Honeywell T8602C Thermostat User Manual

Home

href="
®
T8602C Chronotherm IV  
Deluxe Programmable  
Thermostats  
INSTALLATION INSTRUCTIONS  
APPLICATION  
The T8602 Chronotherm ® IV Deluxe Programmable Thermostat provides electronic control of 24 Vac single-stage  
heating and cooling systems or 750 mV heating system. Refer to Table 1 for a general description of the thermostat. All  
T8602 thermostats are powered by batteries.  
Table 1. Description of T8602 Thermostats.  
Fan  
T8602  
System  
Changeover  
System Selection  
Selection  
Comments  
C
Heat-Cool  
Manual  
Heat-Off-Cool  
On-Auto  
System and fan selections are made on  
keyboard.  
Location  
Install the thermostat about 5 ft (1.5m) above the floor in  
an area with good air circulation at average temperature.  
See Fig. 1.  
MERCURY NOTICE  
If this control is replacing a control that contains  
mercury in a sealed tube, do not place your old  
control in the trash. Dispose of properly.  
Do not install the thermostat where it can be affected by:  
drafts, or dead spots behind doors and in corners.  
hot or cold air from ducts.  
Contact your local waste management authority  
for instructions regarding recycling and the  
proper disposal of the old control.  
radiant heat from sun or appliances.  
concealed pipes and chimneys.  
unheated (uncooled) areas such as an outside wall  
behind the thermostat.  
INSTALLATION  
Wallplate Installation  
When Installing this Product...  
The thermostat can be mounted horizontally on the wall  
or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.  
Position wallplate horizontally on the wall or on a  
2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.  
1.  
Read these instructions carefully. Failure to follow  
the instructions can damage the product or cause  
a hazardous condition.  
2
.
Check the ratings given in the instructions and on  
the product to make sure the product is suitable for  
your application.  
3.  
.
Installer must be a trained, experienced service  
technician.  
4
After completing installation, use these instructions  
to check out the product operation.  
®
U.S. Registered Trademark  
Copyright © 2003 Honeywell •  
• All Rights Reserved  
6
9-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
NO  
YES  
NO  
5
FEET  
NO  
[
1.5 METERS]  
M10106  
Fig. 1. Typical location of thermostat.  
1
.
Position and level the wallplate (for appearance  
only). The thermostat functions correctly even  
when not level.  
WIRING  
All wiring must comply with local electrical codes and  
ordinances. Refer to Fig. 3 and 6 for typical hookup. A  
letter code is located near each terminal for identification.  
2
.
.
Use a pencil to mark the mounting holes.  
See Fig. 2.  
3
Remove the wallplate from the wall and drill two  
3
/16 inch (76 mm) holes in the wall (if drywall) as  
marked. For firmer material such as plaster, drill  
two 7/32 inch (5.56 mm) holes. Gently tap anchors  
CAUTION  
(
provided) into drilled holes until flush with wall.  
Electrical Hazard.  
4.  
Position the wallplate over the holes, pulling wires  
through the wiring opening.  
Can cause electric shock or equipment  
damage.  
5
.
.
Loosely insert the mounting screws into the holes.  
Tighten mounting screws.  
Disconnect power before wiring.  
6
1.  
Loosen the terminal screws on the wallplate and  
connect the system wires. See Fig. 7.  
WALL  
IMPORTANT  
WIRES  
THROUGH WALL  
Use 18 gauge, color-coded thermostat cable for  
proper wiring.  
2. Securely tighten each terminal screw.  
3. Push excess wire back into the hole.  
4. Plug the hole with nonflammable insulation to  
prevent drafts from affecting the thermostat.  
WALL  
ANCHORS (2)  
THERMOSTAT  
G
W
R
MOUNTING  
HOLES  
MOUNTING  
SCREWS  
HEAT  
RELAY  
M15044  
FAN  
1
RELAY  
L1  
Fig. 2. Mounting the wallplate.  
(HOT)  
L2  
TRANSFORMER  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
M10409  
Fig. 3. Typical hookup in heat application.  
