White Rodgers 1F87 361 Thermostat User Manual

Home

href="
1F87-361  
Programmable Electronic Digital Thermostat  
   
INSTALLATION   AND  
   
OPERATION   INSTRUCTIONS  
     
Operator:  Save these instructions for future use!  
                    
   
   
      
   
      
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY  
                     
   
   
   
   
   
         
   
   
   
   
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE  
   
      
   
   
   
   
   
   
   
   
PERSONAL INJURY AND/OR PROPERTY DAMAGE.  
            
DESCRIPTION  
 Temperature override until next program period  
 Manual program override (HOLD temperature)  
 Temporary HOLD  
Your new White-Rodgers 7-Day Digital Thermostat uses the  
technology of a solid-state microcomputer to provide precise  
time/temperature control. This thermostat offers you the flexibil-  
ity to design heating and cooling programs that fit your needs.  
 °F/°C convertibility  
Features:  
 Temperature range 45° to 90°F  
 RC, RH, C, W, Y, G , O and B terminals  
 Optional C terminal (Dual Power option)  
 Separate program for each day of the week with four separate  
time/temperature periods per day  
 Simultaneous heat and cool program storage  
 Preprogrammed temperature control  
 Backlit display  
 B and O terminals for single stage heat pumps (no auxiliary  
heat) or damper operation  
 Program storage in case of power loss  
 2 “AA” Energizer® alkaline batteries included  
 LCD  continuously  displays  setpoint,  and  alternately  dis-  
plays time and room temperature  
PRECAUTIONS  
This thermostat is intended for use with a low voltage system; do  
not use this thermostat with a line voltage system. If in doubt  
about whether your wiring is millivolt, line, or low voltage, have  
it inspected by a qualified heating and air conditioning contractor  
or electrician.  
! WARNING  
Do    not    use    on    circuits    exceeding    specified    voltage.  
   
   
      
   
   
   
                     
Higher   voltage   will   damage   control   and   could   cause  
         
shock   or   fire   hazard.  
Do not exceed the specification ratings.  
                           
Do    not    short    out    terminals    on    gas    valve    or    primary  
control   to   test.   Short   or   incorrect   wiring   will   damage  
                        
thermostat    and    could    cause    personal    injury    and/or  
                  
All wiring must conform to local and national electrical codes and  
ordinances.  
This control is a precision instrument, and should be handled  
carefully. Rough handling or distorting components could cause  
the control to malfunction.  
property   damage.  
   
                     
Thermostat   installation   and   all   components   of   the   sys-  
                              
tem   shall   conform   to   Class   II   circuits   per   the   NEC   code.  
! CAUTION  
To   prevent   electrical   shock   and/or   equipment   damage,  
   
   
   
   
   
   
                        
disconnect   electric   power   to   system   at   main   fuse   or  
circuit   breaker   box   until   installation   is   complete.  
                  
SPECIFICATIONS  
ELECTRICAL   DATA  
   
APPLICATIONS  
For use with:  
   
Electrical   Rating:  
8 to 30 VAC 50/60 Hz. or D.C.  
0.05 to 1.0 Amps (Load per terminal)  
1.5   Amps   Maximum   Total   Load (All terminals combined)  
 Standard heat/cool or heat only systems  
 Electric heat systems  
 Gas or oil fired systems  
            
 Gas systems with intermittent ignition devices (I.I.D.)  
and/or vent dampers  
 Hydronic (hot water or steam) systems  
 Single-stage heat pump systems (no auxiliary heat)  
 Millivolt systems  
THERMAL   DATA  
   
      
Setpoint   Temperature   Range:  
45°F to 90°F (7°C to 32°C)  
Operating   Ambient   Temperature   Range:  
   
   
   
32°F to 105°F  
Operating   Humidity   Range:  
      
         
DO   NOT   USE   WITH:  
 Multi-stage systems  
 Systems exceeding 30 VAC and 1.5 amps  
 3-wire zoned hydronic heating systems  
0 to 90% RH (non-condensing)  
Shipping   Temperature   Range:  
   
   
-4°F to 149°F  
      
PART   NO.   37-6763A  
0614  
href="
INSTALLATION  
   
REMOVE OLD THERMOSTAT  
      
   
Screw anchors  
1. Shut off electricity at the main fuse box until installation is  
complete. Ensure that electrical power is disconnected.  
2. Remove the front cover of the old thermostat. With   wires  
      
still   attached,   remove wall plate from the wall. If the old  
thermostat has a wall mounting plate, remove the thermo-  
stat and the wall mounting plate as an assembly.  
3. Identify   each   wire   attached   to   the   old   thermostat   using  
                  
the   labels   enclosed   with   the   new   thermostat.  
4. Disconnect the wires from old thermostat one at a time. DO  
NOT   LET   WIRES   FALL   BACK   INTO   THE   WALL.  
                     
