White Rodgers 1F80 0261 Thermostat User Manual

Home

href="
Blue 2” Single Stage Thermostat  
Installation and Operating Instructions  
Save these instructions for future use!  
Model  
Programming Choices  
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS  
CAREFULLY BEFORE INSTALLING OR OPERATING THIS  
CONTROL COULD CAUSE PERSONAL INJURY AND/OR  
PROPERTY DAMAGE.  
1F80-0261  
5/1/1 Day Programmable  
APPLICATIONS  
1F80-0261 Thermostat  
For use with the following Class II systems:  
Single Stage systems  
Single-stage heat pump systems with no Aux heat  
DO NOT USE WITH:  
Systems exceeding 30 VAC and 1.5 amps  
3-wire zoned hydronic heating systems  
SPECIFICATIONS  
Electrical Rating:  
Battery Power................................................. mV to 30 VAC, 50/60 Hz or DC  
Input-Hardwire................................................ 20 to 30 VAC  
Terminal Load........................................................ 1.0 A per terminal, 1.5A maximum all terminals combined  
Setpoint Range...................................................... 45° to 90°F (7° to 32°C)  
Differential (Single Stage)...................................... Heat 0.6°F; Cool 1.2°F (adjustable)  
Differential (Heat Pump)........................................ Heat 1.2°F; Cool 1.2°F (adjustable)  
Operating Ambient................................................. 32° to +105°F (0° to +41°C)  
Operating Humidity................................................ 90% non-condensing max.  
Shipping Temperature Range................................ -40° to +150°F (-40° to +65°C)  
Dimensions Thermostat......................................... 3-3/4”H x 4-3/4”W x 1-1/2”D  
PRECAUTIONS  
This thermostat is intended for use with a low voltage NEC  
WARNING  
Do not use on circuits exceeding specified voltage.  
Higher voltage will damage control and could cause  
shock or fire hazard.  
!
Class II system. Do not use this thermostat with a line voltage  
system. If in doubt about whether your wiring is millivolt, line,  
or low voltage, have it inspected by a qualified heating and air  
conditioning contractor or electrician.  
Do not exceed the specification ratings.  
Do not short out terminals on gas valve or primary  
control to test. Short or incorrect wiring will damage  
thermostat and could cause personal injury and/or  
property damage.  
All wiring must conform to local and national electrical codes  
and ordinances.  
This control is a precision instrument, and should be handled  
carefully. Rough handling or distorting components could  
cause the control to malfunction.  
Thermostat installation and all components of the  
system shall conform to Class II (current limited)  
circuits per the NEC code. Failure to do so could  
cause a fire hazard.  
CAUTION  
!
To prevent electrical shock and/or equipment damage,  
disconnect electric power to system at main fuse or  
circuit breaker box until installation is complete.  
PART NO. 37-7009B  
Replaces 37-7009A  
0917  
href="
INSTALLATION  
Battery  
Door  
REMOVE OLD THERMOSTAT  
1. Shut off electricity at the main fuse box until installation is  
complete. Ensure that electrical power is disconnected.  
2. Remove the front cover of the old thermostat. With wires  
still attached, remove wall plate from the wall. If the  
old thermostat has a wall mounting plate, remove the  
thermostat and the wall mounting plate as an assembly.  
Mounting  
Hole  
Mounting  
Hole  
3. Identify each wire attached to the old thermostat using  
the labels enclosed with the new thermostat.  
4. Disconnect the wires from old thermostat one at a time. DO  
O/B  
Switch  
NOT LET WIRES FALL BACK INTO THE WALL.  
5. Install new thermostat using the following procedures.  
Opening  
for wires  
Gas/Elec  
Switch  
ATTENTION!  
Figure 1.Thermostat Base  
This product does not contain mercury. However, this product  
may replace a unit which contains mercury.  
GAS / ELEC SWITCH  
Do not open mercury cells. If a cell becomes damaged, do  
not touch any spilled mercury. Wearing nonabsorbent gloves,  
take up the spilled mercury and place into a container which  
can be sealed. If a cell becomes damaged, the unit should be  
discarded.  