69-1670  
2
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
THERMOSTAT  
THERMOSTAT  
Y
G
O
B
W
R
RC OT  
OT  
Y
G
O
B
W
R
OT  
OT  
3
1
PILOTSTAT  
CONTROL  
(IF USED)  
COMPRESSOR  
CONTACTOR  
COOL  
DAMPER  
HEAT  
RELAY  
2
OUTDOOR  
TH  
TEMPERATURE  
SENSOR  
TH/  
PP  
FAN  
RELAY  
HEAT  
DAMPER  
OUTDOOR  
TEMPERATURE  
SENSOR  
LIMIT  
CONTROL  
PP  
2
MILLIVOLTAGE  
GENERATOR  
MILLIVOLTAGE  
GAS CONTROL  
1
L1  
HOT)  
(
1
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A  
SEPARATE CABLE FROM THE THERMOSTAT CABLE.  
L2  
TRANSFORMER  
M20270  
Fig. 6. T8602 typical millivoltage heating circuit.  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
.
2
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT  
PUMP SYSTEMS.  
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A  
FOR WRAPAROUND  
INSERTION STRIP  
FOR STRAIGHT INSERTION  
STRIP 5/16 IN. (8 MM).  
SEPARATE CABLE FROM THE THERMOSTAT CABLE.  
M10347A  
7/16 IN. (11 MM).  
Fig. 4. Typical hookup in heat and cool system  
with one transformer.  
M4826  
Fig. 7. Correct wiring technique.  
THERMOSTAT  
RC  
Y
G
O
B
W
R
OT  
OT  
Mounting Thermostat  
2
5
4
1.  
Engage tabs at the top of the thermostat and  
wallplate. See Fig. 8.  
COMPRESSOR  
CONTACTOR  
COOL  
DAMPER  
HEAT  
RELAY  
3
2. Press lower edge of case to close and latch.  
OUTDOOR  
TEMPERATURE  
SENSOR  
NOTE: To remove the thermostat from the wall, first pull  
out at the bottom of the thermostat; remove top  
last.  
FAN  
RELAY  
HEAT  
DAMPER  
3
1
L1  
HOT)  
L1  
(HOT)  
(
L2  
L2  
1
HEATING  
TRANSFORMER  
COOLING  
TRANSFORMER  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
A. ENGAGE TABS  
AT TOP OF  
THERMOSTAT  
AND WALLPLATE.  
2
3
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A  
ONE TRANSFORMER SYSTEM.  
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT  
PUMP SYSTEMS.  
4
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A  
SEPARATE CABLE FROM THE THERMOSTAT CABLE.  
5
T8600D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES.  
M10348  
Fig. 5. Typical hookup in heat and cool system  
with two transformers.  
B. PRESS LOWER  
EDGE OF CASE  
TO LATCH.  
M14628  
Fig. 8. Mounting thermostat on wallplate.  
3
69-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
configure Installer Setup,  
Using Thermostat Keys  
check Self-Test,  
The thermostat keys are used to:  
display outdoor temperature (select models),  
set current day and time,  
program times and setpoints for heating and cooling,  
temporarily override program temperatures,  
display present setting,  
See Fig. 9 for location of the keys.  
NOTE: Always press the keys with your fingertip or  
similar blunt tool. Sharp instruments like a pen  
or pencil point can damage the keyboard.  
