Calibration
Procedures
Calibration Procedure (Steps 1–4 apply to all thermostat models)
1. Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. See Figure 9 for unit application.
2. Remove the caps on the tees which are connected to the lines to the flow sensor. Connect a 0–2" magnehelic gage to monitor
flow sensor delta P. The higher-pressure port is further upstream on the air valve inlet.
3. Remove the thermostat line and connect a hand pump with a 0–20 psi gage to port “T”.
4. Tee a 0–20 psi gage in the line from port “B” on the volume regulator to the air valve actuator.
Normally-OpenValve
Normally-OpenValve
Reverse-Acting Thermostat
(See Figure 13 for proper
connections):
Reverse-Acting Thermostat
(See Figure 14 for proper
connections):
Direct-Acting Thermostat
(See Figure 13 for proper
connections)
Direct-Acting Thermostat
(See Figure 14 for proper
connections):
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum. If the
actuator pressure is less
than 3 psi, the air valve is
wide open and duct
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum flow. If
the actuator pressure is
greater than 13 psi, the air
valve is wide open and
duct pressure must
6. Monitor the delta P and
adjust the LO-stat mini-
mum) adjustment to
desired minimum.
6. Monitor the delta P and
adjust the LO-stat (mini-
mum) adjustment to
desired minimum.
7. Set port “T” input at 16
psi or greater with the
hand pump.
7. Set port “T” input at
16 psi or greater with the
hand pump.
pressure must increase to
increase flow.
8. Monitor the delta P and
adjust the HI-stat (maxi-
mum) adjustment to
8. Monitor the delta P and
adjust the HI-stat
increase to increase flow.
7. Set prot “T” to 16 psi
7. Set prot “T” to 16 psi
or greater with the
hand pump.
(maximum) adjustment
to desired maximum flow.
If the actuator pressure is
greater than 13 psi, the air
valve is wide open and duct
pressure must increase to
increase flow.
or greater with the
hand pump.
desired maximum flow. If
the actuator pressure is
less than 3 psi, the air
valve is wide open and
duct pressure must
8. Monitor the delta P and
adjust the HI-stat (mini-
mum) adjustment to
8. Monitor the delta P and
adjust the HI-stat (mini-
mum) adjustment to
desired minimum flow.
increase to increase flow.
desired minimum flow.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
10.Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10. Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10.Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10.Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
Figure 13–Connections of Direct/Reverse-Acting
Thermostat with Normally-Open Valve
Figure 14–Connections of Direct/Reverse-Acting
Thermostat with Normally-Closed Valve
0–2' Magnahelic Gage
HI LO
0–2' Magnahelic Gage
HI LO
Normally-Closed Unit
Normally-Open Unit
Apply 20 psi
Volume
Regulator
Apply 20 psi
Volume
Regulator
LO
LO
HI
HI
T
T
H
H
RESET START
LO STAT
RESET START
LO STAT
P
P
B
B
Actuator
Actuator
HI STAT
P
HI STAT
P
PSI
PSI
R
R
N
NO
NC
M
M
DAMPER
DAMPER
0
10
0
10
Connect 0–20 psi Gage
Connect 0–20 psi Gage
G
G
Airflow Sensor
Airflow Sensor
Connect Hand Pump
0–2 psi
Handpump
Connect Hand Pump
0–2 psi
Handpump
S
20
S
20
8
VAV-SVX02B-EN