If your system is a heat pump, the GAS/ELEC Switch must be  
set to ELEC (see Fig. 1) If your system is a single stage, the  
switch must be set to GAS. The switch setting must agree with  
the system configuration selected in the configuration menu.  
Mercury must not be discarded in household trash. When the  
unit this product is replacing is to be discarded, place in a  
to send the product containing mercury.  
BATTERY LOCATION  
ATTACH THERMOSTAT BASE TO WALL  
“AA” Alkaline Batteries  
1. Remove the packing material from the thermostat. Gently  
pull the cover straight off the base. Forcing or prying on the  
thermostat will cause damage to the unit.  
2. Place base over hole in wall and mark mounting hole  
locations on wall using base as a template (see Fig.1).  
Two “AA” alkaline batteries are installed in your thermostat  
with a battery tag to prevent power drainage. Prior to use,  
open the battery door and remove the battery tag. To open,  
pull the battery door as shown by the arrow and lift open. The  
two “AA” batteries will operate all functions or maintain time  
and continuously display the temperature during a loss of AC  
power. Installed batteries will also allow programming prior to  
installation. To replace batteries, pull the battery door shown  
by the arrow and lift open. Using the polarity indicated inside  
the battery door, insert the batteries. To close the battery door,  
swing the door down while pulling in the direction of arrow.  
Once fully down, snap the door back into position.  
3. Move base out of the way. Drill mounting holes.  
4. Push wires through opening in thermostat base.  
5. Fasten base loosely to wall using two mounting screws.  
Place a level against bottom of base, adjust until level,  
and then tighten screws. (Leveling is for appearance only  
and will not affect thermostat operation.) If you are using  
existing mounting holes, or if holes drilled are too large and  
do not allow you to tighten base snugly, use plastic screw  
anchors to secure subbase.  
6. Connect wires to terminals on base using appropriate  
wiring schematic (see figs. 2 through 4).  
Thermostat can be powered by system AC power or Battery. If  
7. Push excess wire into wall and plug hole with a fire-resistant  
material (such as fiberglass insulation) to prevent drafts  
from affecting thermostat operation.  
isdisplayed, thethermostatisbatterypowered.If  
isnot  
displayed, thermostat is system powered with optional battery  
back-up. When battery power remaining is approximately half,  
the  
will be displayed. When “Change  
is displayed,  
install fresh “AA” alkaline batteries immediately. For best  
results, use new premium brand alkaline batteries such as  
Duracell® or Energizer®. We recommend replacing batteries  
every 2 years. If the home is going to be unoccupied for an  
O/B TERMINAL SWITCH SELECTION  
The O/B switch on this thermostat is factory set to the “O”  
position. This will accommodate the majority of heat pump  
applications, which require the changeover relay to be  
energized in COOL. If the thermostat you are replacing or the  
heat pump being installed with this thermostat requires a “B”  
terminal, to energize the changeover relay in HEAT, the O/B  
switch must be moved to the “B” position.  
extended period (over 3 months) and  
is displayed, the  
batteries should be replaced before leaving. When less than  
two months of battery life remain, the setpoint temperature will  
offset by 10 degrees (10 degrees cooler in Heat mode / 10  
degrees warmer in Cool mode). If offset occurs, the normal  
setpoint can be manually reset with  
or  
. Another offset  
will occur within two days if batteries are not replaced. To  
replace the batteries, set system to OFF.  
2
href="
INSTALLATION  
automatically start the heating system at 5:00 AM, so that the  
programmed temperature of 70°F is reached by about 6:00  
AM.  
ENERGY MANAGEMENT RECOVERY  
(EMR)  
When the EMR feature is activated the thermostat’s  
microcomputer calculates the time it will take to change the  
room temperature to the next heat or cool program setting.  
Then the thermostat will start the system before the next  
programmed period so that the desired temperature is reached  
at or near the beginning of the period (the thermostat calculates  
15 minutes for every 1°F temperature change). This feature  
provides better efficiency by allowing gradual temperature  
changes.  
If the overnight room temperature drops only to 68°F, the  
thermostatwillstartthesystemat5:30toreachtheprogrammed  
temperature of 70°F at 6:00.  
The thermostat is shipped with the EMR feature active, which  
means that the thermostat will start the heating system before  
the beginning of the next program period.  