INCREASE TIME SETTING  
OR SCROLL FORWARD  
THROUGH INSTALLER SETUP  
AND SYSTEM TEST  
SET WAKE TIMES  
AND SETPOINTS  
SET LEAVE TIMES  
AND SETPOINTS  
SET RETURN TIMES  
AND SETPOINTS  
INCREASE TEMPERATURE  
SETTING OR SCROLL  
FORWARD THROUGH  
INSTALLER SETUP OPTIONS  
DECREASE TEMPERATURE  
SETTING OR SCROLL  
BACKWARD THROUGH  
INSTALLER SETUP OPTIONS  
SET CURRENT  
DAY AND TIME  
RETURN TO  
NORMAL  
OPERATIONS  
DISPLAY INFORMATION  
SUCH AS PRESENT  
SETTINGS AND OUTDOOR  
TEMPERATURE  
ENTER  
INDEFINITE  
OR TIMED  
HOLD MODE  
Time  
Set Program  
Leave  
Return  
SET SLEEP TIMES  
AND SETPOINTS  
Run  
Program  
Set Current  
Day/Time  
Wake  
Sleep  
Cool  
Heat Off  
Heat/Cool  
Settings  
SYSTEM SWITCH  
FAN SWITCH  
Hold Temp  
Day  
System  
SET CURRENT OR  
PROGRAM DAY  
On  
Auto  
Daylight  
Time  
Copy  
Fan  
CHANGE BETWEEN  
DAYLIGHT SAVINGS  
AND STANDARD TIME  
DECREASE TIME SETTING OR  
SCROLL BACKWARD THROUGH  
INSTALLER SETUP AND SYSTEM TEST  
CHANGE BETWEEN  
HEATING AND COOLING  
SETPOINTS  
COPY ONE PROGRAMMED  
DAY TO ANOTHER DAY  
M14880  
Fig. 9. T8602D key locations and descriptions.  
SETTINGS  
Temperature Settings  
Refer to Table 2 for the default program. If the daytime  
energy savings period is not used, press the period key  
System and Fan Settings  
The system default setting is Heat and the fan default  
setting is Auto. Use the System and Fan keys to change  
the settings. See Fig. 10.  
(
Leave or Return) until the time is blank. See Owner’s  
Guide for complete instructions on changing the  
program.  
Table 2. Default Program Settings.  
System settings control the thermostat operation:  
Heat: The thermostat controls the heating.  
Off: Both the heating and cooling are off.  
Cool: The thermostat controls the cooling.  
Fan settings control the system fan:  
Period  
Time  
Heat Setpoint Cool Setpoint  
Wake  
6:00 AM  
70°F  
78°F  
(21°C)  
(25.5°C)  
Leave  
Return  
Sleep  
8:00AM  
62°F  
85°F  
On: Fan operates continuously.  
(
16.5°C)  
(29.5°C)  
Auto: Fan operates with equipment.  
5:00 PM  
10:00 PM  
70°F  
78°F  
(
21°C)  
(25.5°C)  
62°F  
82°F  
(
16.5°C)  
(28°C)  
Time  
Set Program  
Leave  
Return  
Run  
Program  
Set Current  
Day/Time  
Wake  
Sleep  
Cool  
Heat Off  
On  
Cool  
Heat  
Off  
Hold Temp  
Day  
H
S
e
e
at tt /i Cn go so l  
System  
On  
Auto  
System  
Daylight  
Time  
Copy  
Fan  
Auto  
Fan  
M14881  
Fig. 10. Thermostat System and Fan key locations.  
69-1670  
4
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
FAN OPERATION SWITCH  
The thermostat fan operation switch, labeled FUEL  
SWITCH in Fig. 11 is factory set in the F position. This is  
the correct setting for most systems. If your system is an  
electric heat system, set the switch to E. The E setting  
allows the fan to turn on immediately with the heating or  
cooling in a system where the G terminal is connected.  
— To advance to the next Installer Setup, press the  
Time  key.  
— To change a setting, use the increase  or  
decrease key.  
— To scroll the Installer Setup numbers backward, press  
the Time  key.  
To exit the Installer Setup, press Run Program.  
System  
Heat  
Wait Set Program Set Day/Time Temporary Setting  
Recovery  
Hold for  
AM  
Off  
Cool  
PM  
Days  
MonTue Wed Thu Fri Sat Sun Repl Batt Room  
Wake Leave Return Sleep  
DST  
Heat Cool  
M19014  
Fig. 12. Display of all LCD segments.  
FUEL SWITCH  
M12676  
Fig. 11. Fan operation switch.  
INSTALLER SETUP  
INSTALLER SETUP  
NUMBER DISPLAY  
(COLUMN 2 OF TABLE 3)  
FACTORY SETTING OR OTHER  
CHOICE DISPLAY (COLUMN 3  
OR 5 OF TABLE 3)  
NOTE: For most applications, the thermostat factory-  
settings do not require changing. Review  
M14618  
factory settings in Table 3 and if no changes are  
necessary, go to the Installer Self-Test section.  