5. Install new thermostat using the following procedures.  
Mounting  
holes  
ATTENTION!  
Mounting  
holes  
This product does not contain mercury. However, this product  
may replace a unit which contains mercury.  
Electric/Gas  
switch  
Do not open mercury cells. If a cell becomes damaged, do not  
touch any spilled mercury. Wearing nonabsorbent gloves, take  
up the spilled mercury with sand or other absorbent material and  
place into a container which can be sealed. If a cell becomes  
damaged, the unit should be discarded.  
         
Figure   1.   Thermostat   Base  
6. Push excess wire into wall and plug hole with a fire-resistant  
material  (such  as  fiberglass  insulation)  to  prevent  drafts  
from affecting thermostat operation.  
Mercury must not be discarded in household trash. When the  
unit  this  product  is  replacing  is  to  be  discarded,  place  in  a  
suitable container and return to White-Rodgers at 2895 Harrison  
Street, Batesville, AR 72501 for proper disposal.  
   
BATTERY LOCATION  
   
   
ELECTRIC HEAT OR SINGLE-STAGE  
         
   
   
2 "AA" alkaline batteries are included in the thermostat at the  
factory with a battery tag to prevent power drainage. You   must  
remove   the   battery   tag   to   engage   the   batteries.  
                     
   
HEAT PUMP SYSTEMS  
      
   
This thermostat is configured from the factory to operate a heat/  
cool, fossil fuel (gas, oil, etc.), forced air system. It is configured  
correctly for any system that DOES NOT require the thermostat  
to energize the fan on a call for heat. If your system is an electric  
heat or heat-pump system that REQUIRES the thermostat to  
turn on the fan on a call for heat, locate the ELECTRIC/GAS  
If  “BATT” is displayed, the batteries are low and should be  
replaced  with  fresh  "AA"  Energizer®  alkaline  batteries.  To  
replace batteries, install the batteries along the top of the base  
(see Fig. 1). The batteries must be installed with the positive (+)  
end to the left.  
switch   on the back of the thermostat (see fig. 1) and switch it to  
   
   
HYDRONIC (HOT WATER OR STEAM)  
            
   
   
   
the  ELECTRIC    position.  This  will  allow  the  thermostat  to  
energize the fan immediately on a call for heat. If you are unsure  
if the heating/cooling system requires the thermostat to control  
the fan, contact a qualified heating and air conditioning service  
person.  
   
HEATING SYSTEMS  
   
This  thermostat  is  set  to  operate  properly  with  a  forced-air  
heating  system.  If  you  have  a  hydronic  heating  system  (a  
system that heats with hot water or steam), you must set the  
thermostat to operate properly with your system. Change the  
second option in the configuration menu to SL (see CONFIGU-  
   
ATTACH THERMOSTAT BASE TO WALL  
            
   
      
1. Remove the packing material from the thermostat. Gently RATION MENU, page 4).  
pull the cover straight off the base. Forcing or prying on the  
thermostat will cause damage to the unit. If necessary, move  
the electric heat switch (see ELECTRIC   HEAT   SYSTEMS,  
above).  
   
CHECK THERMOSTAT OPERATION  
      
   
If  at  any  time  during  testing  your  system  does  not  operate  
properly, contact a qualified service person.  
2. Connect  wires  beneath  terminal  screws  on  base  using  
appropriate wiring schematic (see figs. 2 through 7).  
Turn on power to the system.  
3. Place  base  over  hole  in  wall  and  mark  mounting  hole  
locations on wall using base as a template.  
   
Fan Operation  
   
4. Move base out of the way. Drill mounting holes.  
If your system does   not have a G terminal connection, skip to  
Heating   System.  
   
