W1*
Y2
Auxiliary heating, furnace energized
Second-stage cooling/heating, compressor
energized
OR
S
if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the C terminal.
E*
G
L
Emergency heat
Fan control
Service Indicator
Power Loss/Recovery
C
T
24VAC common
Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of program infor-
mation, HOLD status, programmed temperature setpoint,
heat/cool and fan mode settings, filter reminder status,
maintenance reminder status, and equipment protection
timers). After 24 hours of power loss, programmed settings
will be lost and replaced with default settings.
Outdoor temperature sensor connection 1
Outdoor temperature sensor connection 2
T
* For most applications, E will be jumpered to W1. If sep-
arate wires are not provided for both E and W1, jumper
the E terminal to the W1 terminal on the thermostat sub-
base. For applications involving the use of a balance
point (whereby the outdoor temperature is to be used to
restrict either heat pump operation or backup heat
source operation), the optional outdoor sensor (part
number X2658) MUST be installed.
IMPORTANT
Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
LCD Backlight
Activated for 30 seconds when any button is pressed.
Minimum furnace cycle time (elapsed time between any
furnace activation and the next furnace activation): 6 min-
utes.
NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is nor-
mal and will no longer occur after the electrical disturbance
has passed.
Minimum elapsed time between any compressor activa-
tion and the next compressor activation: 6 minutes.
Thermostat Operating Conditions
NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Page 9
51M37 SERIES 5/2