Fig. 13. Display of Installer Setup number and  
setting.  
The Installer Setup is used to customize the thermostat  
to specific systems. Some of the options include  
temperature display and outdoor temperature display.  
Installer Setup numbers are listed in Table 3. The table  
includes all the configuration options and the factory  
settings for the T8602.  
IMPORTANT  
Only configurable numbers are shown on the  
device. Example: If thermostat does not have a  
system key, Installer Setup Number 12 will not  
be displayed. Review Table 3 factory-settings  
and mark any desired changes in the Actual  
Setting column. When Installer Setup is com-  
plete, review the settings to confirm that they  
match the system.  
A combination of key presses are required to use the  
Installer Setup feature:  
To enter the installer setup, press and hold the  
information i key with the increase and  
decrease keys until the first number is displayed.  
All display segments appear for approximately three  
seconds before the number is displayed. See Fig. 12  
and 13.  
5
69-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
Table 3. Thermostat Installer Setup Options.  
Installer Setup  
Number (Press  
Time  key to  
change)  
Other Choices  
(Press or key to change)  
Factory Setting  
Display Description  
Actual  
Select  
Display  
Description  
Setting  
Not Used.  
1 thru 3  
Heating cycle  
4
6
6—6 cph used for 1, 3 or 9 1—1 cph used for radiant  
rate.  
conventional heat  
floor heat, gravity system  
—3 cph used for hot water  
systems or high  
3
efficiency furnaces  
9
—9 cph used for electric  
heat systems  
Not Used.  
5 thru 12  
13  
0
1
Adaptive  
Intelligent  
Recovery™  
control.  
AdaptiveIntelligent  
Conventional recovery  
(system starts recovery at  
programmed time).  
Recovery™  
control is activated  
(system starts  
early so setpoint is  
reached by start of  
program period).  
Degree  
14  
0
Temperature is  
1
Temperature is displayed  
in °C  
temperature  
display  
displayed in °F  
Not Used.  
Clock format.  
15  
16  
0
1
12-hour clock  
24-hour clock format.  
format.  
Not Used.  
17 thru 23  
24  
0
1
Outdoor  
No outdoor  
temperature is  
displayed.  
Outdoor temperature is  
displayed. Needs a  
C7089B1000 Outdoor  
Temperature Sensor to  
operate.  
temperature  
display(models  
with OT  
terminals).  
Not Used.  
25 thru 32  
33  
5
Minimum off  
time for the  
compressor.  
5 minute minimum 0 thru 4  
Minimum number of minutes  
(0 thru 5) the compressor is  
off between calls for the  
compressor.  
off time for the  
compressor.  
Temperature  
range stops in  
heating.  
Temperature  
range stops in  
cooling.  
34  
35  
36  
90  
45  
Highest heating  
setpoint setting.  
40 to 89 Temperature range (1°F  
increments) of heating  
setpoint settings.  
Lowest cooling  
setpoint setting.  
46 to 99 Temperature range (1°F  
increments) of cooling  
setpoint settings.  
Not Used.  
69-1670  
6
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
Table 3. Thermostat Installer Setup Options. (Continued)  
Installer Setup  
Other Choices  
Number (Press  
Time  key to  
change)  
Factory Setting  
Display Description  
(Press or key to change)  
Actual  
Select  
Display  
Description  
Setting  
Temperature  
37  
0
No difference in  
3 thru -3 1—Display adjusts to 1°F  
higher than actual room  
temperature.  
display  
displayed  
adjustment.  
temperature and  
actual room  
2—Display adjusts to 2°F  
higher than actual room  
temperature.  
temperature.  
3
—Display adjusts to 3°F  
higher than actual room  
temperature.  
-
-
-
1—Display adjusts to 1°F  
lower than actual room  
temperature.  
2—Display adjusts to 2°F  
lower than actual room  
temperature.  
3—Display adjusts to 3°F  
lower than actual room  
temperature.  
Furnace Air  
Filter Timer.  
43  
2
90 days (calendar 0, 1, 3, 4 0 – off  
days)  
1 – 30 days  
3
4
– 180 days  
– 365 days  
(
Time is counted by calendar  
days in any mode.)  
