INSTALLER/CONFIGURATION MENU  
					1) This control can be configured for:  
					8) Select Compressor Lockout CL OFF or ON – Select-  
					ing CL ON will cause the thermostat to wait 5 minutes  
					between cooling cycles. This is intended to help protect  
					the compressor from short cycling. Some newer com-  
					pressors already have a time delay built in and do not  
					require this feature.Your compressor manufacturer can  
					tell you if the lockout feature is already present in their  
					system. When the thermostat compressor time delay oc-  
					curs, it will flash the setpoint for up to five minutes.  
					MS 2 – Multi-Stage System (no heat pump)  
					HP 1 – Heat Pump with one stage of compressor  
					HP 2 – Heat Pump with two stage compressor or two  
					compressor system, Gas or Electric backup  
					SS 1 – Single Stage System  
					2) GAS or Electric (ELE) fan operation. If the heating sys-  
					tem requires the thermostat to energize the fan, select  
					ELE. Select GAS if the heating system energizes the fan  
					on a call for heat.  
					9) System Mode Configuration – This thermostat is  
					configured for Heat and Cool (SYSTEM switch with Cool,  
					Off, Heat) default. It can also be configured for Heat and  
					Cool with Auto changeover (Heat, Auto, Cool, Off), Heat  
					only with fan (Off, Heat), Heat only without fan, Auto only  
					(Auto, Off), and Cool only (Cool, Off).  
					3) Select Cool Savings™ value – Selects the amount  
					of adjustment for the Cool Savings™ feature in Cool  
					mode with 1 (1°) being the least amount of adjustment  
					and 6 (6°) being the most amount of adjustment. Default  
					value is 0 which disables this feature. Selecting a value  
					greater than 0 will display Cool Savings on the screen  
					and enable the key for Cool Savings feature. Cool Sav-  
					ings is an optional energy saving feature that can reduce  
					your cooling costs. It is based on the principal that lower  
					indoor humidity makes a slightly higher temperature  
					feel more comfortable. Cool Savings operates during  
					periods of high demand which normally occur on the  
					hottest summer days when a cooling system may run  
					for hours to reach the thermostat setting. Long cooling  
					run times also lower the indoor humidity. Cool Savings,  
					very slowly, adjusts the setpoint temperature to make the  
					setpoint closer to the displayed room temperature, to a  
					maximum of the number of degrees you select. Adjust-  
					ing the setpoint temperature over a long cooling run time  
					allows the system to reach your set temperature and turn  
					off. The room temperature will actually be higher than  
					the thermostat displays but the reduction in humidity will  
					allow comfort at the slightly higher temperature.  
					10) Select Backlight Display – The display backlight im-  
					proves display contrast in low lighting conditions. When  
					the “C” terminal is powered, selecting backlight CdL ON  
					will keep the light on continuously. Select backlight OFF  
					will turn the light on momentarily after any key is pressed.  
					When the “C” terminal is not powered, the light will be on  
					momentarily after any key is pressed no matter whether  
					the backlight is selected ON or OFF.  
					11) Select Temperature Display Adjustment 4 LO to 4 HI  
					– Allows you to adjust the room temperature display up  
					to 4° higher or lower.Your thermostat was accurately cali-  
					brated at the factory, but you have the option to change  
					the display temperature to match your previous thermo-  
					stat. The current or adjusted room temperature will be  
					displayed.  
					12) Select F° or C° Readout – Changes the display readout  
					to Celsius or Fahrenheit as required.  
					13 & 14) Temperature Limit Range Heat or Cool – This  
					selection sets the maximum HEAT (13) or minimum  
					COOL (14) temperature for the setpoint range. Select the  
					To turn this feature on in the Cool mode press Cool  
					Savings. The display will show “Save” next to the  
					setpoint temperature. When Cool Savings is making ad-  
					justments to the room temperature display “Save” will be  
					flashing and the displayed room temperature may vary  
					within the adjustment range you selected.  
					limit temperature using the  
					or  
					keys. In the Run  
					mode, the setpoint temperature will not adjust past the  
					limit temperature selected. When the limit temperature is  
					reached, trying to raise or lower the setpoint past the limit  
					will cause “L” to be displayed in the times digits for about 6  
					seconds. This feature not available on earlier models.  
					If “Save” is not displayed and this feature is OFF, no  
					change will occur when the cooling system is continu-  
					ously running during periods of high demand.  
					15) Program Options: Configured for 7 day or 5/1/1 day pro-  
					gramming or non-programmable mode. The default set-  
					ting is P7, indicating 7 day programming. The programs  
					4) Energy Management Recovery: Energy Management  
					Recovery (E) On enables the thermostat to start heating  
					or cooling early to make the building temperature reach  
					the program setpoint at the time you specify. Heating will  
					start 5 minutes early for every 1° of temperature required  
					to reach setpoint.  
					per week can be changed to P3 by pressing the  
					or  
					keys. A selection of 0 Days for non-programmable  
					will eliminate the need for EMR, and that step in the  
					menu will be skipped.  
					16 & 17) Select Automatic Schedule – With just one touch  
					of the AUTO SCHEDULE button this feature allows  
					you to program a desired comfort temperature into all  
					the program periods along with a 6° set back for night  
					periods of both Heat and Cool programs. Factory default  
					is “On” for both. When Heat AS On and Cool AS On  
					are activated while in Heat or Cool mode, select desired  
					setpoint temperature and press AUTO SCHEDULE. This  
					value will be copied into all the morning, day and evening  
					program periods. The night program periods will have a  
					6°F set back.  
					Example: E On is selected and your heating is pro-  
					grammed to 65° at night and 70° at 7 AM. If the build-  
					ing temperature is 65°, the difference between 65° and  
					70° is 5°. Allowing 5 minutes per degree, the thermostat  
					setpoint will change to 70° at 6:35 AM. Cooling allows  
					more time per degree, because it takes longer to reach  
					set temperature.  
					5, 6 & 7) Cycle Rate Selection – The factory default setting  
					for Heat and Cool modes, SS1, MS2, is medium cycle  
					(ME). For Heat Pump, HP1, HP2, the default setting is  
					medium (ME). For Emer (Aux) the default setting is fast  
					18 & 19) Select Fast Second Stage ON or OFF – Heat  
					pump or Multi-stage only, in the run mode, with the fast  
					Heat feature enabled (FA Heat On), if the Heat setpoint  
					temperature is manually raised by 3°F (2°C) or more  
					cycle (FA). To change cycle rate, press the  
					key.  
					or  
					Cycle rate differentials for different settings are:  
					Fast  
					FA  
					Medium Slow  
					above the actual temperature using  
					the second  
					MODE  
					ME  
					SL  
					stage will energize immediately. With FA OFF, second  
					stage will not energize until the setpoint temperature is  
					1°F or more above actual temperature for more than ten  
					minutes. The Fast Cool feature (FA Cool) provides the  
					same controls when the setpoint temperature is lowered.  
					Heat (SS1, MS2)  
					Cool (SS1, MS2)  
					Heat Pump (HP1, HP2)  
					Emer (HP1, HP2)  
					0.4°F  
					0.9°F  
					0.9°F  
					0.6°F  
					0.6°F  
					1.2°F  
					1.2°F  
					-
					1.7°F  
					1.7°F  
					1.7°F  
					1.7°F  
					7