To deactivate the EMR function, see the Configuration menu  
on Page 5).The thermostat will then wait until the programmed  
time to start the system for a temperature change.  
For example: The thermostat is programmed to provide an  
overnight heating temperature of 66°F, and during the next  
program period, beginning at 6:00 AM, the programmed  
temperature is 70°F. With EMR activated, the thermostat will  
WIRING DIAGRAMS  
Optional Jumper for  
Single Stage Heat Pump  
THERMOSTAT  
R
O/B  
Y
G
W
C
SYSTEM  
Changeover  
Relay*  
Fan  
Relay  
Optional  
Compressor  
Contactor  
Heat Relay  
Hot  
24 VAC  
120 VAC  
Neutral  
* Changeover Relay is energized in COOL when O/B switch is in the “O” position  
Changeover Relay is energized in HEAT when O/B switch is in the “B” position  
TRANSFORMER  
(Class II Current Limited)  
Figure 2.Typical wiring diagram for single transformer single stage systems  
NOTE  
If safety circuits are in  
only one of the systems,  
remove the transformer  
of the system with NO  
safety circuits.  
Optional Jumper for  
Single Stage Heat Pump  
THERMOSTAT  
SYSTEM  
O/B  
Y
G
W
C
R
CUT AND  
TAPE OFF!  
Changeover  
Relay*  
Fan  
Relay  
Limit or  
Safety  
Switches  
Optional  
HOT  
120 VAC  
24 VAC  
Compressor  
Contactor  
Heat Relay  
NEUTRAL  
Hot  
24 VAC  
120 VAC  
Neutral  
TWO COMMONS MUST  
BE JUMPERED TOGETHER!  
TRANSFORMER  
(Class II Current Limited)  
* Changeover Relay is energized in COOL when O/B switch is in the “O” position  
Changeover Relay is energized in HEAT when O/B switch is in the “B” position  
Figure 3.Typical wiring diagram for two transformer single stage systems with NO safety circuits  
3
href="
WIRING DIAGRAMS  
NOTE  
Polarity must be observed. If the HOT side of the  
second transformer is jumpered to the COMMON side  
of the first transformer a short will be made. Damage  
to equipment will occur when power is restored.  
Optional Jumper for  
Single Stage Heat Pump  
THERMOSTAT  
O/B  
Y
G
W
C
R
SYSTEM  
Limit or  
Safety  
Limit or  
Safety  
Switches  
HOT  
Switches  
24 VAC  
120 VAC  
Changeover  
Relay*  
Fan  
Relay  
NEUTRAL  
Optional  
24 VAC  
Auxiliary  
Heating  
Transformer  
(Class II  
NOTE  
ACCESSORY  
RELAY N.O.  
CONTACT  
The accessory relay scheme  
is required when safety  
circuits exist in both systems.  
Compressor  
Contactor  
Heat  
Relay  
Current Limited)  
COMMON  
TWO COMMONS MUST  
BE JUMPERED TOGETHER!  
Limit or  
Limit or  
Safety  
Switches  
Safety  
HOT  
Switches  
24 VAC  
120 VAC  
COMMON  
NEUTRAL  
* Changeover Relay is energized in COOL when O/B switch is in the “O” position  
Changeover Relay is energized in HEAT when O/B switch is in the “B” position  
Heat Pump Transformer  
(Class II Current Limited)  
Figure 4.Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems  
THERMOSTAT QUICK REFERENCE  
12  
13  
Before you begin programming your thermostat, you should be  
familiar with its features and with the display and the location  
and operation of the thermostat buttons and switches (see  
fig. 5). Your thermostat consists of two parts: the thermostat  
cover and the base. To remove the cover, pull it straight out  
from the base. To replace the cover, line up the cover with the  
base and press until the cover snaps onto the base.  
Displays current temperature.  
“Serviceindicatesadiagnosticfaultintheheating/cooling  
system. It does not indicate a fault in the thermostat.  
14  
15  
“Change Filter” is displayed when the system has run for  
the programmed filter time period as a reminder to change  
or clean your air filter.  
indicates power level of batteries. “Change  
indicates batteries should be replaced.  