Humidifier Pad  
Monitor.  
44  
45  
0
0
Off  
1, 2, 3  
1 – 90 days  
2 – 180 days  
3
– 365 days  
(
Time is counted by calendar  
days in heat mode.)  
Ultraviolet (UV)  
Air Treatment  
System Lamp  
Monitor.  
Off  
1
1 – 365 days  
(Time is counted by calendar  
days in any mode.)  
IMPORTANT  
Review the settings to confirm that they match  
the system. Press Run Program to exit the  
Installer Setup. The thermostat has saved the  
Installer Setup changes and initiated a reset in  
order to operate using the new settings. Be sure  
to set the current day and time immediately.  
7
69-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
Setting Current Day and Time  
1.  
Press Set Current Day/Time.  
Set Day/Time  
AM  
NOTE: On initial powerup or after an extended power  
loss, 1:00 pm flashes on the display until a  
key is pressed.  
Time  
Set Program  
Leave  
Return  
Daylight  
Time  
ProR  
g
u
r
n
am  
S
De at yC / uT ri mr e  
e
nt  
Wake  
Sleep  
Fan  
Hold Temp  
ay  
Settings  
Heat/Cool  
System  
Tue  
DaT  
y
i ml ig  
e
ht  
Copy  
DST  
M14622  
4.  
Press Run Program.  
Set Day/Time  
Time  
Set Program  
Leave  
Return  
PM  
Sys Ht ee ma t  
Set Current  
Day/Time  
ProR  
g
u
r
n
am  
S
De at yC / uT ri mr e  
e
nt  
Wake  
Sleep  
Fan  
AM  
Hold Temp  
Day  
H
S
eat tt /i Cn go so l  
e
System  
Mon  
Time  
Set Program  
Leave  
Return  
Run  
Program  
ProR  
g
u
r
n
am  
S
De at yC / uT ri mr e  
e
nt  
Wake  
Sleep  
Fan  
DaT  
y
i ml ig  
e
ht  
Copy  
Fan  
Hold Temp  
Day  
H
S
eat tt /i Cn go so l  
e
System  
Tue  
Wake  
Room  
M14619  
DST  
Auto  
DaT  
y
i ml ig  
e
ht  
Copy  
M14623  
2.  
Press Day until the current day is displayed.  
NOTE: Sun=Sunday, Mon=Monday,  
Tue=Tuesday, Wed=Wednesday,  
View or Reset Timer Settings  
When the thermostat activates a timer, the thermostat  
Thu=Thursday, Fri=Friday, Sat=Saturday.  
flashes Filter until the timer resets.  
1.  
Reset the timer by pressing the i key until the  
expired timer is displayed.  
Set Day/Time  
Time  
Set Program  
Leave  
Return  
PM  
ProR  
g
u
r
n
am  
S
De at yC / uT ri mr e  
e
nt  
Wake  
Sleep  
Fan  
Day  
Settings  
Heat/Cool  
Tue  
Hold Temp  
Day  
System  
DaT  
y
i ml ig  
e
ht  
Copy  
M14620  
Filter  
Days  
3.  
Press Time  or Time  until the current time is  
displayed.  
M20243  
NOTE: Tapping the Set Current Day/Time changes the  
time in one hour increments.  
2
.
.
Press the Time  key to reset the timer.  
Time  
Set Day/Time  
Filter  
Days  
AM  
Time  
Set Program  
Leave  
Return  
ProR  
g
u
r
n
am  
S
De at yC / uT ri mr e  
e
nt  
Wake  
Sleep  
Fan  
Hold Temp  
Day  
H
S
e
e
at tt /i Cn go so l  
System  
Tue  
DaT  
y
i ml ig  
e
ht  
Copy  
M14621  
M20244  
3
Press the Run Program key.  
NOTE: If the current time is Daylight Savings Time,  
press Daylight Time until DST is displayed.  
NOTE: You can view the number of days remaining at  
any time by pressing the i key three or four  
times. If more than one timer is active, all active  
timers show sequentially when pressing the  
i key several times.  
69-1670  
8
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
INSTALLER SYSTEM TEST  
Use the Installer System Test to check the thermostat  
operation. Refer to Table 4 for a list of the available  
system tests.  