5. Fasten base loosely to wall, as shown in fig. 1, using two  
mounting  screws.  Place  a  level  against  bottom  of  base,  
adjust until level, and then tighten screws. (Leveling is for  
appearance only and will not affect thermostat operation.) If  
you are using existing mounting holes, or if holes drilled are  
too large and do not allow you to tighten base snugly, use  
plastic screw anchors to secure subbase.  
1. Move FAN switch to ON position. The blower should begin  
to operate.  
2. Move FAN switch to AUTO   position. The blower should  
stop immediately.  
2
href="
JUMPER  
WIRE  
THERMOSTAT  
SYSTEM  
Hot  
Y
C
B
O
G
W
RC  
RH  
THERMOSTAT  
SYSTEM  
C
Y
B
O
G
W
RC  
RH  
Cooling  
System Relay System  
Fan  
Heating  
24 VAC  
120 VAC  
Neutral  
Fan  
Relay  
Heating  
System  
Hot  
HEATING  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
NOTE  
For 2-wire Heat only,  
attach to RH and W  
Hot  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
Figure 2. Typical wiring diagram for  
heat only, 3-wire, single transformer systems  
COOLING TRANSFORMER  
Figure 5. Typical wiring diagram for  
heat/cool, 5-wire, two-transformer systems  
JUMPER  
WIRE  
THERMOSTAT  
C
B
O
Y
G
W
RC  
RH  
SYSTEM  
JUMPER  
WIRE  
JUMPER  
WIRE  
THERMOSTAT  
SYSTEM  
Cooling  
System Relay  
Fan  
Y
C
B
O
G
W
RC RH  
Hot  
24 VAC  
120 VAC  
Neutral  
Reversing Compressor Fan  
Valve*  
Contactor Relay  
Hot  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
Figure 3. Typical wiring diagram for  
cool only, 3-wire, single transformer systems  
* Reversing valve is energized when the  
system switch is in the COOL position  
TRANSFORMER  
Figure 6. Typical wiring diagram for heat pump  
with reversing valve energized in COOL  
NOTE  
RED jumper wire (provided with thermostat) must be  
connected between thermostat RH and RC terminals  
for proper thermostat operation with this system.  
JUMPER  
WIRE  
JUMPER  
WIRE  
JUMPER  
WIRE  
THERMOSTAT  
SYSTEM  
Y
C
B
O
G
W
RC RH  
THERMOSTAT  
SYSTEM  
C
B
O
Y
G
W
RC RH  
Cooling  
System Relay  
Fan  
Heating  
System  
Reversing Compressor Fan  
Valve*  
Contactor Relay  
Hot  
Hot  
24 VAC  
120 VAC  
Neutral  
24 VAC  
120 VAC  
Neutral  
* Reversing valve is energized when the  
system switch is in the HEAT position  
TRANSFORMER  
TRANSFORMER  
Figure 7. Typical wiring diagram for heat pump  
with reversing valve energized in HEAT  
Figure 4. Typical wiring diagram for  
heat/cool, 4-wire, single transformer systems  
The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year  
with fresh "AA" Energizer® alkaline batteries.  
   
Cooling System  
   
   
Heating System  
   
! CAUTION  
To   prevent   compressor   and/or   property   damage,   if   the  
   
   
   
   
   
      
1. Move SYSTEM switch to HEAT position. If the heating  
system has a standing pilot, be sure to light it.  
                     
outdoor   temperature   is   below   50°F,   DO   NOT   operate  
      
the   cooling   system.  
2. Press  
 to adjust thermostat setting above room tempera-  
ture. The heating system should begin to operate.  
1. Move SYSTEM switch to COOL position.  
2. Press   to adjust thermostat setting below room tempera-  
3. Press  
 to adjust thermostat setting below room tempera-  
ture. The heating system should stop operating.  
ture.  The  blower  should  come  on  immediately  on  high  
speed, followed by cold air circulation  
3. Press  
 to adjust thermostat setting above room tempera-  
ture. The cooling system should stop operating.  
3
href="
OPERATION  
Before you begin programming your thermostat, you should be  
familiar with its features and with the display and the location  
and operation of the thermostat buttons. Your thermostat con-  
sists  of  two  parts:  the  thermostat    cover  and  the  base.  To  
remove the cover, pull it straight out from the base. To replace  
the cover, line up the cover with the base and press until the  
cover snaps onto the base.  
   
