Aube TH150 Series Thermostat User Manual

Home

href="
TH150 Series  
Installation and User Guide  
VAV Thermostat  
1
. Introduction  
The TH150 Series electronic thermostat is designed for low-voltage  
pressure-dependent variable air volume (VAV) applications. It  
comes in four different models:  
TH150-1A  
• TH150-1F  
Configuration and status display  
TH150-1A2T  
• TH150-1F2T  
Depending on the model, the TH150 thermostat can have up to  
three outputs connected to the following control devices:  
Heating mode  
actuators  
thermal valves (N.O. and N.C.)  
solenoid valves  
solid-state relays (SSRs)  
silicon-controlled rectifiers (SCRs)  
mechanical relays  
Cooling mode  
Temperature display  
Temperature  
adjustment  
button  
Output power display  
contactors  
Accessories  
Override button  
RC840 or RC840T electromechanical relay  
RT850 or RT850T solid-state relay  
AC146-410 temperature sensor  
AC144-03 temperature sensor  
2
. Installation  
2
.1 Mounting Instructions  
2.2 Terminal Designations  
The designations of the terminals vary according to the particular  
model of thermostat. Refer to the following table for the description  
of each terminal.  
n Remove the thermostat from its base by unscrewing the cap-  
tive screw and tilting the bottom of the thermostat up. The  
screw cannot be completely removed.  
TERMINAL DESCRIPTION  
1
2
24 VAC  
COM  
Power supply  
Models TH150-1A and TH150-1A2T  
Models TH150-1F and TH150-1F2T  
3
4
AN1  
COM  
Output 1  
3
4
OPEN  
CLOSED  
5
6
T2/AN2  
T2/COM  
Output 2 (models TH150-1A2T and TH150-1F2T)  
7
8
T3  
T3  
Output 3 (models TH150-1A2T and TH150-1F2T)  
External sensor input. (For applications requiring  
9
COM  
o Pass the wires through the center hole of the base and secure  
10 SENSOR an external sensor, see section 4.2.)  
the base to the wall or onto an electrical box.  
9
11  
COM  
C-Over  
Mode Changeover input (N.O. contact). See sec-  
tion 5.5.2.  
p Wire the thermostat. See section 2.2 for terminal designations  
and section 3 for typical wiring diagrams.  
9
COM  
Night Setback activation input (N.O. contact).  
See section 5.6.  
12 NSB  
q Reinstall the thermostat onto its base and secure with the cap-  
tive screw.  
Note: To configure the terminals, see section 4.  
TH150  
400-150-000-C  
5/9/06  
1/6  
href="
3
. Typical Applications  
FIGURE 1: Damper control with electric reheat and auxiliary  
FIGURE 2: Damper control with electric reheat and auxiliary  
baseboard heating.  
hot-water heating  
FIGURE 3: Damper control with automatic changeover, elec-  
tric reheat and central cooling  
FIGURE 4: Temperature control of fresh air supply  
CAUTION  
CAUTION  
Do not connect  
common to ground  
Do not connect com-  
mon to ground  
FIGURE 5: Changeover and NSB inputs sharing the same  
FIGURE 6: Changeover and NSB inputs using different 24-Vac  
transformers  
24-Vac transformer  
TH150  
400-150-000-C  
5/9/06  
2/6  
href="
4
. Configuration  
n Remove the thermostat from its base and  
4
.1 Configuration Menus  
set the SW2 switch to MENU.  
o Reinstall the thermostat. The thermostat is  
now in configuration mode. The first digit  
flashes to indicate that the first item of the  
menu can now be modified.  
1
A model  
Default mode &  
Application  
Output 1  
min. opening  
(section 4.3.2)  
Maximum  
setpoint  
(section 4.6)  
Minimum  
setpoint  
(section 4.6)  
NSB value  
(section 5.6)  
Output 1 type  
(
section 4.2)  
p To modify the setting, use the up/down  
(
section 4.3.1)  
Cool / 0-10V  
Heat / 0-10 V  
Cool / 2-10 V  
Heat / 2-10 V  
0
Internal sensor  