The Thermostat Buttons and Switches  
16  
17  
18  
Indicates time.  
1
2
3
4
5
6
7
Raises temperature setting.  
Lowers temperature setting.  
TIME button.  
“AP” indicates time as Morning (A) Evening (P).  
“Temp Holdindicates temporary hold or“Hold” indicates  
hold mode.  
SYSTEM switch (COOL, OFF, HEAT, EMER).  
PRGM (program) button.  
FAN switch (ON, AUTO).  
RUN/HOLD (program) button.  
Figure 5.Thermostat display, buttons, and switches  
1
2
The Display  
Indicates days of the week.  
Indicates setpoint temperature.This is blank when system  
switch is in the OFF position. Setpoint temperature is  
displayed (flashing) if the thermostat is in lockout mode to  
prevent the compressor from cycling too quickly.  
8
9
SYSTEM  
10  
11  
“Save” indicates the Cool Savings feature is enabled in  
the configuration menu. “Save” (flashing) indicates Cool  
Savings feature is active.  
3
4
7
6
5
Flame icon ( ) is displayed when the SYSTEM switch is  
in the HEAT position. Flame icon ( ) is displayed flashing  
when thermostat is calling for heat. Snowflake icon ( )  
is displayed (non-flashing) when the SYSTEM switch is  
in the COOL position. Snowflake icon ( ) is displayed  
(flashing) if the thermostat is calling for cool.  
17  
13  
18  
8
9
16  
15  
10  
14  
12  
11  
4
href="
INSTALLER/CONFIGURATION MENU  
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements.  
To enter the menu: Set your thermostat to OFF and press the  
and  
buttons simultaneously. The display will show the  
first item in the configuration menu. Press RUN/HOLD to change to the next menu item or press TIME to go backwards to the  
previous item in the menu. To exit the menu and return to the program operation, press PRGM. If no keys are pressed within  
fifteen minutes, the thermostat will revert to normal operation.  
Configuration Menu  
Menu  
Reference  
Number  
Press  
Key  
Displayed  
(Factory  
Default)  
Comments  
Press  
to select from  
listed options  
or  
1
SS  
HP  
Select Single Stage (SS) or  
Heat Pump (HP, 1 compressor)  
and  
2
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
CS  
(OFF)  
On  
Select Cool Savings Feature On or OFF  
CS  
(3)  
1, 2, 3, 4, 5, 6  
OFF  
If CS selected On, selects Cool Savings value  
Select Energy Management Recovery On or OFF  
3
4
E
(On)  
CR Heat  
(ME)  
FA, SL  
SL  
Select Adjustable Anticipation, cycle rate,  
Heat Single Stage  
5
CR Cool  
(FA)  
Select Adjustable Anticipation, cycle rate,  
Cool Single Stage  
6
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
RUN/HOLD*  
CL  
(OFF)  
On  
Select Compressor lockout OFF or On  
7
L
(On)  
OFF  
Select Display Light On or OFF  
8
Temp  
(0 HI)  
oF  
4 LO to  
4 HI  
oC  
Select temperature display adjustment higher or lower  
9
Select oF / oC Display (temperature units in Fahrenheit  
or Celsius)  
10  
Change Filter  
(OFF)  
On  
Select filter replacement indicator OFF or On  
Change Filter  
(200 h)  
25 to 1975  
If Change Filter selected On, selects time interval for  
Change Filter Indicator. (in 25 hour increments)  
11  
Returns to normal operation  
*Press RUN/HOLD to advance to next item or TIME to move backwards to previous item  
3) Select Energy Management Recovery  
-
Energy  
1) System Configuration - Selects SS (Single Stage) or HP  
(Heat Pump) operating mode. Default configuration is SS.  
For Heat Pump operation choose HP.  
Management Recovery (E) On enables the thermostat  
to start heating or cooling early to make the building  
temperature reach the program setpoint at the time you  
specify. Heating will start 5 minutes early for every 1° of  
temperature required to reach setpoint. Example: E On is  
selected and your heating is programmed to 65o at night  
and 70o at 7AM. If the building temperature is 65o, the  
difference between 65o and 70o is 5o. Allowing 5 minutes  
per degree, the thermostat Setpoint will change to 70o at  
6:35 AM. Cooling allows more time per degree, because it  
takes longer to reach set temperature.  