The Thermostat Buttons and Switches  
            
   
   
   
1
 Raises temperature setting.  
Lowers temperature setting.  
TIME button.  
2
3
4
5
6
7
PRGM (program) button.  
RUN (run program) button.  
HOLD temperature button.  
FAN switch (ON, AUTO).  
SYSTEM switch (COOL, OFF, HEAT).  
8
   
The Display  
   
Press HOLD to change to the next menu item or press TIME to  
go backwards to the previous item in the menu. To exit the menu  
and return to the program operation, press RUN. If no keys are  
pressed  within  fifteen  minutes,  the  thermostat  will  revert  to  
normal operation.  
9
Indicates day of the week.  
Flame   icon ( ) is displayed when the SYSTEM switch is in  
   
10  
the HEAT position. Snowflake   icon ( )is displayed (non-  
flashing) when the SYSTEM switch is in the COOL position.  
Snowflake is displayed (flashing) if the thermostat is in  
lockout mode to prevent the compressor from cycling too  
quickly.  
1) Select   Temporary   Hold   Time   - The thermostat can hold  
any temperature you set it to for the amount of time you  
select on this option. Your choices are 0:00 to 8:00 hours in  
15 minute increments. 0:00 disables the function  
11  
Displays “BATT” when the 2 "AA" batteries are low and  
should be replaced. Only “BATT” and “LO” in the minutes  
field are displayed when batteries are low with no system  
power.  
Example:  
1. You have selected 3:00 hours for the Temporary Hold  
time period.  
Alternately  displays  current  time  and  temperature.  Dis-  
plays “LO” in the minutes field when batteries are low.  
12  
13  
2. With the thermostat set to Heat or Cool, press HOLD for  
      
approximately    five    seconds  until  HOLD  time  (3:00  
indicating 3 hours) appears as a setting reminder.  
The word “HOLD” is displayed when the thermostat is in  
the HOLD mode. “HOLD” is displayed flashing when the  
thermostat is in a temporary HOLD Mode.  
3. After releasing the button, “HOLD” on the display will  
blink.  
14  
15  
Displays  currently  programmed  set  temperature  (this  is  
blank when SYSTEM switch is in the OFF position).  
4. Use  
 or  
  to set the temperature to your prefer-  
ence.  The  thermostat  will  maintain  this  temperature  
setting for 3 hours with “HOLD” blinking to remind you it  
is in Temporary Hold. After 3 hours the thermostat will go  
back to the program temperature and “HOLD” will no  
longer blink or display.  
Displays  “FLTR”  when  the  system  has  run  for  the  pro-  
grammed filter time period as a reminder to change or clean  
your air filter.  
   
CONFIGURATION MENU  
   
2) Select      FA   or   SL   (Fast   or   Slow)   Heating   Cycle   Rate - The  
FA setting is frequently used for gas, oil or electric heat. The  
SL setting produces a longer heating cycle which is nor-  
mally  for  hot  water  or  steam  (hydronic)  systems.  Both  
settings  produce  very  accurate  temperature  control  and  
can  be  set  to  your  personal  preference.  FA  cycles  the  
system just under 1°F and the SL setting cycles at approxi-  
mately 1.5°F.  
The configuration menu allows you to set certain thermostat  
operating characteristics to your system or personal require-  
ments.  
Press RUN to make sure the thermostat is in the run program  
mode, then press PRGM and RUN at the same time to enter the  
configuration menu. The display will show the first item in the  
configuration menu.  
The  configuration  menu  table  summarizes  the  configuration  
options. An explanation of each option follows.  
3) Select    backlit    display - The display backlight improves  
display contrast in low lighting conditions. Selecting back-  
light ON will keep the light on for a short period of time after  
any key is pressed. Selecting OFF will keep the light off.  
4
href="
Configuration Menu  
Step  
Press Button(s)  
Displayed (Factory Default) Press  
or  
to select:  
COMMENTS  
Select temporary Hold time  
1
HOLD  
(0:00)  
0 to 8 hrs (in  
PRGM  
and RUN  
15 minute increments)  
Select FA or SL (Fast or Slow) heating cycle rate  
SL  
2
3
4
5
6
HOLD  
*
(FA)  
d-L  
(ON)  
OFF  
OFF  
Select display backlight OFF or ON  
HOLD  
HOLD  
*
*
E
(ON)  
Select Energy Management Recovery OFF or ON  
Filter  
(000)  
0 to 1950 hours  
(in 50 hour increments)  
HOLD  
HOLD  
HOLD  
*
*
*
Select filter replacement run time  
LOC  
(OFF)  
ON  
Select compressor lockout OFF or ON  
Select temperature display adjustment higher or lower  
0 HI  
(0)  
4 LO to  
4 HI  
7
8
9
Select temperature display to F or C  
Returns to normal operation  
(F)  
C
HOLD  
RUN  
*
* Press HOLD to advance to next item or TIME to move backwards to previous item  
5) Select Energy Management Recovery OFF or ON –  
   