System  
Heat  
Off  
Wait Set Program Set Day/Time Temporary Setting  
Recovery  
Hold for  
AM  
Cool  
PM  
Days  
CAUTION  
MonTue Wed Thu Fri Sat Sun Repl Batt Room  
Wake Leave Return Sleep  
DST  
Heat Cool  
Equipment Damage Hazard.  
Minimum compressor off-time is bypassed  
during Installer System Test.  
Avoid cycling compressor quickly.  
M19014  
Fig. 14. Display of all LCD segments.  
To start the system test:  
Press and hold the increase and decrease keys at  
the same time until 10 appears. All segments of the  
display will be displayed before the 10 appears.  
See Fig. 13 and 14.  
Table 4. Tests Available In Installer System Test.  
Test  
Number  
System Test Description  
Heating equipment can be turned on and off.  
Cooling equipment can be turned on and off.  
Fan equipment can be turned on and off.  
Keyboard keys test.  
M14612  
1
3
4
0-19  
0-39  
0-49  
Fig. 15. Display of test number.  
Refer to Table 5 for the directions and results of the  
specific tests.  
6
0 0 to  
6
0 19  
NOTE: Press Time  to advance to the next test and  
Time  to go back to the previous test. Press  
Run Program to exit the system test.  
Table 5. Installer System Test Options.  
Keys to  
Press  
Test  
Number  
Description  
Heating Equipment System Test  
Time ∆  
10  
11  
10  
Enter heating equipment system test.  
Heat comes on. When Installer Setup number 2 is 1, the system fan is also energized.  
Heat and system fan turn off.  
Cooling Equipment System Test  
Time ∆  
30  
31  
30  
Change from heating to cooling equipment system test.  
Cool and system fan come on.  
Cool and system fan turn off.  
Fan Equipment System Test  
Time ∆  
40  
41  
40  
Change from cooling to fan equipment system test.  
Fan comes on.  
Fan turns off.  
Key Operation System Test  
Time  60 2 Change from fan to key operation system test.  
NOTE: Press any key and the displayed numbers change. Press Time  to go to the previous test and Time  to go to  
the next test. The Run Program key will not exit this test. Press Time  or Time  and then the  
Run Program key to exit.  
9
69-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
THERMOSTAT INFORMATION  
1.  
Press the Time  key to access the thermostat  
4. Press the increase  key again to display the soft-  
information.  
ware revision number.  
(Example: 001 = Revision number 1).  
M14613  
M14616  
2
.
Press the increase key to display the production  
date code. The first two large digits are the month  
and the third digit is the last digit of the year.  
5
.
.
Press the increase key again to display the  
EEPROM identification code.  
(Example: 314 = EEPROM ID 314).  
(
Example: 027 = February 1997).  
M14617  
M14614  
6
Press the Run Program key to exit the System  
Test. The System Test times out after four minutes  
without any key presses.  
3.  
Press the increase key again to display the soft-  
ware identification code.  
(Example: 02 = software ID code 2).  
CHECKOUT  
Outdoor Temperature Sensor  
(
Select Models)  
Allow the outdoor temperature sensor to absorb the  
outdoor air for a minimum of five minutes before taking a  
reading.  
M14615  
69-1670  
10  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
TROUBLESHOOTING GUIDE  
Table 6. Troubleshooting Guide.  
Possible Cause  
Symptom  
Action  
Display does not  
Thermostat is not being  
• Check if batteries are present and installed correctly.  
— If batteries are present and installed correctly, replace  
thermostat.  
come on.  
powered.  
Temperature  
Room temperature display has Enter Installer Setup number 37 and reconfigure the display.  
display is incorrect. been reconfigured.  
Thermostat is configured for °F Enter Installer Setup number 14 and reconfigure the display.  
or °C display.  
Bad thermostat location.  
Relocate the thermostat.  
Temperature  
The upper or lower temperature Check the temperature setpoints:  
limits were reached. • Heating limits are 40 to 90°F (4.5 to 32°C)  
• Cooling limits are 48 to 99°F (7 to 37°C)  
settings do not  
change. (Example:  
Cannot set the  
heating higher or  
the cooling lower.)  