2) Select CS (Cool Savings™) - With Cool Savings™  
enabled, the thermostat will make small adjustments to  
the Setpoint temperature during periods of high demand  
to reduce cooling system running time and save energy.  
When the cooling system has been running for more than  
20 minutes, humidity in the home will be lower and a higher  
setpoint temperature will feel comfortable. After 20 minutes  
of run time, the thermostat will start increasing the setpoint  
temperature in steps of less than one degree as the system  
continues to run. These adjustments will eventually cause  
the system to satisfy the thermostat and turn the system off  
to reduce the energy consumption.When the Cool Savings  
feature is active and making adjustments, the display will  
show “Save”.The amount of the adjustments to the setpoint  
temperature is dependent on the Cool Savings value that  
is set, 1 being the least adjustment and 6 being the most  
adjustment. With this feature set to OFF, no change will  
occur when the cooling system is continuously running  
during the periods of high demand. Periods of high demand  
will normally occur during the late afternoon and early  
evening on the hottest days of the summer.  
4 & 5) Select Cycle Rate Selection - The factory default  
setting for Single Stage Heat is Medium Cycle (ME). For  
Single Stage Cool the default setting is fast (FA).To change  
cycle rate, press the  
and  
buttons.  
The cycle rate differentials for different settings are:  
MODE  
Fast  
(FA)  
Medium  
(ME)  
0.8°F  
-
Slow  
(SL)  
SS Heat  
SS Cool  
0.6°F  
1.2°F  
1.2°F  
1.7°F  
5
href="
INSTALLER/CONFIGURATION MENU  
6) Select Compressor Lockout CL OFF or ON - Selecting  
CL On will cause the thermostat to wait 5 minutes between  
cooling cycles. This is intended to help protect the  
compressor from short cycling. Some newer compressors  
already have a time delay built in and do not require this  
feature. Your compressor manufacturer can tell you if the  
lockout feature is already present in their system.When the  
thermostat compressor time delay occurs, it will flash the  
setpoint for up to five minutes.  
8) Select Temperature Display Adjustment 4 LO to 4 HI -  
Allows you to adjust the room temperature display up to 4°  
higher or lower. Your thermostat was accurately calibrated  
at the factory but you have the option to change the display  
temperature to match your previous thermostat. The  
current or adjusted room temperature will be displayed on  
the display.  
9) Select F° or C° Readout - Changes the display readout to  
Celsius or Fahrenheit as required.  
7) Select Backlight Display - The display backlight improves  
display contrast in low lighting conditions. When the “C”  
terminal is connected, selecting backlight CdL On will keep  
the light on continuously. Select backlight OFF will turn the  
light on momentarily when any key is pressed. When the  
“C” terminal is not connected, regardless of the backlight  
selection, the light will be on momentarily when any key is  
pressed.  
10) Select Filter Replacement Reminder and Set Run Time  
Select the “Change Filter” reminder On or OFF. If selected  
On, press RUN/HOLD to select the time period from 25 to  
1975 hours in 25 hour increments. In a typical application,  
200 hours (default) of run time is approximately 30 days.  
After the selected time of blower operation, the thermostat  
will display “Change Filter” as a reminder to change or  
clean your air filter. When “Change Filter” is displayed,  
press the RUN/HOLD button to clear the display and restart  
the time to the next filter change. A selection of OFF will  
cancel this feature.  
OPERATION  
CHECK THERMOSTAT OPERATION  
If at any time during testing your system does not operate  
properly, contact a qualified service person.  
3. Press  
to adjust temperature setting above room  
temperature. The cooling system should stop operating.  
Turn on power to the system.  
CAUTION  
!
Fan Operation  
If your system does not have a G terminal connection, skip to  
Heating System.  
Do not allow the compressor to run unless the  
compressor oil heaters have been operational for 6  
hours and the system has not been operational for at  
least 5 minutes.  
1. Move fan switch to ON position.The blower should begin to  
operate.  
2. Move fan switch to AUTO position. The blower should stop  
immediately.  