OPERATING FEATURES  
   
Energy Management Recovery (EMR) causes the thermo-  
Now  that  you  are  familiar  with  the  thermostat  buttons  and  
display, read the following information to learn about the many  
features of the thermostat.  
stat to start heating or cooling early to make the building  
temperature reach the program setpoint at the time you  
specify. Heating will start 5 minutes early for every 1° of  
temperature required to reach setpoint. Cooling allows more  
time per degree because it takes longer to reach tempera-  
ture.  
      
 SIMULTANEOUS    HEATING/COOLING    PROGRAM  
STORAGE    When programming, you can enter both  
   
your heating and cooling programs at the same time. There  
is no need to reprogram the thermostat at the beginning of  
each season.  
Example: You select EMR and have your heating pro-  
grammed to 65° at night and 70° at 7 AM. If the building  
temperature is 65° the difference between 65° and 70° is 5°.  
Allowing 5 minutes per degree the thermostat setpoint will  
change to 70° at 6:35 AM.  
 TEMPERATURE   OVERRIDE — Press  
 or  
 until  
the display shows the temperature you want. The thermo-  
stat will override current programming and keep the room  
temperature  at  the  selected  temperature  until  the  next  
program period begins. Then the thermostat will automati-  
cally revert to the program.  
4) Select   filter   replacement   run   time - The thermostat will  
display  “FLTR”    after  a  set  time  of  operation.  This  is  a  
reminder to change or clean your air filter. This time can be  
set from 0 to 1950 hours in 50 hour increments. A   selection  
 HOLD   TEMPERATURE — The thermostat can hold any  
temperature within its range for an indefinite period without  
reverting  to  the  programmed  temperature.  Momentarily  
press HOLD button. HOLD” will be displayed. Then choose  
               
of   000   will   cancel   this   feature. When “FLTR” is displayed,  
you can clear it by pressing HOLD and RUN at the same  
time. This resets the timer and starts counting the hours  
until the next filter change. Changing the time in the menu  
also resets the timer.  
the  desired  temperature  by  pressing  
  or  
.  The  
thermostat will hold the room temperature at the selected  
setting until you press RUN button to start program opera-  
tion again.  
5) Select   Compressor   Lockout   LOC   OFF   or   ON - Selecting  
LOC ON will cause the thermostat to wait 5 minutes before  
turning on the compressor if the heating and cooling sys-  
tem  loses  power.  It  will  also  wait  5  minutes  minimum  
between cooling cycles. This is intended to help protect the  
compressor from short cycling. Some newer compressors  
already have a time delay built in and do not require this  
feature. Your compressor manufacturer can tell you if the  
feature  is  already  present  in  their  system.    When  the  
compressor time delay occurs it will flash the (snowflake  
icon) for about five minutes then turn on the compressor.  
 CONFIGURATION    MENU   Allows  you  to  customize  
certain thermostat options.  
   
PROGRAMMING YOUR THERMOSTAT  
      
   
This section will help you plan your thermostat’s program to  
meet your needs. For maximum comfort and efficiency, keep  
the following guidelines in mind when planning your program.  
 When  heating  (cooling)  your  building,  program  the  
temperatures to be cooler (warmer) when the building is  
vacant or during periods of low activity.  
6) Select   Temperature   Display   Adjustment   4   LO   to   4   HI -  
Allows you to adjust the room temperature display 4° higher  
or lower. Your thermostat was accurately calibrated at the  
factory  but  you  have  the  option  to  change  the  display  
temperature to match your previous thermostat.  
 During  early  morning  hours,  the  need  for  cooling  is  
usually minimal.  
7) Select   F°   or   C°   Readout - Changes the display readout to  
Centigrade or Fahrenheit as required.  
5
href="
   