Room  
0
1
2
3
1
2
3
4
5
6
7
8
9
1°C (2°F)  
2°C (4°F)  
3°C (6°F)  
4°C (8°F)  
5°C (10°F)  
6°C (12°F)  
7°C (14°F)  
8°C (16°F)  
9°C (18°F)  
0
1
2
3
4
5
0%  
arrows. Refer to the adjacent tables.  
1
2
3
4
5
10%  
20%  
30%  
40%  
50%  
Can be set  
between 35°C  
95°F) and  
’minimum  
Can be set  
between 10°C  
(50°F) and  
’’maximum  
setpoint - 1’’  
q Press Override to save the new setting and  
Return  
go to the next item.  
(
Supply  
Auto changeover  
Limited cooling  
r Repeat steps 3 and 4 for remaining items.  
setpoint + 1’’  
s When the configuration is done, set the  
Default value  
is 35°C (95°F) is 10°C (50°F)  
Default value  
SW2 switch back to NORMAL.  
1F model  
NOTE: Factory settings are  
inside the shaded cells.  
Output 1  
min. opening  
Output 1  
opening time  
(section 4.3.3)  
Maximum  
setpoint  
(section 4.6)  
Minimum  
setpoint  
(section 4.6)  
Application  
Default mode  
(section 4.3.1)  
NSB value  
(section 5.6)  
(section 4.2)  
(section 4.3.2)  
0
1
2
3
4
5
Internal sensor  
Room  
0
Cool  
1
2
3
4
5
6
7
8
9
1°C (2°F)  
2°C (4°F)  
3°C (6°F)  
4°C (8°F)  
5°C (10°F)  
6°C (12°F)  
7°C (14°F)  
8°C (16°F)  
9°C (18°F)  
0
0%  
0
1
2
3
4
5
6
7
8
80  
1
Heat  
1
2
3
4
5
10%  
90  
Can be set  
between 35°C  
Can be set  
between 10°C  
(50°F) and  
’’maximum  
setpoint - 1’’  
Return  
20%  
100  
110  
120  
130  
140  
150  
160  
(95°F) and  
Supply  
30%  
’’minimum  
Auto changeover  
Limited cooling  
40%  
setpoint + 1’’  
50%  
Default value  
is 35°C (95°F) is 10°C (50°F)  
Default value  
1A2T model  
Default mode &  
Output 1 type  
Output 3  
activation  
(section 4.5)  
Output 1  
min. opening  
(section 4.3.2)  
Maximum  
setpoint  
(section 4.6)  
Minimum  
setpoint  
(section 4.6)  
Output 2 typea  
(section 4.4)  
Application  
Output 3 type  
(section 4.5)  
NSB value  
(section 5.6)  
(section 4.2)  
(
section 4.3.1)  
Cool / 0-10V  
Heat / 0-10 V  
Cool / 2-10 V  
Heat / 2-10 V  
0
1
2
3
4
5
Internal sensor  
Room  
0
1
2
3
0
Not used  
0
Not used  
SSR 24 VAC  
N.C. Valve  
N.O. Valve  
Mech. relay  
Contact  
0
1
2
3
4
5
6
7
8
9
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
1
2
3
4
5
6
7
8
9
1°C (2°F)  
2°C (4°F)  
3°C (6°F)  
4°C (8°F)  
5°C (10°F)  
6°C (12°F)  
7°C (14°F)  
8°C (16°F)  
9°C (18°F)  
0
1
2
3
4
5
0%  
1
2
3
4
5
6
7
8
SSR 24 VAC  
N.C. Valve  
N.O. Valve  
Mech. relay  
SSR 3-32 V  
SCR 0-10 V  
Act. 0-10 V  
Act. / 2-10 V  
1
2
3
4
5
10%  
20%  
30%  
40%  
50%  
Can be set  
between 35°C  
95°F) and  
’’minimum  
Can be set  
between 10°C  
(50°F) and  
’’maximum  
setpoint - 1’’  
Return  
Supply  
(
Auto changeover  
Limited cooling  
setpoint + 1’’  
Default value  
is 35°C (95°F) is 10°C (50°F)  
Default value  
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).  
1
F2T model  
Output 3  
activation  
section 4.5)  
Output 1  
min. opening  
(section 4.3.2)  
Output 1  
opening time  
(section 4.3.3)  
Maximum  
setpoint  
(section 4.6) (section 4.6)  
Minimum  
setpoint  
Output 2 typea  
(section 4.4)  
Application  
Default mode  
(section 4.3.1)  
Output 3 type  
(section 4.5)  
NSB value  
(section 5.6)  
(section 4.2)  
(
0
1
2
3
4
5
Internal sensor  
Room  
0
Cool  
0
1
2
3
4
5
6
7
8
Not used  
0
1
2
3
4
5
Not used  
SSR 24 VAC  
N.C. Valve  
N.O. Valve  
Mech. relay  
Contact  
0
1
2
3
4
5
6
7
8
9
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
1
2
3
4
5
6
7
8
9
1°C (2°F)  
2°C (4°F)  
3°C (6°F)  
4°C (8°F)  
5°C (10°F)  
6°C (12°F)  
7°C (14°F)  
8°C (16°F)  
9°C (18°F)  
0
1
2
3
4
5
0%  
0
80  
1
Heat  
SSR 24 VAC  
N.C. Valve  
N.O. Valve  