MANUAL OPERATION  
HOLD TEMPERATURE — With the SYSTEM switch set  
to HEAT or COOL, momentarily press RUN/HOLD button.  
Heating System  
1. Move SYSTEM switch to HEAT position. If the auxiliary  
HOLD will be displayed. Use  
or  
to adjust the  
temperature.The thermostat will hold the room temperature  
at the selected setting until you press RUN/HOLD button to  
start program operation again.  
heating system has a standing pilot, be sure to light it.  
2. Press  
to adjust thermostat setting to 1° above room  
temperature. The system should begin to operate.  
TEMPERATURE OVERRIDE (TEMPORARY HOLD)  
3. Press  
to adjust temperature setting below room  
temperature. The heating system should stop operating.  
Press or untilthetemperatureyouwantisdisplayed.  
The thermostat will override current programming and  
keep the room temperature at the selected temperature for  
2 hours or until the next program period begins. Then the  
thermostat will automatically revert to the program.  
Cooling System  
CAUTION  
!
To prevent compressor and/or property damage, if the  
outdoor temperature is below 50oF, DO NOT operate  
the cooling system.  
1. Move SYSTEM switch to COOL position.  
2. Press  
to adjust thermostat setting below room  
temperature. The blower should come on immediately on  
high speed, followed by cold air circulation. However, if the  
setpoint temperature is flashing, the compressor lockout  
feature is operating (see Configuration menu, item 6).  
6
href="
PROGRAMMING  
3. Press TIME once again. The display window will show the  
minutes only.  
PROGRAMMINGYOUR THERMOSTAT  
This section will help you plan your thermostat’s program to  
meet your needs. For maximum comfort and efficiency, keep  
the following guidelines in mind when planning your program.  
EXAMPLE:  
4. Press and hold either  
minutes.  
or  
until you reach the correct  
When heating (cooling) your building, program the  
temperatures to be cooler (warmer) when the building is  
vacant or during periods of low activity.  
5. Press TIME once again. The display will show the day of  
the week.  
During early morning hours, the need for cooling is usually  
minimal.  
6. Press  
week.  
or  
until you reach the current day of the  
PlanningYour Program  
7. Press RUN/HOLD once. The display will show the correct  
time, day, room temperature and set-point temperature.  
Look at the factory preprogrammed times and temperatures  
shown in the sample schedule. If this program will suit your  
needs, simply press the RUN/HOLD button to begin running  
the factory preset program.  
Enter Heating Program  
1. Move the SYSTEM switch to HEAT.  
If you want to change the preprogrammed times and  
temperatures, follow these steps.  
2. Press PRGM once. “Mo Tu We Th Fr” (indicating weekday  
program) will appear in the display. Also displayed are the  
currently programmed start time for the 1st heating period  
and the currently programmed temperature (flashing).  
Determine the time periods and temperatures for your program.  
You must program four periods for each day. However, you  
may use the same heating and cooling temperatures for  
consecutive time periods.You can choose start times, heating  
temperatures, and cooling temperatures independently (for  
example, you may select 5:00 AM and 70° as the daily 1st  
period heating start time and temperature, and also choose  
7:00 AM and 76° as the daily 1st period cooling start time  
and temperature).  
EXAMPLE:  
This display window shows that for the 1st weekday  
period, the start time is 6:00 AM, and 70° is the  
programmed temperature (this example reflects factory  
preprogramming).  
Use the table to plan your program time periods and the  
temperatures you want during each period. Fill in the complete  
table to have a record of your programs.  
3. Press  
or  
to change the displayed temperature  
to your selected temperature for the 1st heating program  
period.  
4. Press TIME once (the programmed time will flash). Press  
EnteringYour Program  
or  
until your selected time appears. The time will  
Set Current Time and Day  
change in 15 minute increments. When your selected time  
is displayed, press TIME again to return to the change  
temperature mode.  
1. Press TIME button once. The display will show the hour  
only.  
5. Press PRGM once. The currently programmed start time  
and setpoint temperature for the 2nd heating program  
period will appear.  
EXAMPLE:  
2. Press and hold either  
or  
until you reach the correct  
6. Repeat steps 3 and 4 to select the start time and heating  
temperature for the 2nd heating program period.  
hour and AM/PM designation (AM begins at midnight; PM  
begins at noon).  