Planning Your Program  
      
   
2. Press and hold either  
 or  
 until you reach the correct  
hour and AM/PM designation (AM begins at midnight; PM  
begins at noon).  
Look at the factory preprogrammed times and temperatures  
shown in the sample schedule. If this program will suit your  
needs, simply press the RUN button to begin running the factory  
preset program.  
3. Press TIME once. The display window will show the minutes  
only.  
If you want to change the preprogrammed times and tempera-  
tures, follow these steps.  
EXAMPLE:  
Determine  the  time  periods  and  temperatures  for  your  daily  
programs. You must program four periods for both the weekday  
and  weekend  program.  However,  you  may  use  the  same  
heating and cooling temperatures for consecutive time periods.  
You can choose start times, heating temperatures, and cooling  
temperatures  independently  for  each  day  programs  (for  ex-  
ample, you may select 5:00 AM and 7 as the Monday 1st  
4. Press and hold either  
minutes.  
 or  
 until you reach the correct  
5. Press TIME once. The display will show the day of the week.  
6. Press   or   until you reach the current day of the week.  
7. Press  RUN once. The display will show the correct time and  
room temperature alternately.  
period   heating start time and temperature, and also choose  
   
7:00 AM and 76° as the Monday 1st   period   cooling start time  
and temperature).  
Enter Heating Program  
Use the following table to plan your program time periods and  
the  temperatures  you  want  during  each  period.  Fill  in  the  
complete table to have a record of your programs.  
1. Move the SYSTEM switch to HEAT.  
2. Press PRGM once. “MO” (indicating Monday program) will  
appear in the display. Also displayed are the currently  
programmed start time for the 1st heating period and the  
currently programmed temperature (flashing).  
   
Entering Your Program  
      
   
MO  
Follow these steps to enter the heating and cooling programs  
you have selected.  
AM  
EXAMPLE:  
            
Set   Current   Time   and   Day  
This display window shows that for Monday's 1st heating  
period, the start time is 6:00 AM, and 70° is the programmed  
temperature(thisexamplereflectsfactorypreprogramming).  
1. Press TIME button once. The display will show the hour only.  
3. Press  
or  
to change the displayed temperature to  
PM  
EXAMPLE:  
your selected temperature for Monday's 1st heating pro-  
gram period.  
4. Press TIME once (the programmed time will flash). Press  
SAMPLE  
or  
until your selected start time for Monday's 1st  
Heating/Cooling Schedule Plan (Factory Program)  
heating program period appears. The time will change in 15  
minute increments. When your selected time is displayed,  
pressTIMEagaintoreturntothechangetemperaturemode.  
ALL DAYS OF THE WEEK  
Start Time  
6:00 AM  
8:00 AM  
5:00 PM  
10:00 PM  
6:00 AM  
8:00 AM  
5:00 PM  
10:00 PM  
Temperature  
70 F  
Period  
1ST  
5. Press PRGM once. The currently programmed start time  
and setpoint temperature for the Monday's 2nd heating  
program period will appear.  
2ND  
3RD  
4TH  
1ST  
2ND  
3RD  
4TH  
62 F  
70 F  
6. Repeat steps 3 and 4 to select the start time and heating  
temperature for Monday's 2nd heating program period.  
62 F  
78 F  
7. Repeat steps 3 through 5 for the 3rd and 4th heating  
program periods. Monday heating programs are now  
complete.  
85 F  
78 F  
82 F  
Heating/Cooling Schedule Plan  
PERIOD 2  
PERIOD 1  
PERIOD 3  
PERIOD 4  
HEAT  
Time Temp  
COOL  
Time Temp  
HEAT  
Time Temp  
COOL  
Time Temp  
HEAT  
Time Temp  
COOL  
Time Temp  
HEAT  
Time Temp  
COOL  
Time Temp  
Mon  
Tues  
Wed  
Thur  
Fri  
Sat  
Sun  
6
href="
NOTE  
1. Move SYSTEM switch to COOL position.  
If you are programming your thermostat for the first time and you 2. Follow the procedure for entering your cooling program,  
want programming for all days of the week to be the same as  
Monday's program, press RUN or HOLD at this point, and  
proceed to Enter Cooling Program. (This simplified COPY  
DAY feature only works the first time you program your thermo-  
stat. If you want to copy one day's programming to a specific day  
programming, refer to COPY DAY FUNCTION in OPERATING  
FEATURES. If you are changing your thermostat's program-  
ming, you must program each day separately.)  
using your selected cooling times and temperatures.  
CHECK YOUR PROGRAMMING  
Follow these steps to check your thermostat programming one  
final time before beginning thermostat operation.  
1. Move SYSTEM switch to HEAT position.  
2. PressPRGMtoviewthe1stMondayheatingperiodtimeand  
temperature. Each time you press PRGM, the next heating  
period time and temperature will be displayed in sequence  
for Monday. Press HOLD to display Tuesday's 1st heating  
period, and press PRGM to view each of the remaining  
Tuesday's heating period time and temperatures. To view  
eachday'sheatingprogram, pressHOLDtochangedayand  
them press PRGM to look at each programming period for  
the day. (You may change any time or temperature during  
this procedure.)  
8. Press HOLD once. “TU” (indicating Tuesday program) will  
appear in the display, along with the start time for the 1st  
heating period and the currently programmed temperature.  
9. Repeat steps 3 through 7 to complete Tuesday's heating  
programming.  
10.Continue entering each day's programming until all heating  
periods time and temperatures have been entered.  
11.When you have completed entering your heating program,  
press RUN.  
3. Press RUN.  
4. Move SYSTEM switch to COOL position.  
5. Repeat step 2 to check cooling program.  
Enter Cooling Program  
6. Move SYSTEM switch to HEAT or COOL and press RUN to  
! CAUTION  
begin program operation.  
YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND  
READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!  
If the outside temperature is below 50°F, disconnect  
power to the cooling system before programming.  
Energizing the air conditioner compressor during  
cold weather may cause personal injury or property  
damage.  
TROUBLESHOOTING  
   