Mech. relay  
SSR 3-32 V  
SCR 0-10 V  
Act. 0-10 V  
Act. / 2-10 V  
10%  
20%  
30%  
40%  
50%  
1
2
3
4
5
6
7
8
90  
Can be set  
between  
35°C (95°F) 10°C (50°F)  
and ’’min and ’’max  
setpoint + 1’’ setpoint - 1’’  
Can be set  
between  
Return  
100  
110  
120  
130  
140  
150  
160  
Supply  
Auto changeover  
Limited cooling  
Default  
value is  
Default  
value is  
35°C (95°F) 10°C (50°F)  
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).  
TH150  
400-150-000-C  
5/9/06  
3/6  
href="
4
.2 Application Types  
The following table shows the different default modes, the different  
output types for Output 1, and their corresponding settings in the  
configuration menu.  
The following table shows the different thermostat applications and  
their corresponding settings in the configuration menu.  
Menu setting  
1A & 1A2T models  
1F & 1F2T models  
Menu setting  
Description  
Cool / 0-10 V analog  
Cool  
0
Internal  
0
To control the ambient temperature using the internal  
(built-in) sensor  
(
max. of 10 min. refresh)  
(24 V tri-state floating)  
sensor  
Heat / 0-10 V analog  
(max. of 10 min. refresh)  
Heat  
1
2
3
To control the ambient temperature using the AC144-03  
temperature sensor (the internal sensor is not used)  
(24 V tri-state floating)  
1
2
Room  
Cool / 2-10 V analog  
(max. of 10 min. refresh)  
To control the temperature at the air return using the  
AC146-410 temperature sensor (the internal sensor is  
not used)  
Air return  
Heat / 2-10 V analog  
(
max. of 10 min. refresh)  
To control the temperature at the fresh air supply using  
the AC146-410 temperature sensor (the internal sensor  
is not used)  
4
.3.2 Minimum Opening  
3
4
Air supply  
The minimum damper opening can be set between 0 and 50 %.  
To control the ambient temperature using the internal  
sensor. The AC146-410 temperature sensor is used for  
automatic changeover. See section 5.5.1.  
Note: It is not recommended to set the minimum damper opening to  
0 % (fully closed) when a duct heater is connected to Output 2 or 3.  
Automatic  
changeover  
4
.3.3 Opening time (1F and 1F2T models only)  
To use the outdoor air for cooling whenever possible.  
The AC146-410 temperature sensor is used to measure  
the outdoor air temperature. The internal temperature  
sensor measures the room temperature which is then  
compared with the setpoint. If the room temperature is  
lower than the setpoint, the air intake damper remains  
closed. If the room temperature is higher than the  
setpoint, the latter is then compared with the outdoor  
temperature. If the fresh air temperature is lower than  
the setpoint by more than 3°C (5.4°F), the damper  
opens to allow cool air in.  
The damper opening time can be set between 80 and 160 seconds.  
4.4 Output 2 (models TH150-1A2T and TH150-1F2T)  
Limited  
cooling  
Output 2 controls heating only, regardless of the thermostat’s mode.  
When the thermostat is in heat mode, Output 2 is activated as soon  
as Output 1 reaches its full capacity. When the thermostat is in cool  
mode, Output 2 is activated when the measured temperature drops  
below the setpoint.  
5
4.3 Output 1  
Output 1 is used to control a damper. It controls heating when the  
thermostat is in heat mode or cooling when the thermostat is in cool  
mode.  
The following table shows the output types for Output 2 and their  
corresponding settings in the configuration menu.  
Menu setting Description  
0
Not used  
Set the following configuration parameters:  
24 VAC pulsed (triac) / 1 sec. cycle  
1
(
e.g., 24 V SSR such as Aube’s RT850 or RT850T)  