7. Repeat steps 3 through 5 for the 3rd and 4th heating  
program periods.  
SAMPLE  
Heating/Cooling Schedule Plan (Factory Program)  
Heating/Cooling Schedule Plan  
WEEKDAYS  
(5 Day)  
SATURDAY  
(1 Day)  
SUNDAY  
(1 Day)  
WEEKDAYS  
(5 Day)  
SATURDAY  
(1 Day)  
SUNDAY  
(1 Day)  
Start  
Time  
Start  
Time  
Start  
Time  
Start  
Time  
Start  
Time  
Start  
Time  
Period  
1ST  
Period  
1ST  
Temp  
Temp  
Temp  
Temp  
Temp  
Temp  
6:00 AM  
70F 6:00 AM  
70F 6:00 AM  
70F  
62F  
70F  
2ND  
3RD  
4TH  
1ST  
2ND  
3RD  
4TH  
2ND  
3RD  
4TH  
1ST  
2ND  
3RD  
4TH  
8:00 AM  
5:00 PM  
62F 8:00 AM  
70F 5:00 PM  
62F 8:00 AM  
70F 5:00 PM  
10:00 PM 62F 10:00 PM 62F 10:00 PM 62F  
6:00 AM  
8:00 AM  
5:00 PM  
78F 6:00 AM  
85F 8:00 AM  
78F 5:00 PM  
78F 6:00 AM  
85F 8:00 AM  
78F 5:00 PM  
78F  
85F  
78F  
10:00 PM 82F 10:00 PM 82F 10:00 PM 82F  
7
href="
PROGRAMMING  
8. Press PRGM once. “SA” (indicating Saturday program)  
will appear in the display, along with the start time for  
the 1st heating period and the currently programmed  
temperature.  
CHECKYOUR PROGRAMMING  
Follow these steps to check your thermostat programming one  
final time before beginning thermostat operation.  
1. Move SYSTEM switch to HEAT position.  
9. Repeat steps 3 through 7 to complete Saturday heating  
programming.  
2. Press PRGM to view the 1st weekday heating period time  
and temperature. Each time you press PRGM, the next  
heating period time and temperature will be displayed in  
sequence for weekday, then Saturday and Sunday program  
periods (you may change any time or temperature during  
this procedure).  
10. Press PRGM once to change to SU (Sunday) heating  
programming and repeat steps 3 through 7 to complete  
Sunday programming.  
11. When you have completed entering your heating program,  
press RUN/HOLD.  
3. Press RUN/HOLD.  
4. Move SYSTEM switch to COOL position.  
5. Repeat step 2 to check cooling program.  
Enter Cooling Program  
CAUTION  
!
6. Move SYSTEM switch to HEAT or COOL and press RUN/  
HOLD to begin program operation.  
If the outside temperature is below 50oF, disconnect  
power to the cooling system before programming.  
Energizing the air conditioner compressor during  
cold weather may cause personal injury or property  
damage.  
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO  
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!  
1. Move SYSTEM switch to COOL position.  
2. Follow Enter Heating Program for entering your  
cooling program, using your selected cooling times and  
temperatures.  
8
href="
TROUBLESHOOTING  
Reset Operation  
If a voltage spike or static discharge blanks out the display  
or causes erratic thermostat operation, reset the thermostat  
If the thermostat has power, has been reset and still does not  
function correctly contact your heating/cooling service person  
or place of purchase.  
by pressing the  
,
and TIME buttons simultaneously.  
Symptom  
Possible Cause  
Corrective Action  
No Heat/No Cool/No Fan  
(common problems)  
1. Blown fuse or tripped circuit breaker. Replace fuse or reset breaker.  
2. Furnace power switch to OFF. Turn switch to ON.  
3. Furnace blower compartment door or Replace door panel in proper position to engage safety  
panel loose or not properly installed. interlock or door switch.  
No Heat  
1. System Switch not set to Heat.  
Set System Switch to Heat and raise setpoint above  
room temperature.  
2. Loose connection to thermostat or  
system  
3. Heating System requires service or  
thermostat requires replacement.  