Reset   Operation  
program. If the thermostat has power, has been reset and still  
If a voltage spike or static discharge blanks out the display or does not function correctly contact your heating/cooling ser-  
causes erratic thermostat operation you can reset the thermo- vice person or place of purchase.  
stat by pressing  
,  
 and TIME at the same time. This also  
Batteries  
resets  the  factory  defaults  to  the  configuration  menu  and For optimum performance, we recommend replacing batteries  
once a year with fresh "AA" Energizer® alkaline batteries.  
Symptom  
Possible   Cause  
Corrective   Action  
No   Heat/No   Cool/No   Fan  
(common   problems)  
   
   
1. Blown fuse or tripped circuit breaker.  
2. Furnace power switch to OFF.  
Replace fuse or reset breaker.  
Turn switch to ON.  
3. Furnace blower compartment door or  
panel loose or not properly installed.  
Replace door panel in proper position to engage  
safety interlock or door switch.  
   
No   Heat  
1. Pilot light not lit.  
Re-light pilot.  
2. SYSTEM Switch not set to HEAT.  
Set SYSTEM Switch to Heat   and raise setpoint  
above room temperature.  
3. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely  
attached.  
4. Furnace Lock-Out Condition. Heat may also  
be intermittent.  
Many furnaces have safety devices that shut the  
system down when a lock-out condition occurs.  
If the heat works intermittently contact the furnace  
manufacturer or local service person for assistance.  
Diagnostic: Set SYSTEM Switch to HEAT and  
raise the setpoint above room temperature. Within  
a few seconds the thermostat should make a soft  
click sound. This sound usually indicates the  
thermostat is operating properly. If the thermostat  
does not click, try the reset operation listed above.  
If the thermostat does not click after being reset  
contact your heating and cooling service person or  
place of purchase for a replacement. If the  
thermostat clicks, contact the furnace manufacturer  
or a service person to verify the heating system is  
operating correctly.  
5. Heating System requires service or  
thermostat requires replacement.  
7
                                                                                             
                                                                                             
                                                                                              
                                                                                              
                                                                                                 
                                                                                                 
                                                                                                    
                                                                                                    
                                                                                                      
                                                                                                      
                                                                                                        
                                                                                                        
                                                                                                          
                                                                                                          
                                                                                                                                                         
                                                                                                                                                         
                                                                                                                                                            
                                                                                                                                                            
                                                                                                                                                              
                                                                                                                                                              
                                                                                                                                                               
                                                                                                                                                               
                                                                                                                                                                 
                                                                                                                                                                 
                                                                                                                                                                   
                                                                                                                                                                   
                                                                                                                                                                     
                                                                                                                                                                     
                                                                                                                                                                      
                                                                                                                                                                      
                                                                                                                                                                       
                                                                                                                                                                       
                                                                                                                                                                         
                                                                                                                                                                         
                                                                                                                                                                            
                                                                                                                                                                            
                                                                                                                                                                               