4 VAC pulsed (triac) / 10 min. cycle / direct action  
e.g., N.C. thermal valve)  
4 VAC pulsed (triac) / 10 min. cycle / reverse action  
e.g., N.O. thermal valve)  
4 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical  
Default mode  
Output type (1A and 1A2T models only)  
Minimum opening  
2
(
2
3
2
(
Opening time (1F and 1F2T models only)  
4
.3.1 Default Mode / Output Type  
2
4
5
6
relay such as Aube’s RC840 or RC840T)  
The default mode (heat/cool) is used for the following:  
0-10 V pulsed / 1 sec. cycle (e.g., 3-32 V SSR)  
The default mode is the thermostat’s mode at power-up.  
0
-10 V analog / 1 sec. refresh  
The default mode is the active mode when the N.O. changeover  
contact is open (see section 5.5.2).  
(e.g., SCR controlled device such as a re-heater)  
7
8
0-10 V analog / max. of 10 min. refresh (e.g., valve)  
2-10 V analog / max. of 10 min. refresh (e.g., damper)  
When configured as a contact (see section 4.5), Output 3 controls  
either heating or cooling depending on whether the default mode  
is set to heat or cool respectively.  
Note: If 0-4 is selected, set the SW6 switch to Triac. If 5-8 is  
selected, set the switch to Analog (see section 4.7)  
TH150  
400-150-000-C  
5/9/06  
4/6  
href="
4
.5 Output 3 (models TH150-1A2T and TH150-1F2T)  
4.7 DIP Switches  
The following table shows the output types for Output 3 and their  
corresponding settings in the configuration menu.  
Three switches at the back of the control module are used to select  
various options.  
Temperature Display (SW1)  
Menu setting Description  
Selects the desired temperature display (°C or °F).  
Access Mode (SW2)  
0
Not used  
4 VAC pulsed (triac) / 1 sec. cycle  
e.g., 24 V SSR such as Aube relays RT850 or RT850T)  
4 VAC pulsed (triac) / 10 min. cycle / direct action  
e.g., N.C. thermal valve)  
4 VAC pulsed (triac) / 10 min. cycle / reverse action  
e.g., N.O. thermal valve)  
4 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical  
2
(
1
Selects the operation mode (NORM) or the configuration mode  
(
MENU).  
2
(
2
3
4
5
Place the switch to MENU to access the configuration menu.  
Place the switch to NORM for normal display.  
2
(
Output 2 Type (SW6)  
2
Sets Output 2 type (Analog or Triac).  
relay such as Aube relays RC840 or RC840T)  
WARNING: Place the switch according to the type of device (Ana-  
log or Triac) connected to Output 2. Failure to do so can result in  
thermostat damage.  
N.O. contact (The contact closes when Output 1 reaches  
or exceeds set percentage. See section 4.1.)  
When any setting between 1 and 4 is selected, Output 3 controls  
heating only, regardless of the thermostat’s mode.  
5
. Operation  
5.1 Power-Up  
Upon power-up, the thermostat undergoes a series of test before  
displaying the actual temperature.  
Note: On the TH150-1F and TH150-1F2T models, at power-up, the  
message OPEN appears at the top of the screen during the calibra-  
tion of the damper opening. This can last up to 3 minutes.  
5
.2 Backlight  
To turn the backlight on, press any button. The display will illuminate  
for 12 seconds.  
When setting 5 is selected, Output 3 controls heating or cooling  
depending on whether the default mode has been set to heat or  
cool respectively (see section 4.3.1). For example, if the default  
mode has been set to heat mode, the contact remains opened when  
the thermostat is in cool mode. When the thermostat is in heat  
mode, the contact closes when Output 1 reaches a percentage of its  
capacity, set via the configuration menu.  
5.3 Temperature Display and Setting  
