PRINCIPLE OF OPERATION
Warp Switch
Contacts
2061 Two-Wire
Damper Motor
This schematic shows the damper motor in the closed
position. As the thermostat calls for heat, the damper (Normally Closed)
To auxiliary circuit
for operating oil
2
2
motor is energized as a circuit is made through side “A” of
burner or gas valve
motor switch. (At the same, time a circuit is made through
110-280 or
3
120-280
the warp switch heater.) The damper motor begins to
Thermostat
NOTE: If same
Contact
“C”
4
transformer powers both
the auxiliary circuit and the
damper motor, connect
the auxiliary circuit to
terminals 1 and 3 instead
of 2 and 3.
open.
Before the damper motor reaches the full open position,
side “B” of motor switch closes (providing a low voltage
auxiliary circuit for starting oil burner or opening gas
valve), side “A” of motor switch makes with contact “C”,
and the warp switch heater opens the warp switch con-
tacts. The warp switch heater remains energized and
keeps the warp switch contacts open as long as the
thermostat calls for heat.
Side “A” of
Motor Switch
Line
1
Side “B” of
Motor Switch
Transformer
Warp Switch
Heater
Motor
INTERNAL WIRING
EXTERNAL WIRING
The system is so wired so that if any one zone still calls for
heat, the burner stays on. When all thermostats are
satisfied, all dampers will have closed, and the circuit
broken to the gas valve or oil burner control.
When the thermostat is satisfied, the circuit through the
warp switch is broken. After this heater cools for a short
time, the warp switch contacts close, energizing the
damper motor through side “A” of motor switch. Just after
the damper motor begins closing, side “B” of motor switch
opens (breaking the auxiliary circuit), while side “A” of
motor switch makes with contact 4 just before the damper
motor fully closes.
The blower in the furnace operates as in any conven-
tional, unzonedhotairsystem. Whentheairintheplenum
is warmed to a set temperature, the fan control turns the
blower on. When the air temperature drops, the fan
controlturnsthebloweroff. Theadditionofzoninghasnot
affected normal fan operation.
The damper motor draws no current while in the closed
position.
INSTALLATION
Outlet Zone 1
Outlet
DUCT LAYOUT
This illustration shows a typical layout for a zoned warm
air system using Zone-Air Controls.
Zone 2
BypassDamper
Parts Group
133-0010
Supply Duct
Bypass Duct
Zone 1
Zone 2
NOTE
DAMPER
MOTORS
The use of a bypass damper is recommended. See
page 6 for details.
Outlet
Zone 4
Zone 3
Outlet
Zone 3
Zone 4
INSTALLING DAMPER MOTOR
The following instructions apply for 6, 8, and 10” ducts.
(For round ducts and rectangular ducts under 6” a special
bracket is available which replaces the access-mounting
plate.)
Duct Layout For
4 Zone Warm Air System
Return Duct
1. Select a convenient position for damper motor instal-
lation on duct work to each zone. Carefully locate and
mark center line on each side of duct.
Bearing
Plate
#10 Sheet
Metal Screws
2. Marklocationfor1⁄
to attach bearing plate by measuring 15⁄16” from center
of 1⁄
” hole. Drill all three holes and attach bearing plate
2
”hole.Alsomarklocationsforholes
2
with two #10 sheet metal screws provided.
3. Locate point “X” on center line exactly opposite 1⁄
15
Point “X”
(locate exactly
opposite 1⁄
” hole)
⁄16”
1
⁄2” Dia. Hole
2
”
2
hole.
Centerlines
of Duct
2