                                                                                                                                                                               
                                                                                                                                                                                 
                                                                                                                                                                                 
                                                                                                                                                                                  
                                                                                                                                                                                  
                                                                                                                                                                                   
                                                                                                                                                                                   
                                                                                                                                                                                     
                                                                                                                                                                                     
href="
TROUBLESHOOTING  
Symptom  
Possib  
l
e
    
   
C
a
u
s
e
C
o
r
r
e
c
t
iv  
e
    
   
A
c
t
i
o
n
   
No   Cool  
1. SYSTEM Switch not set to COOL  
Set SYSTEM Switch to COOL and lower setpoint  
below room temperature.  
2. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely  
attached.  
3. Cooling System requires service or thermostat  
requires replacement.  
Same procedure as diagnostic for No Heat  
condition except set the thermostat to COOL and  
lower the setpoint below the room temperature.  
There may be up to a five minute delay before  
the thermostat clicks in Cooling if the compressor  
lock-out option is selected in the configuration  
menu (Item 6).  
               
Heat,   Cool   or   Fan   Runs   Constantly.  
1. FAN Switch set to Fan ON.  
2. Possible short in wiring.  
3. Possible short in thermostat.  
4. Possible short in Heat/Cool/Fan system.  
Check each wire connection to verify they are  
not shorted or touching together. No bare wire  
should stick out from under terminal screws.  
Try resetting the thermostat. If the condition  
persists the manufacturer of your system or  
service person can instruct you on how to test the  
Heat/Cool system for correct operation. If the  
system operates correctly, replace the thermostat.  
                  
Furnace   Cycles   Too   Fast   or   Too   Slow 1. The location of the thermostat and/or the size  
Item 2 in the Configuration Menu is the adjustment  
that controls the cycle rate. If an acceptable cycle  
rate is not achieved using the FA  (Fast) or SL  
(Slow) adjustment contact a local service person  
for additional suggestions.  
            
(narrow   or   wide   temperature   swing)  
of the Heating System may be influencing the  
cycle rate.  
                  
Cooling   Cycles   Too   Fast   or   Too   Slow 1. The location of the thermostat and/or the size  
The cycle rate for cooling is fixed and can not be  
adjusted. Contact a local service person for  
suggestions.  
            
(narrow   or   wide   temperature   swing)  
of the Cooling System may be influencing the  
cycle rate.  
         
Thermostat   Setting   and   Thermometer 1. Thermostat thermometer setting requires  
The thermometer can be adjusted +/- 4 degrees as  
listed in item 7 of the Configuration Menu. No other  
adjustment is possible.  
Disagree  
 adjustment.  
            
Clock   Loses   or   Gains   Time  
1. Loss of power to thermostat and low batteries.  
The thermostat will maintain its program in memory  
even with no power/no batteries but the clock time  
will be incorrect when power is restored. See No  
Heat/No Cool/No Fan (common problems) above  
for items to check in the system.  
            
Heat   or   Cool   Starts   Early  
1. EMR activated  
See Configuration Menu (Item 4).  
            
Thermostat   Does   Not   Follow   Program 1. AM or PM set incorrectly in program.  
Check current clock and program settings including  
the AM or PM designations for each time period.  
If a voltage spike or static discharge occurs use the  
Reset Operation listed above.  
2. AM or PM set incorrectly on the clock.  
3. Voltage spike or static discharge.  
Blank   Display   and/or   Keypad   Not  
Responding  
   
   
   
   
1. Loss of power and dead batteries.  
2. Voltage Spike or Static Discharge.  
Replace batteries and check heat/cool system for  
proper operation. If a voltage spike or static discharge  
occurs use the Reset Operation listed above.  
   
HOMEOWNER HELP LINE:  1-800-284-2925  
           
   
     
White-Rodgers is a division  
of Emerson Electric Co.  
The Emerson logo is a  
trademark and a service mark  
of Emerson Electric Co.  

Honeywell RTH7500D1007 Thermostat User Manual

Aprilaire 8336 Thermostat User Manual

White Rodgers 50A65 843 Thermostat User Manual

Aube TH116 F Thermostat User Manual

Honeywell TH3210D Thermostat User Manual

White Rodgers 2B61 Thermostat User Manual

Honeywell T8611M Thermostat User Manual

Aube TH102D Thermostat User Manual

White Rodgers 903990 Thermostat User Manual

Lennox 51M32 Thermostat User Manual