The thermostat usually displays the actual temperature. To view the  
setpoint, press once on one of the  
appears for 5 seconds and is indicated by the display. During the  
setpoint display, press one of the buttons to change it.  
buttons. The setpoint  
Note: The temperature setpoint is automatically increased or  
decreased by 1°C (2°F) when the controller switches to heating  
mode or to cooling mode respectively. For example, if the setpoint is  
at 25°C (77°F) in heating mode, it will become 26°C (79°F) in cool-  
ing mode and will return to 25°C (77°F) when the controller is back  
in heating mode.  
5.4 Output Display  
The bar graph represents the voltage for an analog out-  
put or the duty cycle for a triac output. The bar graph  
usually shows Output 1 power (% of damper opening).  
To view Output 2 or 3, press Override for 2 seconds to  
enter the diagnostic mode. Press Override momentarily  
to switch between the three output graphs. To exit the  
diagnostic mode, press Override for 2 seconds or wait  
for 1 minute for the mode to exit automatically.  
4
.6 Minimum and Maximum Setpoints  
The minimum and maximum setpoints are factory-set at 10°C  
50°F) and 35°C (95°F). The maximum setpoint can be set between  
5°C (95°F) and (minimum setpoint + 1). The minimum setpoint can  
(
3
be set between 10°C (50°F) and (maximum setpoint - 1).  
TH150  
400-150-000-C  
5/9/06  
5/6  
href="
5
.5 Mode Changeover  
6
. Technical Specifications  
The thermostat can switch between heat mode and cool mode  
either via:  
Power: 24 VAC  
Current consumption: 25 mA  
Output signals: Depends on output configurations  
Output ratings:  
the automatic changeover  
the changeover input  
-
-
-
Triac output: 0.5 A maximum @ 24 VAC  
Analog output (SCR connection): 0 - 10 V, 10 kW minimum  
Analog output (SSR connection): 0 - 10 V, 45 mA maximum  
5
.5.1 Automatic changeover  
In automatic changeover, the thermostat detects when the system  
switches between heat mode and cool mode by comparing the air  
supply temperature with the ambient temperature. If the thermostat  
is in heat mode, it switches to cool mode when the air supply is  
cooler than ambient by 5°C (9°F) or more. If it is in cool mode, it  
switches to heat mode when the air supply is warmer than ambient  
by 5°C (9°F) or more.  
Setpoint range: 10°C to 35°C (50°F to 95°F)  
Temperature display: 0°C to 60°C (32°F to 140°F)  
Temperature display resolution: 0.5°C (1°F)  
Mode hysteresis: 2°C (4°F)  
Automatic changeover deadband: 5°C (9°F)  
Duty cycle: Depends on output configurations  
NSB offset: Programmable 1°C to 9°C (2°F to 18°F)  
NSB override period: 2 hours  
Note: Neither the heat mode icon ( ) nor cool mode icon (  
)
Memory protection: Configuration and setpoint  
Temperature control: Proportional integral adaptive (P.I.A.)  
Operating temperature: 32°F to 140°F (0°C to 60°C)  
Storage temperature: -4°F to 122°F (-20°C to 50°C)  
Humidity limits: 0 to 95% R.H., non-condensing  
Dimensions: 69 x 118 x 27 mm (2.7 x 4.6 x 1.0 in.)  
appears when TH150 is placed in automatic changeover.  
5
.5.2 Changeover Input  
The thermostat is in the default mode when the contact between ter-  
minals 9 and 11 is open and switches mode when the contact is  
closed. The default mode is set via the configuration menu .  
Note: The changeover contact state is ignored if TH150 is config-  
ured in automatic changeover or in limited cooling.  
7
. WARRANTY  
5
.6 Night Setback  
Aube warrants this product, excluding battery, to be free from defects in the work-  
manship or materials, under normal use and service, for a period of three (3)  