The setpoint temperature range Check Installer Setup numbers 34 and 35 and reconfigure the  
stops were configured.  
setpoint stops.  
Heating does not  
No power to the thermostat.  
• Check for 24 Vac between R and W terminals (check for  
come on.  
®
7
50 mV on PowerPile Systems).  
If missing 24 Vac:  
check if the circuit breaker is tripped—reset the circuit  
breaker.  
check if the system fuse is blown—replace the fuse.  
check if the power switch on the HVAC equipment is in  
the Off position—set to the On position.  
check wiring between thermostat and HVAC  
equipment—replace any broken wires and tighten any  
loose connections.  
If 24 Vac is present, proceed with troubleshooting.  
Thermostat minimum off time is Wait up to five minutes for the system to respond.  
activated.  
System selection is not set to  
Heat.  
Set system selection to Heat.  
Heating setpoint is below room Check heating setpoint. Set heating setpoint to desired  
temperature.  
temperature.  
Cooling does not  
come on.  
No power to the thermostat.  
• Check for 24 Vac between R or RC and Y terminals  
— If missing 24 Vac:  
check if the circuit breaker is tripped—reset the circuit  
breaker.  
check if the system fuse is blown—replace the fuse.  
check if the power switch on the HVAC equipment is in  
the Off position—set to the On position.  
check wiring between thermostat and HVAC  
equipment—replace any broken wires and tighten any  
loose connections.  
If 24 Vac is present, proceed with troubleshooting.  
Thermostat minimum off time is • Wait up to five minutes for the system to respond.  
activated.  
• Enter Installer Setup number 33. Reconfigure minimum off  
time (if required).  
System selection is not set to  
Cool.  
Set system selection to Cool.  
Cool setpoint is above room  
Check cooling setpoint. Set cooling setpoint to desired  
temperature.  
temperature.  
11  
69-1670  
href="
T8602C CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS  
Table 6. Troubleshooting Guide. (Continued)  
Symptom  
System on indicator Fan operation set for F  
flame=heat, (conventional heat) when it  
Possible Cause  
Action  
Set Fan Operation switch (Fuel switch).  
(
snowflake=cool) is should be set for E (electric  
displayed, but no  
warm or cool air is  
coming from the  
registers.  
heat).  
Conventional heating equipment Wait a minute after seeing the on indicator and then check the  
turns on the fan when the  
furnace has warmed up to a  
setpoint.  
registers.  
Heating or cooling equipment is Verify operation of heating or cooling equipment in self-test.  
not operating.  
Outdoor tempera- Option not activated.  
Enter Installer Setup number 24 and set to 1. Thermostat must  
have OT terminals and a C7089B1000 installed.  
a
ture not displayed  
Outdoor  
Outdoor sensor is connected  
incorrectly.  
Wrong sensor.  
Refer to C7089B1000 Installation Instructions and check wiring  
temperature  
between the thermostat and sensor.  
a
display is incorrect  
Thermostat  
Replace sensor with C7089B1000 Sensor.  
Backlight can fade over the life • Wait until Replace Battery indicator is illuminated and  
backlight appears of the batteries.  
replace batteries.  
dim.  
• Replace batteries now.  
a
Select models.  
Automation and Control Solutions  
Honeywell International Inc  
Honeywell Limited-Honeywell Limitée  
35 Dynamic Drive  
Scarborough, Ontario  
M1V 4Z9  
1
985 Douglas Drive North  
Golden Valley, MN 55422  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
69-1670 G.H. 1-03  
www.honeywell.com/yourhome  

White Rodgers 1F95 0680 Thermostat User Manual

Lux Products TX250 Thermostat User Manual

Honeywell T4039B Thermostat User Manual

Honeywell T8665D Thermostat User Manual

Honeywell TH1210DN Thermostat User Manual

Honeywell T874 Thermostat User Manual

White Rodgers 1F90 71 Thermostat User Manual

Honeywell TH8320WF Thermostat User Manual

White Rodgers 37E73A 918 Thermostat User Manual

Honeywell TG511 Thermostat User Manual