E. Auto-Changeover
VI. PROGRAMMING THERMOSTAT SCHEDULES
When the thermostat mode is set to AUTO, the thermostat
will provide automatic changeover from Heating to Cooling
mode and Cooling to Heating mode when required. The ther-
mostat will automatically switch to maintain the desired
temperature setting. The thermostat does not need to be
manually changed from heating to cooling or cooling to heat-
ing operation.
Before programming the thermostat, plan the thermostat
daily schedule. The schedule is divided into 7 days (Monday
through Sunday). Each day has 4 time periods (OC1, UN1,
OC2, UN2). Each time period has a start time, heating set
point, and cooling set point. Fill in Table 1 on page 4 as an
aid to programming the daily schedules.
When choosing the times for OC1, UN1, OC2, and UN2, the
following rules must be followed:
NOTE: It is recommended that auto-changeover mode not be
used if the outdoor temperature is consistently lower than
•
The maximum number of hours allowed from OC1 to
UN1, or from OC2 to UN2 is 12 hours. For example, if
OC1 has a value of 6:00 AM and UN1 had a value of
5
0 F or greater than 80 F. In these cases, select heating or
cooling mode only.
5
:00 PM, this would be acceptable. If however, OC1 has
F. Unoccupied Override
a value of 6:00 AM and UN1 has a value of 7:00 PM, this
would not be acceptable because the difference is greater
than 12 hours.
The value of UN2 must be greater than or equal to the
value of OC2, while the value of OC2 must be greater
than or equal to the value of UN1, and the value of UN1
must be greater than or equal to OC1. For example,
acceptable values would be:
The Occupied button is only active during unoccupied peri-
ods. The Occupied button is inactive during occupied periods.
If the thermostat is in unoccupied mode and the user presses
the Occupied button, the set points are changed to the OC1
set points for heating and cooling. The OC1 icon will flash to
show the user that the thermostat is in override.
•
The thermostat will remain in override until the next sched-
uled time period or for the number of allowed override hours
programmed in the thermostat configuration (Option 18)
whichever comes first.
OC1
UN1
OC2
UN2
6
:00 AM
5:00 PM
5:00 PM
10:00 PM
In the example above, the thermostat will be occupied from
:00 AM to 10:00 PM. However, if the following values were
entered, the thermostat would not be occupied as one may
expect:
NOTE: If the set points are changed during unoccupied over-
ride, the unoccupied 1 (UN1) set points will be changed.
6
G. Smart Recovery (Heating Mode)
OC1
UN1
OC2
UN2
The smart recovery function is designed to save energy by
gradually adjusting temperatures to meet scheduled set
points. The thermostat has 2 schedule modes, normal occu-
pied mode and setback mode (a time when the space is unoc-
cupied). The Smart Recovery function begins 1 to 1.5 hours
before the scheduled occupied mode and gradually adjusts
room temperature so the temperature is at the occupied
mode set point when the occupied time period begins.
6
:00 AM
7:00 PM
6:00 PM
12:00 AM
In the new example, the thermostat will display UN2 from
2:00 AM to 6:00 AM, then OC1 from 6:00 AM to 6:00 PM,
then OC2 from 6:00 PM to 7:00 PM, then UN1 from
:00 PM to 12:00 AM. The thermostat, in this example,
would be occupied from 6:00 AM to 7:00 PM because OC2
has a value less than the value of UN1.
1
7
This is more efficient than making the system run at full
capacity until the desired temperature is met.
A. Programming Mode
To program the daily schedules, perform the following
procedure:
NOTE: Smart Recovery does not apply to cooling operation.
1
. Enter Programming mode by pressing the Program
button. The PROGRAMMING annunciator will
appear on the thermostat display. The current day of
the schedule will be displayed and the current pro-
gramming time period of that day will be displayed.
The TIME annunciator will flash.
III. SET CURRENT DAY
The Change Day button will change the day shown on the
thermostat display to the next day. If a schedule has been
entered, the thermostat will follow the schedule of the new
selected day.
IV. SET CURRENT TIME
NOTE: If a programming button is not pushed for 2 minutes,
the thermostat will exit Programming mode and any
changes made will be saved.
The Set Time/Temp button allows the user to change the
time displayed on the thermostat. Press the Set Time/Temp
button. The TIME annunciator will flash. Press the Up and
Down buttons until the correct time is shown. Hold down the
buttons to quickly move through the time display. The AM
and PM annunciators will automatically change. To ensure
the schedules are properly followed, make sure that AM or
PM is correct for the time chosen. When the correct time is
shown, press the End button to exit the Set Time mode.
2. Press the Up and Down buttons to set the start time
for the schedule day and period shown.
3
. Press the Set Time/Temp button once the correct
time is shown. The TIME annunciator will stop flash-
ing and the HEAT annunciator will flash.
4
. The heating and cooling set points can now be pro-
grammed. The HEAT and COOL annunciators will
flash for the heating and cooling set points respec-
tively. The Set Time/Temp button is used to toggle
between the time, heating, and cooling set points.
Use the Up and Down buttons to raise and lower the
temperature set points.
V. RESET FILTER
The Reset Filter function is used to clear the “Clean Filter”
icon on the display screen. The Reset Filter function is initi-
ated by pressing the Hold and Occupied buttons simulta-
neously. The “Clean Filter” icon reminds the user when it is
time to change or clean the filter of the unit.
NOTE: There must be at least 2 degrees difference between
the cooling and heating set points. The thermostat will auto-
matically change any set points closer than 2 degrees.
—
2—