Verify thermostat and system wires are securely attached.  
Diagnostic: Set System Switch to Heat and raise the  
setpoint above room temperature. Within a five minutes  
the thermostat should make a soft slick sound. This  
sound usually indicates the thermostat is operating  
properly. If the thermostat does not click, try the reset  
operation listed above. If the thermostat does not click  
after being reset contact your heating and cooling  
service person or place of purchase for a replacement.  
If the thermostat clicks, contact the furnace manufac-  
turer or a service person to verify the heating system is  
operating correctly.  
No Cool  
1. System Switch not set to Cool.  
Set System Switch to Cool and lower setpoint below  
room temperature.  
2. Loose connection to thermostat or  
system.  
3. Cooling System requires service or  
thermostat requires replacement  
Verify thermostat and system wires are securely attached.  
Same procedures as diagnostic for No Heat condi-  
tion except set the thermostat to Cool and lower the  
setpoint below the room temperature. There may be up  
to a five minute delay before the thermostat clicks in  
Cooling if the compressor lock-out option is selected in  
the configuration menu (Item 6).  
Heat, Cool or Fan Runs  
Constantly  
1. Possible short in wiring.  
2. Possible short in thermostat.  
3. Possible short in Heat/Cool/Fan  
system.  
Check each wire connection to verify they are not  
shorted or touching together. No bare wire should  
stick out from under terminal screws. Try resetting the  
thermostat as described below. If the condition persists,  
the manufacturer of your system or service person  
can instruct you on how to test the Heat/Cool/ system  
for correct operation. If the system operates correctly,  
replace the thermostat.  
4. Fan Switch set to Fan On.  
Furnace CyclesToo Fast orToo Slow 1. The location of the thermostat and/  
Item 4 (CR Heat) or 5 (CR Cool) in the Configuration  
Cooling CyclesToo Fast orToo Slow  
(narrow or wide temperature swing)  
or the size of the Heating or Cooling Menu is the adjustment that controls the cycle rate. If  
System may be influencing the  
cycle rate.  
an acceptable cycle rate is not achieved using the FA  
(Fast) or SL (Slow) adjustment contact a local service  
person for additional suggestions.  
Thermostat Setting and  
Thermometer Disagree  
1. Thermostat thermometer setting  
requires adjustment.  
The thermometer can be adjusted +/- degrees as listed  
in item 8 of the Configuration Menu. No other adjust-  
ment is possible.  
Clock Loses or Gains Time  
1. Loss of power to thermostat.  
The thermostat will maintain its program in memory  
even with no power but the clock time will be incorrect  
when power is restored. See No Heat/No Cool /No Fan  
(common problems) above for items to check in the  
system.  
Heat or Cool Starts Early  
1. EMR activated.  
See Configuration Menu (Item 3)  
Thermostat Does Not Follow  
Program  
1. AM or PM set incorrectly in program. Check current clock and program settings including  
2. AM or PM set incorrectly on the clock. the AM or PM designations for each time period. If a  
3. Voltage spike or static discharge.  
voltage spike or static discharge occurs use the Reset  
4. See “Heat or Cool Starts Early” above. Operation listed above.  
Blank Display and/or Keypad Not 1. Voltage Spike or Static Discharge.  
Responding  
If a voltage spike or static discharge occurs use the  
Reset Operation listed above.  
9
href="
NOTES  
10  
href="
NOTES  
11  
href="
Homeowner Help Line: 1-800-284-2925  
White-Rodgers is a division  
of Emerson Electric Co.  
The Emerson logo is a  
trademark and service mark  
of Emerson Electric Co.  

Lennox l7742u Thermostat User Manual

White Rodgers 1F70 Thermostat User Manual

White Rodgers 1F97 0671 Thermostat User Manual

Honeywell T8621D Thermostat User Manual

White Rodgers 1D56 310 Thermostat User Manual

White Rodgers 1C26 Thermostat User Manual

White Rodgers 2B61 186 Thermostat User Manual

White Rodgers 37C72U Thermostat User Manual

Honeywell RTH111 Thermostat User Manual

Honeywell R7849B Thermostat User Manual