years from the date of purchase by the consumer. If at any time during the war-  
ranty period the product is determined to be defective or malfunctions, Aube shall  
repair or replace it (at Aube's option).  
The Night Setback (NSB) mode is activated when the  
contact between terminals 9 and 12 is closed. When  
TH150 is in the NSB mode, indicated by the ECONO  
display, the temperature is lowered or raised by the set  
NSB value depending whether the thermostat is in heat  
mode or cool mode respectively. The NSB value is set via the con-  
figuration menu.  
If the product is defective,  
(
(
i)  
return it, with a bill of sale or other dated proof of purchase, to the place  
from which you purchased it, or  
contact Aube. Aube will make the determination whether the product  
should be returned, or whether a replacement product can be sent to you.  
ii)  
Night Setback Override  
This warranty does not cover removal or reinstallation costs. This warranty shall  
not apply if it is shown by Aube that the defect or malfunction was caused by  
damage which occurred while the product was in the possession of a consumer.  
Aube's sole responsibility shall be to repair or replace the product within the terms  
stated above. AUBE SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF  
ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES  
RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WAR-  
RANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PROD-  
UCT. Some provinces, states or regions do not allow the exclusion or limitation of  
incidental or consequential damages, so this limitation may not apply to you.  
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY AUBE MAKES ON  
THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUD-  
ING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PAR-  
TICULAR PURPOSE, IS HEREBY LIMITED TO THE THREE-YEAR DURATION  
OF THIS WARRANTY. Some provinces, states or regions do not allow limitations  
on how long an implied warranty lasts, so the above limitation may not apply to  
you.  
To temporarily override the NSB mode, press the Over-  
ride button. The NSB mode is lifted for the next 2 hours  
or until the Override button is pressed again. During the  
override, the normal setpoint is used and OVERRIDE is  
displayed.  
5
.7 Error Codes  
The following error codes can appear at the top of the display.  
E1: The internal temperature sensor is defective  
E2: The internal temperature sensor is shorted  
E3: The external temperature sensor is defective or not connected  
E4: The external temperature sensor is shorted  
This warranty gives you specific legal rights, and you may have other rights which  
vary from one province, state or region to another.  
8
. SERVICE  
If you have any questions on the product installation or operation, contact us at:  
7
05 Montrichard Avenue  
Saint-Jean-sur-Richelieu, Quebec  
J2X 5K8  
Canada  
Tel.: (450) 358-4600  
Toll-free: 1-800-831-AUBE  
Fax: (450) 358-4650  
Email: aube.service@honeywell.com  
For more information on our products, visit us at:  
www.aubetech.com  
TH150  
400-150-000-C  
5/9/06  
6/6  

Honeywell V8944B Thermostat User Manual

Carrier 33CS2PPRH 01 Thermostat User Manual

Honeywell L7248A,C,L Thermostat User Manual

White Rodgers 1F86 0244 Thermostat User Manual

Honeywell TH400 Thermostat User Manual

Honeywell SERIES 2000 Thermostat User Manual

Lux Products PSP721U Thermostat User Manual

Honeywell 69 1776EFS 01 Thermostat User Manual

Honeywell Q7300L Thermostat User Manual

Honeywell RTH8580WF Thermostat User Manual